Step 6 — Position and Connect Controller  — 

Wired  controllers  should  be  installed  in  a  position  that

maintains good temperature control:
• Position  the thermostat approximately 48 inches above

floor level.

• Do not position the thermostat where it can be directly

affected by the unit’s discharge airstream.

• Avoid external walls and drafts from windows and doors.
• Avoid  positioning  near  shelves  and  curtains  as  these

restrict air movement.

• Avoid  heat  sources  such  as  direct  sunlight,  heaters,

dimmer switches, and other electrical devices.

• See  Fig.  18  for  an  example  of  communication  wire

connection.

CONTROL WIRING 

1. The  communication  wire  should  be  2-core  stranded

shielded cable.

2. For indoor unit and outdoor unit communication, use P,

Q terminals. Shielded core should be used for ground.

3. Wiring should be run according to the wiring diagram.

4. Communication wire must not form a closed loop.

Fig. 18 —Communication Wire Connection

OPTION/EXTENSIONS OF COMMUNICATION 

WIRING — To  extend  control  wiring  or  to  make  terminal

connections,  use  the  PQE  connection  wire  supplied  in  the

accessory kit and follow the steps below. 

1. Cut the connector on the outdoor unit side as shown in

Fig. 19 below.

Fig. 19 —Shearing Outdoor Connector

2. Strip a suitable length of the insulation layer as shown in

Fig. 20 below. 

Fig. 20 —Stripping The Wire

3. Use a suitable screwdriver to fix the communication wire

on the outdoor unit communication terminal as shown in

Fig. 21 below.

If communication wires are used to connect indoor units, find

the corresponding port and plug it in as shown in Fig. 22.

Fig. 22 —Connecting the Communication Wires

If it is not possible to buy communication wires from Carrier,

connect the indoor unit side of communication wires using the

connector provided with the accessories as shown in Fig. 23.

See Fig. 24 and 25 for typical communication wiring of the

heat pump and the heat recovery systems.

LEGEND

ACB

Auxiliary Control Board

To outdoor/indoor/MDC units

comm. bus

To wired controller comm. bus

XT2

CAUTION

Failure to follow these procedures may result in personal

injury or damage to equipment.

NEVER CONNECT the main power source to the control

or communication terminal block.

USE AN APPROPRIATE SCREWDRIVER for 

tightening the terminal screws. Do not over tighten the 

terminal screws.

IMPORTANT:  Wiring  for  communication  shall  be  two

inches or more apart from power source wiring to avoid

electric  noise.  Do  not  insert  control/communication  and

power source wire in the same conduit.
Pay attention to polarity of the communication wire.

Fig. 21 — Connecting Communication Wire to 

Outdoor Unit Communication Terminal

Содержание 40VML007-024

Страница 1: ...could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is th...

Страница 2: ...OT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the actual time r...

Страница 3: ...0 37 0 Medium 32 0 34 6 35 2 38 0 38 8 High 34 0 34 5 37 0 36 7 40 2 41 3 UNIT Unit Dimensions W x H x D in 30 3 4 x 8 1 4 x 19 3 4 39 1 4 x 8 1 4 x 19 3 4 48 x 8 1 4 x 19 3 4 Packing Dimensions W x...

Страница 4: ...015 018 36 1 4 39 3 8 28 7 8 32 1 4 7 7 8 37 3 4 024 44 7 8 48 37 5 8 41 46 1 2 AIR FILTER ELECTRICAL CONTROL BOX SIDE VIEW FRONT VIEW REAR VIEW BOTTOM VIEW P TOP VIEW SUSPENSION BRACKETS 4 P N 3 4 20...

Страница 5: ...M Low ax ESP er lim it of ESP P Upper limit of ESP p e r l i m Min ES U p M a x E S P i t o f E S P H S M S L S H S M S L S ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Poin...

Страница 6: ...ESP r l i m M L o w a x e E S P i t o f E S P Min p e r l i m ESP Upper limit of ESP U p M a x E S P i t o f E S P Fig 6 Size 018 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Ma...

Страница 7: ...ture theft vandalism and debris on jobsite Equipment covered in this manual is not suitable for outdoor installations Do not allow foreign material to fall into drain pan Prevent dust and debris from...

Страница 8: ...wo inches below the mounting brackets as shown in Fig 9 INSTALLING THE DUCT Connect the return and supply ducts to the duct collars provided on the unit Adequate distance between the return and supply...

Страница 9: ...piping The highest point in the condensate piping should be as close to the unit as possible See Fig 15 Condensate piping should slope downward in the direction of condensate flow with a minimum grad...

Страница 10: ...ge to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls...

Страница 11: ...let Pipe Temperature Sensor XP1 4 Connectors XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring EEV FM ALARM PUMP CN24 N3 CN1 C 8 CN2 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To wired c...

Страница 12: ...Connector 2 Strip a suitable length of the insulation layer as shown in Fig 20 below Fig 20 Stripping The Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communicat...

Страница 13: ...indoor To No 3 indoor To No 4 indoor To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoo...

Страница 14: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Страница 15: ...e unit ON in cooling mode The pump comes on Watch the end of the drain pipe for any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check an...

Страница 16: ...oller 40VM900001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor...

Страница 17: ...32 2 Press TEMP UP or TEMP DOWN to move the cursor and choose IDU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set as shown in Fig 33...

Страница 18: ...ting Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None Check...

Страница 19: ...board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance...

Страница 20: ...the default settings v POSITION 1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 IN...

Отзывы: