22
14.1.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the
cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side),
disconnect the charge hose from the 3-
way valve’s service port immediately and turn off the air conditioner
before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
Electronic scale
Содержание 38QUS014D8S2 Series
Страница 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual 2018...
Страница 9: ...1...
Страница 21: ...13 3 3 Console 16 Drain pipe 195 Hanging arm 700 600 210...
Страница 24: ...16 4 3 Console 4 4 Hi wall...
Страница 25: ...17 5 Wiring diagram 38QUS018D8S2...
Страница 26: ...18 Note S 1 S 2 are used in other type of models They don t need to be connected in multi models 38QUS027D8S3...
Страница 27: ...19 38QUS036D8S4 38QUS042D8S5...
Страница 29: ...21 42QSS009D8S 42QSS012D8S 42QZA012D8S...
Страница 42: ...11...