background image

To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.

NOTE:

Install branch circuit of adequate size per NEC to handle

unit starting current. Locate disconnect within sight from and
readily accessible from unit per Section 440-14 of NEC.

The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault
should occur. The ground may consist of electrical wire or
metal conduit when installed in accordance with existing
electrical codes. Failure to follow this warning can result in an
electrical shock, fire, or death.

ROUTE GROUND AND POWER WIRES — Remove access
panel and control box cover to gain access to unit wiring. Extend
wires from disconnect through power wiring hole provided and
into unit control box.

CONNECT GROUND AND POWER WIRES — Connect ground
wire to ground connection in control box for safety. Connect
power wiring to contactor as shown in Fig. 4.

CONNECT CONTROL WIRING — Route 24-v control wires
through control wiring grommet and connect leads to control
wiring. (See Fig. 5.)

Use No. 18 AWG color-coded, insulated (35° C minimum) wire.
If thermostat is located more than 100 ft from unit as measured
along the control voltage wires, use No. 16 AWG color-coded
wires to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.

Use furnace transformer, fan-coil transformer, or accessory trans-
former for control power, 24-v/40va minimum.

NOTE:

Use of available 24-v accessories may exceed the mini-

mum 40-va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.

Step 8—Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hrs before starting unit. To furnish power to heater
only, set thermostat to OFF position and close electrical disconnect
to outdoor unit.

A crankcase heater is required if the refrigerant tubing is longer
than 50 ft. Refer to Residential Split System Long-Line Applica-
tion Guideline.

Step 9—Install Electrical Accessories, If Any

Refer to the individual instructions packaged with the kit or
accessory when installing.

Table 2—Accessory Usage

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(OVER 50 FT)

REQUIRED FOR

SEA COAST

APPLICATIONS

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

Low-Ambient Controller,

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline.
† Only when low-pressure switch is used.
‡ Required for Low-Ambient Controller (full modulation feaature) and MotorMaster Control only.

Fig. 4—Line Power Connections

A91056

DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

4

Содержание 38TKB

Страница 1: ...y or death INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate the unit away from windows 2 Ensu...

Страница 2: ...1 8 060 3 8 3 8 7 8 1 1 8 7 8 1 1 8 Notes 1 Tube diameters are for lengths up to 50 ft For tube sets over 50 ft consult Residential Long Line Application Guideline 2 Do not apply capillary tube indoo...

Страница 3: ...em Long Line Application Guideline will reduce these losses Refer to Table 1 for field tubing equivalent line length Refer to Table 2 for accessory require ments For buried line applications greater t...

Страница 4: ...um 40 va power requirement Determine total transformer load ing and increase the transformer capacity or split the load with an accessory transformer as required Step 8 Compressor Crankcase Heater Whe...

Страница 5: ...1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NOT USED 24 VAC COM NOT USED NOT USED NOT USED OPTIONAL OUTDOOR...

Страница 6: ...HOT R C W W1 Y Y2 G R DH W2 W1 Y Y2 CARRIER NON PROGRAMMABLE THERMOSTAT MODEL AC FK4C FV4A FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 24 VAC COM Y1 C SEE NOTE 2 G O J2 JUMPER J1...

Страница 7: ...to increase system efficiency Step 11 Check Charge UNIT CHARGE Factory charge is shown on unit rating plate Adjust charge by following procedure shown on charging tables located on unit NOTE If super...

Страница 8: ...2 67 1 70 0 73 0 76 0 79 2 82 4 85 7 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53...

Отзывы: