background image

5

Fig. 4 —Threaded Rod

Step 4 — Connect Piping

CONDENSATE PIPING  — The unit is supplied with a 

1 inches OD drain connection to connect copper or PVC drain 

piping as shown in Fig. 5.

When installing condensate piping, follow these 

recommendations:
• Condensate piping should slope downward in the

direction of condensate flow, with a minimum gradient

of 1 in. per 100 inches.

• Condensate piping must not be installed where it may be

exposed to freezing temperatures.

• Condensate pipe hangers should be spaced 59 in. or less

between hangers.

• For additional recommendations see Fig. 6.

REFRIGERANT PIPING

When connecting refrigerant piping follow these

procedures:
• The refrigerant piping should be dry and free of dust and

other impurities.

• The number of bends in the refrigeration piping must be

fewer than 15.

• The bending angle of the refrigerant pipe should not

exceed 90 degrees and the bending radius should be as

large as possible to prevent any breakage in piping.

• Use a torque wrench for flare nuts. Refer to Table 3 for

flare nut torque recommendations.

Table 3 — Flare Nut Torque Recommendations

• Before connecting any piping to the MDC cut the tips off

every gas and liquid pipe of the MDC unit to release the

gas in the system as shown in Fig. 7, even if the pipe is

not being used for this installation.

PIPING BETWEEN MDC AND INDOOR UNIT — 

When connecting indoor units to an MDC follow these

procedures:
• Check maximum height drop and length of refrigerant

piping between the indoor units and MDC. To ensure the

drop and length are acceptable, refer to the refrigerant

piping allowable limits in the manual.

• Refrigerant piping connection between indoor units

should be performed once the units are secured at their

respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the MDC. 

• Before insulating the suction and liquid refrigeration

pipes, perform pressure and leak tests. For details, see

the outdoor unit installation manual. Insulating both

suction and liquid refrigerant pipes is mandatory.

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

CAUTION

Multiport Distribution Controller’s (MDCs) are shipped

from the factory with brazed caps on all lines and

pressurized with nitrogen to keep the system clean.

Cutting the tip relieves the pressure in the system. Cut

all the tips on the MDC piping prior to removing any

brazed caps. Failure to cut the tip before removing the

brazed cap may cause equipment damage or personal

injury.

a40-1722

Fig. 5 — Connecting the Condensate Drain

(1[

ĭ

25])

Hard PVC binder

Condensate outlet

pipe

Drain pan

Clamp

Condensate connection

PVC water

Fig. 6 — Space Required for Condensate Drain 

Installation

Pipe hanger

59” or less

Refrigerant pipe

(Gradient: 1 in. per 100 in.)

Minimum 2”

Ceiling

7 7/8”  or more

     59” or less

Outside Diameter (in.)

Recommended Torque (ft-lb)

1/4

15

3/8

26

1/2

41

5/8

48

CAUTION

MDCs are shipped from the factory with brazed caps on

all lines and pressurized with nitrogen to keep the

system clean. Failure to remove the brazed cap before

connecting piping will result in equipment malfunction

or damage.

Fig. 7 — Cutting the Tip off the Gas and Liquid 

Lines

c

a

b

LEGEND

a

Brazed Cap

b —

Cut Here

c

MDC Unit

Содержание 40VMD 008

Страница 1: ...1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in...

Страница 2: ...required to service the equipment Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed Failure to follow these procedures may...

Страница 3: ...fasten the connector between flexible condensate pipe and MDC condensate Condensate connection 2 Reducer for smaller pipe diameter only for size 018 unit PQE connection wire No of Ports 3 Connect out...

Страница 4: ...o determine if shipping screws are to be removed Remove screws as directed Step 2 Position the Unit Install the unit in a location that meets the following requirements Allow adequate space for instal...

Страница 5: ...e acceptable refer to the refrigerant piping allowable limits in the manual Refrigerant piping connection between indoor units should be performed once the units are secured at their respective instal...

Страница 6: ...6 Connecting Liquid Pipes to the Indoor Unit LEGEND Table 7 Combination Table INDOOR UNIT kBtu h LIQUID SIDE in GAS SIDE in 5 7 9 12 15 1 4 1 2 18 24 30 36 48 54 3 8 5 8 72 3 8 7 8 96 3 8 7 8 a c b L...

Страница 7: ...ecommended nitrogen flow rate is approximately 1 76 ft3 h This is brazing sequence for Note that the flow capacity through this system is limited so you cannot blow through the lines with a high flow...

Страница 8: ...C and the Y joint Table 8 Piping Between the MDC and Y Joint PIPING BETWEEN MDC AND SUB MDC 3 pipes are used to connect the main MDC and the sub MDC Selection of the Sub MDC should follow the requirem...

Страница 9: ...to a Single Sub MDC Fig 12 Connecting Main MDC to Two Sub MDCs Main MDC unit Outdoor unit Indoor Sub MDC1 Sub MDC2 unit Indoor Indoor unit High pressure pipe pipe Low pressure Liquid pipe High pressu...

Страница 10: ...13 For a typical example of running the refrigerant pipes see Fig 14 INDOOR UNIT CAPACITY kBtu h CONNECTION DIAGRAM 72 73 108 109 168 a MDC Unit b Sub MDC Pipe Accessory c Pipe 3 4 d Cut Here e Pipe 7...

Страница 11: ...r PS Pressure Sensor SV A SV B SVM SVP Solenoid Valve Tm Temperature Sensor Check valves PS3 Tm2 SVP EXVA Tm3 SV1A 1 SV1B 1 SVmA n SVmB n HEX2 separator Gas Liquid Tm3 Tm1 Tm2 SVMC EXVB EXVC SVME SVP...

Страница 12: ...O 1 Sub MDC Unit MDC Indoor NO 1 Indoor NO 2 Indoor NO 3 Indoor NO 4 Indoor NO 5 Indoor MDC Outdoor or Sub MDC Outdoor Sub MDC NO 1 Sub MDC Unit 6 5 4 3 1 2 Main MDC Unit Indoor Unit NO 3 NO 4 Indoor...

Страница 13: ...e outdoor unit should be in the closed position throughout the refrigerant piping process Failure to follow this procedure may result in equipment damage OUTDOOR MODEL kBtu h HIGH PRESSURE SIDE in LOW...

Страница 14: ...pe 1 1 8 g ODU Pipe Accessory h Pipe 1 3 8 k Pipe 1 5 8 WARNING Electrical shock can cause personal injury and death Disconnect power supply before making wiring connections There may be more than one...

Страница 15: ...his might cause disturbance on the controls side Use 2 core stranded shielded twisted pair communication wire Make sure the control wire does not form a closed loop The control wire is polarity sensit...

Страница 16: ...Indoor unit 5 Indoor unit 6 Outdoor Unit Centralized Controller No N Sub MDC unit 1 Touch Screen Wired Controller HA HB HA HB HA HB HA HB HA HB P Q P Q P Q P Q P Q P Q wired controller HA HB To No 1...

Страница 17: ...ommunication bus 75 16 250 5 75 16 M O M O CN10 CN12 CN51 TRANS OUT TRANS IN CN53 CN55 S3 CN41 EXVA T3 CN1 CN45 T1 T2 CN43 CN44 690 690 OXH 5HG OXH 5HG UHHQ XT1 1 M I 2 M I CN13 UHHQ URZQ 5HG KLWH OXH...

Страница 18: ...1 DSP2 CN53 CN52 CN51 EXVA EXVB EXVC CN27 WATER T3 CN25 CN20 T1 T2 HOORZ ODFN OXH 5HG OXH 5HG OXH 5HG UHHQ UHHQ UHHQ UHHQ UHHQ UHHQ URZQ 5HG KLWH OXH URZQ 5HG KLWH OXH URZQ 5HG KLWH OXH URZQ 5HG KLWH...

Страница 19: ...e as the actual quantity DISPLAY DSP1 AND DSP2 DISPLAY DEFINITION S E0 Communication error with outdoor unit S E1 T1 temperature sensor error S E2 T2 temperature sensor error S E3 T3 temperature senso...

Страница 20: ...7 the switch must be set to OFF OFF or ON ON v POSITION 1 2 S1 IDU PIPES SETTING OFF OFF Normal Mode default ON ON 2 Ports Twinned Together Fig A S1 S3 S5 and S7 Settings POSITION 1 2 S3 IDU PIPES SET...

Отзывы: