If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screwdriver) for 5 sec and released, a
short defrost cycle will be observed (actual length is dependent
upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 sec
compressor off period followed by 30 sec of defrost with com-
pressor operation). On return to heating operation, compressor will
again turn off for an additional 30 sec and the fan for 40 sec. When
the Quiet Shift is in OFF position, only a brief 30 sec cycle will be
observed.

If it is desirable to observe a complete defrost in warmer weather,
the thermostat must be closed as follows:

1. Turn off power to outdoor unit.

2. Disconnect outdoor fan motor lead from OF2 on control board

(See Fig. 9.) Tape to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate on

outdoor coil.

4. After a few minutes in heating mode, liquid line temperature

should drop below closing point of defrost thermostat (ap-
proximately 30°F).

NOTE:

Unit will remain in defrost until defrost thermostat

reopens at approximately 80°F coil temperature at liquid line or
remainder of defrost cycle time.

5. Turn off power to outdoor and reconnect fan motor lead to

OF2 on control board after above forced defrost cycle.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment.

Leave User’s Manual with owner. Explain system operation and
periodic maintenance requirements outlined in manual. Frequency
of maintenance may vary depending upon geographic areas, such
as coastal applications.

OF2

CESO130076–00

OF1

ON

Q

UIET

SHIFT

120

30

60

60

30

90

INTER

V

AL  

TIMER

OFF

P3

DFT

O   R   

W

2

   

Y   C

T2 C  C  O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A99442

Fig. 9—Defrost Control

7

Содержание 38YCX

Страница 1: ...k Equipment and Job Site UNPACK UNIT Move to final location Remove carton taking care not to damage unit INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged...

Страница 2: ...8 460 4 14 3 8 365 1 5 8 15 88 33 15 16 862 0 036 30 762 0 6 1 2 165 1 23 1 2 596 9 20 508 0 3 4 19 05 39 15 16 1014 4 048 30 762 0 6 1 2 165 1 23 1 2 596 9 20 508 0 7 8 22 23 33 15 16 862 0 060 30 7...

Страница 3: ...e and completely sur rounds vapor tube 9 When necessary use hangar straps which are 1 in 25mm wide and conform to shape of tubing insulation See Fig 4 10 Isolate hangar straps from insulation by using...

Страница 4: ...ordance with existing electrical codes Failure to follow this warning can result in an electric shock fire or death NOTE Use No 18 AWG American Wire Gage color coded insulated 35 C minimum wires If th...

Страница 5: ...R G THERMOSTAT W2 L E C R G ODTS2 ODTS1 BLU VIO SYSTEMS WITH TWO OUTDOOR THERMOSTATS A97053 HEAT PUMP E L O O Y Y SYSTEMS WITHOUT OUTDOOR THERMOSTAT FB4ASX FAN COIL W2 W2 W2 C C C R R G THERMOSTAT R G...

Страница 6: ...ed with a time delay relay circuit the blower runs an additional 90 sec to increase system efficiency Heating On a call for heating the thermostat makes circuits R Y and R G If phasing is correct circ...

Страница 7: ...n heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in heating mode liquid line temperature should drop below closing point of defrost thermostat ap proximately 30 F NOTE...

Страница 8: ...31 38ycxc3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 003 88...

Отзывы: