background image

2

GENERAL

The 40VML low static ducted indoor fan coil unit offers simple

operation and long service with proper installation, operation,

and regular maintenance.

The equipment is initially protected under the manufacturer’s

standard warranty; however, the warranty is provided under the

condition  that  the  steps  outlined  in  this  manual  for  initial

inspection,  proper  installation,  regular  periodic  maintenance,

and everyday operation of the unit be followed in detail. This

manual  should  be  fully  reviewed  in  advance  before  initial

installation, start-up, and any maintenance. Contact your local

sales representative or the factory with any questions before

proceeding.

See  Fig.  1  for  model  number  nomenclature.  Table 1  shows

components  that  may  or  may  not  be  used  for  a  particular

installation. Table 2 lists physical data for each unit size. Fig. 2

shows  unit  dimensions.  Figs.  3-7  show  fan  performance

curves.

Fig. 1 — Model Number Nomenclature

Table 1 —Components Shipped With Unit

WARNING

The  ducting  for  the  7K  (40VMM007--3)  and  9K

(40VMM009--3)  (supply  and  return  air  ducts)  is

intended  for  use  in  one  room  only.  Do  not  install

ductwork from a single unit to multiple rooms for these

two models.

CAUTION

DO NOT re-use compressor oil or any oil that has been

exposed to the atmosphere. Dispose of oil per local codes

and regulations. DO NOT leave refrigerant system open to

air any longer than the actual time required to service the

equipment.  Seal  circuits  being  serviced  and  charge  with

dry  nitrogen  to  prevent  oil  contamination  when  timely

repairs  cannot  be  completed.  Failure  to  follow  these

procedures  may  result  in  damage  to  equipment.  For

information about replacement oil type and viscosity, see

the Installation, Start-Up, and Service Instructions for the

38VMAH and 38VMAR outdoor units.

NAME OF ACCESSORY

OUTLINE

QUANTITY

USAGE

PQE connection wire

2

Connect outdoor unit, indoor unit, and sub MDC

Pipe insulation material

2

Heat insulation

Condensate connection

1

For drainage

Clamp

1

Connect the drain hose to condensate connection

Copper nut

1

Use for pipe connection

LED display panel

1

Operation and error display

Copper pipes

2

Use for inlet and outlet connection

Connecting wire

1

For occupancy sensor

No Beep Harness

1

Prevent beeping noise

     

LEGEND

VRF — Variable Refrigerant Flow

40

VM

L

007 - - -

3

Equipment Type

0

40

4

— Indoor Unit

Product Type

VM — VRF

Volta ge (V-Ph-Hz)

3  — 208/230-1-60

Blank

Model Type

L  — Low  Static Duct

Capacity (Btuh)

007 — 7,000
009 — 9,000
012 — 12,000

018 — 18,000

015 — 15,000

024 — 24,000

a40-1873

MANUAL OPERATION TIMER DEF./FAN ALARM

     

LEGEND

MDC — Multiport Distribution Controller

Содержание 40VML007-024

Страница 1: ...could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is th...

Страница 2: ...OT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the actual time r...

Страница 3: ...0 37 0 Medium 32 0 34 6 35 2 38 0 38 8 High 34 0 34 5 37 0 36 7 40 2 41 3 UNIT Unit Dimensions W x H x D in 30 3 4 x 8 1 4 x 19 3 4 39 1 4 x 8 1 4 x 19 3 4 48 x 8 1 4 x 19 3 4 Packing Dimensions W x...

Страница 4: ...015 018 36 1 4 39 3 8 28 7 8 32 1 4 7 7 8 37 3 4 024 44 7 8 48 37 5 8 41 46 1 2 AIR FILTER ELECTRICAL CONTROL BOX SIDE VIEW FRONT VIEW REAR VIEW BOTTOM VIEW P TOP VIEW SUSPENSION BRACKETS 4 P N 3 4 20...

Страница 5: ...M Low ax ESP er lim it of ESP P Upper limit of ESP p e r l i m Min ES U p M a x E S P i t o f E S P H S M S L S H S M S L S ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Poin...

Страница 6: ...ESP r l i m M L o w a x e E S P i t o f E S P Min p e r l i m ESP Upper limit of ESP U p M a x E S P i t o f E S P Fig 6 Size 018 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Ma...

Страница 7: ...ture theft vandalism and debris on jobsite Equipment covered in this manual is not suitable for outdoor installations Do not allow foreign material to fall into drain pan Prevent dust and debris from...

Страница 8: ...wo inches below the mounting brackets as shown in Fig 9 INSTALLING THE DUCT Connect the return and supply ducts to the duct collars provided on the unit Adequate distance between the return and supply...

Страница 9: ...piping The highest point in the condensate piping should be as close to the unit as possible See Fig 15 Condensate piping should slope downward in the direction of condensate flow with a minimum grad...

Страница 10: ...ge to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls...

Страница 11: ...let Pipe Temperature Sensor XP1 4 Connectors XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring EEV FM ALARM PUMP CN24 N3 CN1 C 8 CN2 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To wired c...

Страница 12: ...Connector 2 Strip a suitable length of the insulation layer as shown in Fig 20 below Fig 20 Stripping The Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communicat...

Страница 13: ...indoor To No 3 indoor To No 4 indoor To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoo...

Страница 14: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Страница 15: ...e unit ON in cooling mode The pump comes on Watch the end of the drain pipe for any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check an...

Страница 16: ...oller 40VM900001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor...

Страница 17: ...32 2 Press TEMP UP or TEMP DOWN to move the cursor and choose IDU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set as shown in Fig 33...

Страница 18: ...ting Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None Check...

Страница 19: ...board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance...

Страница 20: ...the default settings v POSITION 1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 IN...

Отзывы: