40MBAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
CONNECTORS (CONT.)
Table 2 — Unit Configuration Settings
DIAL CODE
FEATURES
ON
OFF (DEFAULT)
S3
Electric heating turns on outdoor T4 temperature
0 (zero) means that the temperature protection is not turned on.
1 through F maps to -4°F through 46°F (-20°C through 8°C).
Each increment represents 3.6°F (2°C).
SW1-1
Whether 24V control selection
YES
NO
SW1-2
Cold wind protection option
NO
YES
SW1-3
Single cooling/heating and cooling options
Cooling
Heating and Cooling
SW1-4
Set machine.single internal machine
Indoor unit
KIT
SW2-1
The first group controls the electric heating to turn on the
temperature difference
1.8°F (1°C)
3.6°F (2°C)
SW2-2
Whether the electric heating is delayed
YES
NO
SW2-3
Electric auxiliary heating delay start time
30 minutes
15 minutes
SW2-4
Electric heating/compressor allow opening limit
Compressor allowed to operate to low
limit set by S3
Electric heating allowed to operate
to high limit set by S3
SW3-1
Continuous running time when the 1.8°F (1°C) set temperature
is not reached
E-square value (0.5 hour)
1.5 hours
SW3-2
Cooling and heating Y2 signal setting temperature adjustment
value A
1.8°F (1°C)
3.6°F (2°C)
SW3-3
Hysteresis of the second group of electric heating
3.6°F (2°C)
5.4°F (3°C)
SW3-4
Reserve
/
/
S4-1
Default ON
Short circuit W1 and W2
W1, W2 separate
S4-2
Default ON
DH is off by default
DH on
SW4-1
000 is the default
000/001/010/011/100/101/110/111, internal machines with different abilities, electric heating and PSC classification for use
SW4-2
SW4-3