INSTALLATION

Step 1—Check Equipment and Job Site

UNPACK UNIT — Move to final location. Remove carton taking
care not to damage unit.

INSPECT EQUIPMENT — File claim with shipping company
prior to installation if shipment is damaged or incomplete. Locate
unit rating plate on unit service panel. (See Fig. 2.) It contains
information needed to properly install unit. Check rating plate to
be sure unit matches job specifications.

Step 2—Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to a pad,
tie down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern shown in
Fig. 2 to determine base pan size and knockout hole location.

On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.

Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult Low-Ambient Guideline for wind baffle
construction.

NOTE:

Unit must be level to within ±2° per compressor manu-

facturer specifications.

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)

UNIT

SIZE

LIQUID

VAPOR

VAPOR (LONG LINE)

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

018, 024

3/8

3/8

5/8

5/8

5/8

3/4

030, 036

3/8

3/8

3/4

3/4

3/4

7/8

042, 048

3/8

3/8

7/8

7/8

7/8

1-1/8

060

3/8

3/8

7/8

1-1/8

7/8

1-1/8

Notes: 1. Tube diameters are for lengths up to 50 ft. For tube sets over 50 ft. consult Residential Long-Line Application Guideline.

2. Do not apply capillary tube indoor coils to these units.

Fig. 2—Unit Reference Drawing

MODEL 38TKB

A

B

C

D

In.

In.

In.

In.

018, 024, 030, 036

22-1/2

27-1/2

2-13/16

6-15/16

042, 048, 060

30

34-15/16

4

9-3/4

A91055

AIR DISCHARGE

FIELD CONTROL SUPPLY 
CONN  

7

/

8

″ 

(22.22) DIA HOLE

AIR DISCHARGE

AIR DISCHARGE

AIR IN

AIR IN

UNIT RATING PLATE

1.  ALLOW 30

″ 

(762)

 

CLEARANCE TO SERVICE END OF

     UNIT, 48

″ 

(1219) ABOVE UNIT, 6

″ 

(152) ON ONE SIDE, 12

″ 

(306)

     ON REMAINING SIDE, AND 24

″ 

(610)

 

BETWEEN

     UNITS FOR PROPER AIRFLOW.
2.  MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS
     55°F (12.8°C), (UNLESS LOW AMBIENT CONTROL IS USED) MAX 125°F (51.7°C).

NOTES:

ACCESS

PANEL

AIR IN

C

L

B

C

3/8

 (9.53) DIA TIEDOWN

KNOCKOUTS IN BASEPAN
(2) PLACES

3.   MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE IS 66°F (18.9°C).
4.   DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS.
5.   SERIES DESIGNATION IS THE 13TH POSITION  OF THE UNIT
      MODEL NUMBER.

D

UNIT MOUNTING PATTERN

VIEW FROM TOP

FIELD POWER SUPPLY CONN

7

/

8

″ 

(22.22) DIA HOLE WITH 

1

/

8

″ 

(28.57) DIA KNOCKOUT

(ALL SIZES) AND 1 

3

/

8

 (34.92)

DIA KNOCKOUT (036 THRU 060 
SIZES ONLY)

3/8

 

(9.53) DIA LIQUID 

LINE CONNECTION

       

9

/

16

(39.6)

 

1

/

2

(63.7)

 

10 

1

/

2

(266.7)

 

3

/

16

(106.3)

 

3

/

4

(44.6)

 

3

/

16

(207.9)

 

A

INDIANAPOLIS IN

46206

313948-401

REV A

MAX CKT-BKR

MAX HACR CKT-BKR

MAX FUSE

TYPE

MINIMUM CIRCUIT AMPS

LO

HI

DESIGN/TEST PRESSURE GAGE

FLA

HZ

PH

VOLTS AC

LRA

RLA

HZ

PH

VOLTS AC

MAX

PH

LBS

PISTON

MODEL

PROD

SERIAL

N/A

USA

N/A

CANADA

MAX OVERCURRENT PROTECTIVE DEVICE

kPa

kPa

PSI

PSI

FAN MOTOR

COMPRESSOR

SUITABLE FOR OUTDOOR USE

MIN

HZ

Kg

VOLTS

POWER SUPPLY

ID

OD

FACTORY CHARGED R-22

®

®

PERMISSIBLE VOLTAGE AT UNIT

CARRIER CORP

2

Содержание 38TKB

Страница 1: ...y or death INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate the unit away from windows 2 Ensu...

Страница 2: ...1 8 060 3 8 3 8 7 8 1 1 8 7 8 1 1 8 Notes 1 Tube diameters are for lengths up to 50 ft For tube sets over 50 ft consult Residential Long Line Application Guideline 2 Do not apply capillary tube indoo...

Страница 3: ...em Long Line Application Guideline will reduce these losses Refer to Table 1 for field tubing equivalent line length Refer to Table 2 for accessory require ments For buried line applications greater t...

Страница 4: ...um 40 va power requirement Determine total transformer load ing and increase the transformer capacity or split the load with an accessory transformer as required Step 8 Compressor Crankcase Heater Whe...

Страница 5: ...1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NOT USED 24 VAC COM NOT USED NOT USED NOT USED OPTIONAL OUTDOOR...

Страница 6: ...HOT R C W W1 Y Y2 G R DH W2 W1 Y Y2 CARRIER NON PROGRAMMABLE THERMOSTAT MODEL AC FK4C FV4A FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 24 VAC COM Y1 C SEE NOTE 2 G O J2 JUMPER J1...

Страница 7: ...to increase system efficiency Step 11 Check Charge UNIT CHARGE Factory charge is shown on unit rating plate Adjust charge by following procedure shown on charging tables located on unit NOTE If super...

Страница 8: ...2 67 1 70 0 73 0 76 0 79 2 82 4 85 7 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53...

Отзывы: