DIAGNOSIS AND SOLUTION (CONT.)
EH0E - Water-Level Alarm Malfunction Diagnosis and Solution
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Water-level switch
• Water pump
• Indoor PCB
Troubleshooting and Repair:
Power off, then restart the unit 2 minutes
later.
Is the water-level switch
inserted properly?
Insert the water-level switch
properly
NO
YES
Replace the water-level switch
NO
YES
Replace the indoor main PCB
Does a problem
remain?
YES
The unit is operating normally.
NO
Is the water level
switch broken?