FILE NO. SVM-07009
– 58 –
11. HOW TO DIAGNOSE THE TROUBLE
The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose troubles
according to the diagnosis procedure as described
below. (Refer to the check points in servicing written on
the wiring diagrams attached to the indoor/outdoor
units.)
Table 11-1
No. Troubleshooting Procedure
1 First Confirmation
2 Primary Judgement
3 Judgement by Flashing LED
of Indoor Unit
4 Self-Diagnosis by Remote Controller
5 Judgement of Trouble by
Every Symptom
6 How to Check Simply the Main Parts
Fig. 11-1
NOTE:
A large-capacity electrolytic capacitor is used in the
outdoor unit controller (inverter). Therefore, if the power
supply is turned off, charge (charging voltage DC280V)
remains and discharging takes a lot of time. After
turning off the power source, if touching the charging
section before discharging, an electrical shock may be
caused. Discharge the electrolytic capacitor completely
by using soldering iron, etc.
<Discharging method>
(1) Remove the inverter cover (plating) by opening
four mounting claws.
(2) As shown below, connect the discharge resistance
(approx. 100
Ω
40W) or plug of the soldering iron to
voltage b – terminals of the C12
(“CAUTION HIGH VOLTAGE” is indicated.)
electrolytic capacitor (760
µ
F/400V) on P.C. board,
and then perform discharging.
11-1. First Confirmation
11-1-1. Confirmation of power supply
Confirm that the power breaker operates (ON)
normally.
11-1-2. Confirmation of power voltage
Confirm that power voltage is AC 220-240 V
±
10%. If
power voltage is not in this range, the unit may not
operate normally.
PC board
(Soldered surface)
Inverter cover
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering
iron
Содержание 38NYV025M
Страница 16: ...C L C L FILE NO SVM 07009 4 2 Outdoor Unit 16...
Страница 17: ...5 WIRING DIAGRAM 5 1 Indoor Unit FILE NO SVM 07009 17...
Страница 18: ...5 2 Outdoor Unit FILE NO SVM 07009 18...
Страница 80: ...FILE NO SVM 07009 80 P C board layout Solder side...
Страница 91: ...FILE NO SVM 03008 87...