background image

19

Fig. 9 — Typical Evaporator Coil Connections (40RU)

Fig. 10 — TXV Sensing Bulb Location

Chilled Water Piping

See Tables 5 and for chilled water connection sizes. For ease in

brazing, it is recommended that all internal solder joints be made

before unit is placed in final position.

Knockouts  are  provided  in  the  unit  corner  posts  for  40RUS

refrigerant piping. Additional field-fabricated access holes are re

-

quired  for  40RUS  chilled  water  piping.  See  Fig.  7,  which  lists

recommended knockouts and access holes to use for each 40RUS

unit size.

To size, design, and install chilled water piping, consult the Carrier

System Design manual. See Fig. 11 for an example of a typical in

-

stallation. Recommended fittings are listed in Table 11.

To access 40RUS coil vents and drains, remove the unit side panel

over  the  coil  header.  Vent  and  drain  plugs  are  on  the  top  and

bottom of header, respectively. See the Service section for infor

-

mation on preventing coil freeze-up during winter.

FIRST ON/LAST  OFF  = B

VERTI CAL I NSTALLATI ON

FIRST ON/LAST OF F = A

HORIZONTAL INSTALLATIO N

LEGEND

TXV —

 Thermostatic Expansion Valve

NOTE: The 8 o’clock position is shown above.

Содержание 40RU 07-16

Страница 1: ...performed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply...

Страница 2: ...1 2 ft 762 mm Right Side 3 1 2 ft 1067 mm Left Side 2 1 2 ft 762 mm For units equipped with an economizer refer to the accessory installation instructions for additional clearance requirements Be sur...

Страница 3: ...only 4 Example 0 R U A A 1 2 A 1 A 6 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Packaging 0 Standard Future Use A Standard Cabinet Paint 0 None 1 Painted Future Use A Standard Revision Num...

Страница 4: ...4 Fig 2 Dimensions Sizes 07 12...

Страница 5: ...5 Fig 2 Dimensions Sizes 07 12 cont...

Страница 6: ...6 Fig 3 Dimensions Size 14 and 16...

Страница 7: ...7 Fig 3 Dimensions Size 14 and 16 cont...

Страница 8: ...12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins in 4 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 2 1 1 8 DX Co...

Страница 9: ...ts per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins m 4 591 4 591 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1...

Страница 10: ...Split 15 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 D...

Страница 11: ...9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 4 591 4 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liqu...

Страница 12: ...3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Chilled Water Out 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Stea...

Страница 13: ...3 591 3 591 3 591 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Chilled Water Out 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8...

Страница 14: ...suspension technique The unit needs support underneath to prevent sagging Unit Isolation Where extremely quiet operation is essential install isolators be tween floor and base of unit or between ceili...

Страница 15: ...s coils for all 40RUA 07 08 12 14 and 16 and 40RUQ 07 08 and 12 units 40RUQ 16 units as well as 40RUS 08 12 14 and 16 units require additional holes that must be field fabricated to accommodate the p...

Страница 16: ...ZE 8 GA 1 1113 12 3 16 1 G5 40RUA 08 4 Row 1 BBIZE 6 GA 1 1136 15 1 4 1 G5 40RUQ 08 4 Row 1 BBIZE 8 GA 1 1113 12 3 16 1 G5 40RUA 12 4 Row 2 BBIZE 4 GA 2 1135 9 1 4 2 G3 40RUQ 12 4 Row 2 BBIZE 5 GA 2 1...

Страница 17: ...ng Radius Elbow 1 1 8 Nipple 12 L 1 1 8 Long Radius Elbow 40RUQ 12 1 Suction Lower 2 1 1 8 Street Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 5 1 2 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Stre...

Страница 18: ...le 7 L 1 3 8 Long Radius Elbow 7 Supply Upper 1 3 8 Long Radius Elbow 1 3 8 Nipple 11 3 4 L 1 3 8 Long Radius Elbow Table 11 Fitting Requirements cont UNIT ACCESS HOLE NO CONNECTION TYPE CIRCUIT FITTI...

Страница 19: ...commended knockouts and access holes to use for each 40RUS unit size To size design and install chilled water piping consult the Carrier System Design manual See Fig 11 for an example of a typical in...

Страница 20: ...static pressure created by fans preventing complete drainage Conditions will worsen as filters become dirty Install clean out plugs in trap Pitch drain line downward to an open floor drain or sump Pr...

Страница 21: ...ontactor coil data Fig 14 Disconnect Switch and Unit Adjustment Slots Both Ends of Unit PVC Stub Unit Drain Connection WARNING Failure to follow this warning could result in personal injury or death D...

Страница 22: ...40RUQ 16 208 230 3 60 187 253 3 7 2 76 10 2 13 0 20 460 3 60 414 506 3 7 2 76 4 8 6 0 15 575 3 60 518 632 3 0 2 24 3 8 5 0 15 Table 13 Electrical Data Alternate Motors Single Speed UNIT V PH Hz VOLTA...

Страница 23: ...20 460 3 60 414 506 3 7 2 76 4 9 7 0 15 575 3 60 518 632 3 7 2 76 4 5 6 0 15 Table 15 Electrical Data Alternate Motors Two Speed UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA MINIMUM C...

Страница 24: ...Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclosure and 40RU power entry location Inst...

Страница 25: ...on on the units corner post Fan motors are factory installed on all units Indoor fan contactors are located in the fan contactor box behind the side access panel See Fig 15 and 16 Wire the thermostat...

Страница 26: ...using return air ductwork route return air duct to the unit s return air inlet near the filter rack using a canvas connection to prevent transmission of unit vibration If the duct blocks off the unit...

Страница 27: ...27 Fig 18 Typical Fan Discharge Connections for Multiple Fan Units Fig 19 Duct Flange Installation...

Страница 28: ...ntation When service is completed replace unit panels Panels Panels are fastened to unit frame with sheet metal screws Fan and coil compartment must be sealed tightly after service to prevent air from...

Страница 29: ...Adjustment Loosen the 2 locking bolts holding the fan wheel hub to shaft See Fig 22 Position fan wheel in center of the fan housing and tight en locking bolts Clearance between wheel and housing shoul...

Страница 30: ...ining water Reinstall plugs and side panel Alternative freeze protection methods follow Circulate hot water within the water coil s supply main or supplementary space heating Close off supply lines to...

Страница 31: ...ical Manufacturers Association Table 19 Fan Motor Data 40RUA Q S Alternate Motor Single Speed English UNIT 40RUA Q 07 40RUA Q S 08 40RUS 10 40RUA Q S 12 40RUA S 14 40RUA Q S 16 208 230 1 60 Speed rpm...

Страница 32: ...HZ 56HZ 56HZ Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 22 2 NEMA National Electrical Manufacturers Association Table 22 Fan Motor Data 40RUA Q S Alternate Motor Single Speed SI UNIT 40RUA Q 07 40RUA Q S 0...

Страница 33: ...ciency 40RUA S Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 2 4 80 0 2 9 86 5 3 7 83 6 5 0 89 5 89 5 EPACT Energy Policy and Conservation Act of 1992 Table 26 Fan Motor Data 40RUA S Standar...

Страница 34: ...1 1 8 Table 30 Motor Efficiency 40RUQ Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 1 7 82 0 2 4 80 0 2 9 86 5 3 7 83 6 3 7 87 9 5 0 89 5 87 9 EPACT Energy Policy and Conservation Act of 199...

Страница 35: ...SHAFTS CENTER DISTANCE IN 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 34 Medium Static Drive Data 60 Hz English UNIT 40RUA Q 07 40RUA Q S 08 40RUS 10 40RUA Q S 12 40...

Страница 36: ...1200 1200 Change per 1 2 Turn of Moveable Motor Pulley Flange 24 6 28 7 28 7 28 7 19 4 18 4 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 6 6 SHAFTS CENTER DISTANCE IN 10 44 12 32 10 44 12 32 10 44 12 3...

Страница 37: ...0 20 0 20 0 20 0 20 0 20 0 Change per 1 2 Turn of Moveable Motor Pulley Flange 0 328 0 360 0 360 0 360 0 352 0 278 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 6 6 SHAFTS CENTER DISTANCE MM 265 313 265...

Страница 38: ...0 0 97 833 1 08 2975 462 0 60 556 0 72 634 0 84 701 0 95 762 1 06 818 1 18 870 1 29 3400 527 0 80 612 0 93 684 1 06 748 1 18 806 1 30 860 1 41 910 1 53 3825 593 1 05 670 1 18 737 1 31 797 1 44 852 1 5...

Страница 39: ...1 29 975 1 40 1018 1 50 1059 1 61 2975 919 1 40 965 1 51 1009 1 62 1050 1 73 1090 1 84 3400 957 1 64 1002 1 76 1044 1 87 1085 1 98 1124 2 10 3825 998 1 92 1041 2 04 1082 2 16 1122 2 27 1160 2 39 4250...

Страница 40: ...00 7 70 0 45 9 27 0 54 10 57 0 63 11 68 0 71 12 70 0 79 13 63 0 88 14 50 0 96 1600 8 78 0 60 10 20 0 69 11 40 0 79 12 47 0 88 13 43 0 97 14 33 1 05 15 17 1 14 1800 9 88 0 78 11 17 0 88 12 28 0 98 13 2...

Страница 41: ...3 0 88 15 52 0 96 16 25 1 05 16 97 1 12 17 65 1 20 1400 15 32 1 05 16 08 1 13 16 82 1 21 17 50 1 29 18 17 1 37 1600 15 95 1 23 16 70 1 31 17 40 1 40 18 08 1 48 18 73 1 57 1800 16 63 1 43 17 35 1 52 18...

Страница 42: ...Fig 15 and 28 4 Reverse the procedure to install new filters To install new filters in larger units that have 2 fans follow the preceding steps but use the factory supplied filter hook to slide filter...

Страница 43: ...ding main power supply TIGHT Y N ______________ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS Y N _________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE...

Страница 44: ...__ ____________ INDOOR UNIT ENTERING AIR DB TEMP ______________ ____________ INDOOR UNIT ENTERING AIR WB TEMP ______________ ____________ INDOOR UNIT LEAVINGAIR DB TEMP ______________ ____________ IND...

Отзывы: