Carrier 40VMV0012A Скачать руководство пользователя страница 12

12

ACB (Auxiliary Control Board) Interface — 

The

ACB interface is a dry contact board that can output up to four

signals  controlling  devices.  Refer  to  Fig.  14  for  connecting

devices to the ACB interface board.

Fig. 14 —ACB Interface

START-UP
Pre-Start Check

 Once installation is complete, make the

following pre-start checks:

1. All indoor and outdoor units are properly installed.

2. All piping and insulation is complete.

3. All electrical  connections (both power and control) are

properly terminated.

4. All condensate drains are installed correctly.

5. The power supply is of the right voltage and frequency. 

6. The  units  are  properly  grounded  in  accordance  with

current electrical codes. 

7. Suction  and  liquid  line  service  valves  are  in  open

position.

System Operation Check

  Once  the  installation  and

pre-start checks are completed, follow these steps:

1. Using remote controller, select cooling or heating mode

to check the operation of the system.

2. While the system is in operation, check the following on

indoor unit:

a. Switches  or  buttons  on  the  remote  controller  are

easy to push.

b. Indicator light is showing normal operation and no

error is indicated.

c. Swing  mode  of  air  louvers  is  working  (if

applicable to unit).

d. Drain pump operation is normal (if applicable).

e. No abnormal vibration or noise is noticed.

3. While the system is in operation, check the following on

outdoor unit:

a. No abnormal vibration or noise is noticed.

b. Condenser fan is in operation.

c. Indicator light is showing normal operation and no

error is indicated.

NOTE

:

 

If the unit  is turned  off or  restarted, there  is a time

delay of three minutes for the compressor to start from the time

the power is restored.

MAINTENANCE

Every 3 Months:

•   Check the air filter condition. Clean or replace if 

necessary.

Every 6 Months: 

Follow 3-month maintenance schedule. In addition:

•   Clean condensate tray with suitable cleaning agent.

•   Clean the grille and panel.

Every 12 Months:

 

Follow 6-month maintenance schedule. In addition:

•   Be sure all electrical connections are secure.

•   Check condensate pump operation.

•   Check the heating and cooling action to confirm 

proper operation.

INDOOR UNIT ADDRESSING

For  proper  system  operation,  each  indoor  unit  must  have  a

unique address set from 0 to 63. When setting an address by

remote controller; the outdoor units, indoor units, and MDC

must be powered on. If FE is displayed on the LED screen or

display board, this unit has no address. After setting all indoor

units’ addresses, turn off the power supply to all indoor units to

clear errors.

Indoor units’ addressing can be distributed automatically in the

heat pump system. When dip switch “S6” on the outdoor unit’s

main PCB board is set to 00 (default set  in factory), indoor

units are set for auto-addressing. When powering on for the

first time, it takes six minutes or more to finish auto-addressing

each indoor unit. The heat recovery system cannot accomplish

this function at this time.

Wireless Remote Controller (40VM900001) 

Indoor  unit  addressing  can  be  performed  using  the  wireless

remote controller. When using the wireless controller, the user

must maintain a line of sight with the receiver on the indoor

unit. See Fig. 15 for a description of the buttons on the wireless

remote.

LEGEND
ACB

— Auxiliary control board

AUXH

— Output for auxiliary heat

CTON

— Output for cooling operation

FAN

— Output for exhaust fan

HTON

— Output for heating operation

MAX AMPS

1A

MAX VOLTAGE

24V

CN50

CN51

FAN CTON HTON AUXH

CAUTION

When  servicing  or  repairing  this  unit,  use  only  factory-

approved  service  replacement  parts.  Refer  to  the  rating

plate on the unit  for complete unit model number, serial

number and company address. Any substitution of parts or

controls not approved by the factory will be at the owner’s

risk and may result in equipment damage.

CAUTION

To avoid equipment damage, do not attempt to reuse any

mechanical  or  electrical  controllers  that  have  been  wet.

Replace defective controller.

Содержание 40VMV0012A

Страница 1: ...ER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe p...

Страница 2: ...h Unit CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer tha...

Страница 3: ...700 840 1120 1260 EXTERNAL STATIC PRESSURE in wg 0 8 INDOOR UNIT NOISE LEVEL dBA High 37 6 41 6 46 2 52 2 46 9 53 0 57 1 Medium 34 5 37 1 42 3 48 4 44 1 48 5 52 6 Low 34 5 34 4 37 9 44 4 39 3 43 8 47...

Страница 4: ...ig 2 40VMV012A 054A Dimensions 40VMV UNIT SIZE A B C D 012A 030A 46 1 2 19 5 8 18 21 5 8 036A 054A 54 1 2 22 19 1 2 24 RIGHT SIDE A FRONT B C D DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT SIDE PIPE LI...

Страница 5: ...es in their parts of the installation Units must be installed in compliance with all applicable local code requirements IDENTIFYING AND PREPARING UNITS Be sure power requirements match available power...

Страница 6: ...een the bottom of the trap and outlet should also be three inches See Fig 4 Fig 4 Condensate Drain Trap Auxiliary drain should be connected and run to a location where it is easily visible when it bec...

Страница 7: ...rectly affected by the unit s discharge airstream Avoid external walls and drafts from window and doors Avoid positioning near shelves and curtains as these restrict air movement Avoid heat sources su...

Страница 8: ...CN3 CN18 CN31 CN54 CN4 CN15 CN19 CN8 CN21 CN12 CN26 CN14 CN25 CN52 CN17 CN9 To wired controller comm bus XP8 XP9 MDC unit comm bus To outdoor indoor P Q XT2 HA HB HA HB BLUE WHITE L1 L2 POWER IN P Q E...

Страница 9: ...cting Communication Wire to Outdoor Unit Communication Terminal CAUTION Failure to follow these procedures may result in personal injury or damage to equipment NEVER CONNECT the main power source to t...

Страница 10: ...o outdoor To Sub MDC To outdoor Indoor unit 1 L1 L2 L3 L3 L3 L3 L4 L5 L6 L7 L8 L9 L10 1 1 L Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA HB HA HB HA HB HA HB HA HB HA HB To...

Страница 11: ...it 5 Indoor unit 6 P Q HA HB HA HB HA HB HA HB HA HB HA HB Network Resistor Maximum wiring length L1 L3 3937 ft 18 AWG 2 Core Stranded Shield L5 3937 ft 18 AWG 2 Core Stranded Shield L6 L7 L8 L9 820 f...

Страница 12: ...ble cleaning agent Clean the grille and panel Every 12 Months Follow 6 month maintenance schedule In addition Be sure all electrical connections are secure Check condensate pump operation Check the he...

Страница 13: ...setting interface Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Access parameter settings as shown in Fig 18 Fig 18 Programmable Controller IDU...

Страница 14: ...DE STATUS NO ERROR Setting Temperature Starting Shutdown Standby Timing ON Timing OFF Setting Temperature System Defrost ON Setting Temperature System Defrost OFF ERROR dd Heating Cooling Mode Conflic...

Страница 15: ...e PC board E7 EEPROM Error Data Storage Chip or PC board fault Replace PC board E9 Communication Error Between Indoor Unit Controller Signal wires are short circuited or disconnected Check or reconnec...

Страница 16: ...de POSITION 2 OFF Normal Mode Default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF STANDARD INDOOR UNIT Default MODE PRIORITY INDOOR UNIT HP ONLY ON IDU...

Страница 17: ...ring replacement parts or contacting the factory about the unit This information can be found on the serial plates attached to the unit as shown in Figs 21 27 Fig 21 40VMV012 3 Unit Serial Plate Fig 2...

Страница 18: ...18 Fig 25 40VMV036 3 Unit Serial Plate Fig 27 40VMV054 3 Unit Serial Plate Fig 26 40VMV048 3 Unit Serial Plate...

Страница 19: ...s Fig D 40VMV030A Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 EXTERNAL STATIC PRESSURE in wg H speed 500 AIRFLOW cfm M speed L speed 700 300 600 400 Upper Limit of ESP 0 00 0 20 0 40 0 60 0 80 1 00 EXTER...

Страница 20: ...VMV048A Fan Curves Fig G 40VMV054A Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 700 800 900 1000 1100 1200 1300 1400 EXTERNAL STATIC PRESSURE in wg H speed M speed L speed Upper Limit of ESP AIRFLOW cfm 0...

Отзывы: