background image

– 41 –

Item

9. ECO

operation

Operation flow and applicable data, etc.

When pressing [ECO] button on the remote controller, a 

Economic operation is performed

.

 

<Cooling operation>

This function operates the air conditioner with the difference

between the set and the room temperature as shown in the

following figure.

Description

<Heating operation> 

<Heating operation>

1) Setting the compressor speed to

Max. aHz, the temperature zone

in which the operation can be

performed with Max. cHz is

gradually widened after 30

minutes passed when starting

ECO operation.

* 12 (DRY max - COOL min) /6 x 5 + COOL min
* 11 (DRY max - COOL min) /6 x 4 + COOL min
* 10 (DRY max - COOL min) /6 x 3 + COOL min

* 9 (DRY max - COOL min) /6 x 2 + COOL min
* 8 (DRY max - COOL min) /6 x 1 + COOL min

30 minutes

A

B

C

A

B

C

 Time Compressor

speed

 0Hz

A zone

aHz

B zone

a to cHz

C zone

cHz

0

–0.5
–1.0
–1.5
–2.0
–2.5
–3.0
–4.0
–5.0
–6.0
–7.0
–8.0
–9.0

–10.0
–11.0

(Room temp. 

 Set temp.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+3.5 
+3.0 
+2.5 

+1.5 

+1.0 

 TSC 

-1.0 

-2.0 

+5.5

 

1H

 

2H 

11 
10

 7
 6

  5 

 4
 3

  2 

  1

 

OFF 

Dry Max 

*12 
*11 

*9

*8 

*10 

TA

+6.0

 

+6.5

 

3H

4H 

+5.0

 

+4.5

 

+4.0

 

+2.0 

+0.5 

-0.5 

12 

 9
 8

Time

Zone Frequency

FAN

Min

Hz

Fan speed depend on presetting and can change every speed.

 

 

 

 

 
 

Hz 

  42NQV025H   42NQV035M

   

42NQV035H 42NQV045M,42NQV045H

Cool  min

20

20

13

13

DRY  max

35

37

31

35

Hz

42NQV025H

42NQV035M

42NQV035H

42NQV045M

 

42NQV045H

a

20

13

13

c

50

43

50

1) 

The control target temperature
increase 0.5ºC per hour up to 2ºC
starting from the set temperature

when ECONO has been received.

2

The indoor fan speed is depend
on presetting and can change 
every speed after setting ECO

operation.

<Cooling operation>

 
 

2

The indoor fan speed is depend
on presetting and can change 
every speed after setting ECO

operation.

3

The compressor speed is
controlled as shown in the left
figure.

FILE NO. SVM-07013

Содержание 38NYV025H

Страница 1: ...M 07013 1 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit High Wall Heat PumpType Heat PumpType 42NQV025H 38NYV025H 42NQV035H 38NYV035H 42NQV035M 38NYV035M 42NQV045H 38NYV045H 42NQV045M 38NYV045M R...

Страница 2: ...5 WIRING DIAGRAM 18 6 SPECIFICATIONS OF ELECTRICAL PARTS 20 7 REFRIGERANT CYCLE DIAGRAM 21 8 CONTROL BLOCK DIAGRAM 25 9 OPERATION DESCRIPTION 31 10 INSTALLATION PROCEDURE 54 11 HOW TO DIAGNOSE THE TR...

Страница 3: ...d installation tools are different from those used for the conventional refrigerant units Accordingly special tools are required for the new refrigerant R410A units For connecting pipes use new and cl...

Страница 4: ...d electrician in accordance with the Installation Manual Make sure the air conditioner uses an exclusive circuit An insufficient circuit capacity or inappropriate installation may cause fire When wiri...

Страница 5: ...780 780 Depth mm 290 290 290 Net weigh kg 35 35 35 Compressor Motor output W 750 750 750 Type Model DA89X1C 23FZ DA89X1C 23FZ DA111A1F 20F1 Fan motor output W 43 Air flow rate Cooling Heating m 3 min...

Страница 6: ...ion Height mm 550 550 Width mm 780 780 Depth mm 290 290 Net weigh kg 35 39 Compressor Motor output W 750 750 Type Twin rotary type with DC inverter variable speed control Model DA111A1F 20F1 DA111A1F...

Страница 7: ...ing Capacity ratio 42NQV025H 42NQV035M 42NQV035H 42NQV045M 42NQV045H 7 FILE NO SVM 07013 Cooling Heating 0 1 2 3 4 5 6 7 8 9 10 0 10 20 30 40 50 60 70 80 90 100 110 120 Compressor Speed rps Current A...

Страница 8: ...in the refrig eration cycle may become abnormally high so that a rupture or personal injury may be caused 5 After completion of installation work check to make sure that there is no refrigeration gas...

Страница 9: ...t joints Nominal diameter 1 4 3 8 1 2 5 8 Reference outer diameter of copper pipe jointed mm 6 35 9 52 12 70 15 88 Minimum joint thickness mm 0 50 0 60 0 70 0 80 3 2 2 Processing of Piping Materials W...

Страница 10: ...to 0 5 0 to 0 5 0 to 0 5 0 to 0 5 Conventional flare tool Clutch type Wing nut type 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 2 0 to 2 5 1 0 to 1 5 2 0 to 2 5 Table 3 2 4 Dimensions relat...

Страница 11: ...orque for R410A is the same as that for conventional R22 Incidentally when the torque is weak the gas leakage may occur When it is strong the flare nut may crack and may be made non removable When cho...

Страница 12: ...ant charging Refrigerant cylinder Leakage detector Charging cylinder Usage Pipe flaring Flaring by conventional flare tool Connection of flare nut Evacuating refrigerant charge run check etc Vacuum ev...

Страница 13: ...nnecting port of the electronic balance and charge liquid refrigerant Water heat exchanger unit Outdoor unit Opened Opened Refrigerant cylinder with siphon Check valve Open close valve for charging El...

Страница 14: ...of silver and copper It is used to join iron copper or copper alloy and is relatively expensive though it excels in solderability 2 Phosphor bronze brazing filler Phosphor bronze brazing filler is gen...

Страница 15: ...flux which does not contain chlorine 3 When adding water to the flux use water which does not contain chlorine e g distilled water or ion exchange water 4 Remove the flux after brazing 3 5 3 Brazing A...

Страница 16: ...ion plate hanger For 42NQV025M 035M 035H Flare 9 52mm 116 62 69 49 Knock out system Front panel Knock out system 48 7 63 48 63 7 205 Air inlet Air filter Heat exchanger 275 790 170 or more 170 or more...

Страница 17: ...de Flare 12 7 Service port 2 11x14 Long holes Installation dimension Air outlel 100 or more 100 or more 600 or more 600 or more Air intlel 6 hole 86 6 hole 11x14 hole R15 30 A 320 R5 5 36 108 125 50 1...

Страница 18: ...18 5 WIRING DIAGRAM 5 1 42NQV025H 38NYV025H 42NQV035H 38NYV035H 42NQV035M 38NYV035M FILE NO SVM 07013...

Страница 19: ...5 2 42NQV045H 38NYV045H 42NQV045M 38NYV045M 19 FILE NO SVM 07013...

Страница 20: ...door fan motor DC140V 43W 3 Suction temp sensor TS sensor 10k 25 C 4 Discharge temp sensor TD sensor 62k 20 C 5 Outside air temp sensor TO sensor 10k 25 C 6 Heat exchanger temp sensor TE sensor 10k 25...

Страница 21: ...opper pipe Outer dia 6 35mm Thickness 0 8mm Sectional shape of heat insulator Allowable height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting p...

Страница 22: ...nal shape of heat insulator Allowable height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Strainer Pulse Modulating valve at liquid side...

Страница 23: ...hickness 0 8mm Sectional shape of heat insulator Allowable height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Strainer Pulse Modulating...

Страница 24: ...0 8 to 1 0 11 to 13 46 to 48 High High 63 42NQV045M 0 7 to 0 9 10 to 12 47 to 49 High High 89 42NQV045H 0 8 to 1 0 11 to 13 40 to 42 High High 83 condition C Tempeature Heat exchanger pipe temp Model...

Страница 25: ...Power Supply Circuit Infrared Rays 36 7kHz Remote Controller Thermo Setting Fan Speed Selection ON TIMER Setting OFF TIMER Setting Louver AUTO Swing Louver Direction Setting Operation Mode Selection...

Страница 26: ...Hz Remote Controller Thermo Setting Fan Speed Selection ON TIMER Setting OFF TIMER Setting Louver AUTO Swing Louver Direction Setting Operation Mode Selection AUTO COOL DRY HEAT FAN ONLY REMOTE CONTRO...

Страница 27: ...nd and Information Serial Signal Transmitter Receiver Converter D C circuit Noise Filter Indoor Fan Motor Louver Motor Louver Motor Drive Control Indoor Fan Motor Control Initializing Circuit Clock Fr...

Страница 28: ...Command and Information Serial Signal Transmitter Receiver Converter D C circuit Noise Filter Indoor Fan Motor Louver Motor Louver Motor Drive Control Indoor Fan Motor Control Initializing Circuit Cl...

Страница 29: ...ition detect circuit Rotor position detect circuit PWM synthesis function Input current release control IGBT over current detect control Outdoor fan control High power factor correction control Invert...

Страница 30: ...on control 2 Role of outdoor unit controller Receiving the operation command signal Serial signal from the indoor unit controller the outdoor unit performs its role Compressor operation control Operat...

Страница 31: ...tion adjustment 38 3 Swing 38 9 ECO operation 39 10 Temporary operation 40 11 Discharge temperature control 40 12 Pulse Modulating valve P M V control 41 13 Remote A or B selection 42 9 3 Auto Restart...

Страница 32: ...controller ON OFF Air conditioner Air purifier Operation select COOL HEAT AUTO DRY Temperature setup Air direction Swing Air volume select AUTO LOW LOW MED MED HIGH ECO PRESET ON timer setup OFF timer...

Страница 33: ...e operation mode the fan speed is controlled by the previous operation mode 4 DRY operation DRY operation is performed according to the difference between room temperature and the setup temperature as...

Страница 34: ...e M WB 3 4 5 L W6 Air volume AUTO L L M M H W6 L M 2 W9 M H 2 WC Indication Fan speed Fan speed setup COOL ON AUTO MANUAL 3 Fan speed M L x 3 4 L 4 Fan speed M L x 2 4 L 5 Fan speed M L x 1 4 L Linea...

Страница 35: ...c 1 0 d 1 5 e 2 0 f 2 5 g 5 0 5 5 L W9 M WD 1 2 3 H WE H WE Line approximate H and SUL with Tc SUL W2 Stop 46 46 Tc 34 45 45 33 33 33 21 32 32 20 A 4 A 4 A 4 A 4 A 4 A 4 Fan speed MANUAL in starting F...

Страница 36: ...roller Fan motor ON 3 Fan lock OFF status of fan motor continues 4 Motor operates as shown in the table below 1 Outdoor unit operation command Outdoor fan control Air conditioner OFF Alarm display Out...

Страница 37: ...e specified value 5 Current release control Set temp Ts Room temp Ta Correction of Hz signal Outdoor temp To Setup of current release point Capacity control continues Detection of electromotive force...

Страница 38: ...ressor speed is kept Q zone When temperature of the indoor heat exchanger drops in the range from 46 C to under 55 C the compressor speed is kept Q zone 2 When temperature of the indoor heat exchanger...

Страница 39: ...ower stop the indoor fan Finish of defrost operation Returning conditions from defrost operation to heating operation 1 Temperature of outdoor heat exchanger rises to 8 C or higher 2 Temperature of ou...

Страница 40: ...ither upper or lower limit position swing operation is performed in width 35 from the limit which the stop position exceeded 3 Swing 2 Louver position in heating operation 2 Air direction adjustment T...

Страница 41: ...peed 0Hz A zone aHz B zone a to cHz C zone cHz 0 0 5 1 0 1 5 2 0 2 5 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 Room temp Set temp 3 5 3 0 2 5 1 5 1 0 TSC 1 0 2 0 5 5 1H 2H 11 10 7 6 5 4 3 2 1 OFF Dry Max...

Страница 42: ...er lamp ON Press RESET button Did you press RESET button for 3 seconds or more Did you press RESET button for 10 seconds or more Switch to AUTO RESTART control YES YES NO NO NO YES Temporary AUTO oper...

Страница 43: ...in the range of set tempera ture Discharge temp control 4 When defrost operation is performed the open degree of valve is adjusted accord ing to each setup conditions during preparation for defrost an...

Страница 44: ...e remote controller selection is set to A on all the indoor units There is no A setting display Setting the remote controller To separate using of remote control for each indoor unit in case of 2 air...

Страница 45: ...tap The preset temperature drops 1 C The value of the preset temperature on the 3 Heating operation remote controller does not change The indoor unit s fan speed level increase 1 tap The preset tempe...

Страница 46: ...uously for j Press button to turn the unit OFF k Set the operation mode on the signal to the unit l Use the tip of the pencil to push the and then will 00 disappear m Press button to turn the unit ON...

Страница 47: ...on This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shu...

Страница 48: ...peat the setting procedure the unit receives the signal and beeps three times The unit will be required to be turned on with the remote controller after the main power supply is turned off When the sy...

Страница 49: ...Heating Max 30 C Fan Only No temperature indication 3 Press FAN Select AUTO LOW LOW MED MED or HIGH FILE NO SVM 07013 Note Some models remote will have text above the buttons 2 Start Stop button 3 Mo...

Страница 50: ...emote control Pressing the RESET button the unit can start or stop without using the remote control Operation mode is set on AUTOMATIC operation preset temperature is 24 C and fan operation is automat...

Страница 51: ...restart the conditioner after the power failure Power of the unit must be on 1 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beep sound and OPERATION lamp bli...

Страница 52: ...ER indicator Indicates when the Hi POWER operation starts Press the Hi POWER button to start and press it again to stop the operation 7 PRESET indicator Flashes for 3 seconds when the PRESET button is...

Страница 53: ...ear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Pan head wood screw Remote control holder V...

Страница 54: ...iffuser Elongated drain hole Drain hole Part name Q ty Installation plate 1 Wireless remote control 1 Battery 2 Remote control holder 1 Part No Part name Q ty Mounting screw 4 25L 6 Remote control hol...

Страница 55: ...size have been changed to 1 2 UNF 20 threads per inch When purchasing a charge hose be sure to confirm the port size As pressure is high and gasification speed is fast it is difficult to read the indi...

Страница 56: ...ht or close to a heating source such as a stove Keep the remote controller at least 1 m away from the nearest TV set or stereo equipment This is necessary to prevent image disturbances or noise interf...

Страница 57: ...air conditioner NOTE Wire type More than 1 5 mm2 H07RN F or 60245IEC66 CAUTION This appliance can be connected to a main circuit breaker in either of the following two ways 1 Connection to fixed wirin...

Страница 58: ...nnection with a pair of nippers 2 Changing drain hose For left connection left bottom connection and rear left connection s piping it is necessary to relocate the drain hose and drain cap CAUTION Conn...

Страница 59: ...posi tioned within 43 mm above the wall surface If the connecting pipes are positioned more than 43 mm above the wall surface the indoor unit may be unstable When bending the connecting pipe make sure...

Страница 60: ...ooked on the installation plate Installation plate Indoor unit Connecting cable Auxiliary pipes 10 3 7 Drainage 1 Run the drain hose at a downward sloped angle NOTE Hole should be made at a slight dow...

Страница 61: ...in water does not cause any problems Precautions for adding refrigerant Use a scale having a precision with at least 10 g per index line when adding the refrigerant Do not use a bathroom scale or simi...

Страница 62: ...he installation diagram of the indoor and outdoor units Check that the outdoor unit is horizontal and route the drain hose at a downward sloped angle while ensuring that it is connected tautly Do not...

Страница 63: ...ng the pipes 2 Tighten connections carefully between pipes and unit 3 Evacuate the air in the connecting pipes using a VACUUM PUMP 4 Check for gas leaks at all connections Use a vacuum pump Be sure to...

Страница 64: ...parts to burn out Be sure to comply with local regulations codes when running the wire from outdoor unit to indoor unit Size of wire and wiring method etc Every wire must be securely connected If inc...

Страница 65: ...lled in the same room or adjacent two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either...

Страница 66: ...erter 3DV inverter will be incorporated starting with this unit 3DV 3 shunt Discrete Vector control K The control circuitry has an uninsulated construction No 1 2 3 4 5 First Confirmation Primary Judg...

Страница 67: ...components Sensor leads Do NOT lay the circuit board assembly flat K Precautions when inspecting the control section of the outdoor unit NOTE A large capacity electrolytic capacitor is used in the ou...

Страница 68: ...asing of compressor motor speed stops approx 30 seconds after operation started and then compressor motor speed increases again approx 30 seconds after In AUTO mode the operation mode is changed In HE...

Страница 69: ...nditioner operates 2 When item B and C and item B and a part of item E occur concurrently priority is given to the block of item B 3 The check codes can be confirmed on the remote controller for servi...

Страница 70: ...e display All indicators on the indoor unit will flash 5 times per 1 sec Press button to release the service mode The display of the remote controller returns to as it was before service mode was enga...

Страница 71: ...returns the initial status However the check codes are not deleted even if the power supply is turned off because they are stored in the fixed memory 3 After servicing press CLR button under check mo...

Страница 72: ...ion Block Outdoor P C board Not displayed Outdoor P C board Others including compressor Operation of diagnosis function Cause of operation Inverter over current protective circuit operates Short time...

Страница 73: ...ushing START STOP button on remote controller Is voltage DC12V or 5V indicated on rear of indoor control board normal Does transmission mark on remote controller flash normally and is its signal trans...

Страница 74: ...erly Is DC310 340V supplied between CN10 1 3 Does fan motor connector between CN10 1 3 short circuit Item by symptoms Operation Check Item Considerable principle cause Measures Parts R04 R05 DB01 C01...

Страница 75: ...y hand at the operation stop condition is the rotation signal DC 12V 0V detected between 2 Purple lead and 3 Blue lead of the motor connector CN33 1 pulse 1 revolutio Dose AC120V or ligher voltage app...

Страница 76: ...r CN31 Check this condition within 15 seconds after starting unit Start to operate the indoor unit in except heating operation At this time is it possible to detect DC 1V or more between 5 and 3 of mo...

Страница 77: ...42NQV045H 42NQV045M Cause The IC is built in the indoor fan motor Therefore the P C board is also mounted to inside of the motor If the P C board is soldered imperfectly or the IC is defective the fan...

Страница 78: ...uble by Every Symptom AFS 220 20 4AR Do not disconnect the connector while the fan motor is rotating For P C board side proceed to the item Only indoor fan does not oper 1 3 5 1 2 3 2 1 3 2 1 3 2 1 3...

Страница 79: ...are exhausted Does radio sound is affected by remote controller when a signal is transmitted at distance of 5 cm from radio Is transmission mark indicated P C board is defective Replace P C board Rep...

Страница 80: ...ransmission from indoor unit to outdoor unit is correctly performed based upon the follow ing diagram NOTE Measurement should be performed 2 minutes and 30 seconds after starting of the operation Be s...

Страница 81: ...essure is low Is connecter of coil connected to inverter Is coil of the pulse motor valve P M V correctly set Existence of condensation at outlet of P M V If there is condensation at outlet 1 4 inch 6...

Страница 82: ...mary If fuse was blown be sure to check the electrolytic capacitor and diode block DB01 Connect discharge resistance approx 100 40W or soldering iron plug between terminals of the electro lytic capaci...

Страница 83: ...How to Check the P C Board Indoor Unit 1 Operating precautions 1 When removing the front panel or the P C board be sure to shut off the power supply breaker 2 When removing the P C board hold the edge...

Страница 84: ...her or not the com pressor operates 2 Check whether or not the OP ERATION indicator flashes Causes Impulse voltage was applied or the indoor fan motor short circuited 1 The terminal block or the cross...

Страница 85: ...ble to detect the voltage AC120V or higher voltage between red and black 2 The motor does not operate or the fan motor does not rotate with high speed But it is possible to receive the signal from the...

Страница 86: ...CN01 DC 15 60V 1 Check whether or not the com pressor operates 2 Check whether or not the OP ERATION indicator flashes 1 Check whether or not the com pressor operates 2 Check whether or not the OP ER...

Страница 87: ...the above condition in No 5 1 Check it is impossible to detect the voltage DC 15V between 3 and 4 of the motor terminals 2 The motor does not operate or the fan motor does not rotate with high speed B...

Страница 88: ...e value k Temperature C TD Discharge temp sensor TA Room temp sensor TC Heat exchanger temp sensor TO Outdoor temp sensor TE Outdoor heat exchanger temp sensor TS Suction temp sensor TA TC TO TE TS TD...

Страница 89: ...50 Resistance value k Temperature C TD Discharge temp sensor TA Room temp sensor TC Heat exchanger temp sensor TO Outdoor temp sensor TE Outdoor heat exchanger temp sensor TS Suction temp sensor TA TC...

Страница 90: ...ce value of each winding coil by using the tester Under normal temp 25 C Position 1 to 2 1 to 3 1 to 4 1 to 5 Resistance value 250 20 Refer to 11 5 1 3 and 4 Under 20 C Disconnect the connector and me...

Страница 91: ...ered surface Heat sink IGBT side C12 C13 C14 Case that product is good Pointer swings once and returns slowly When performing test once again under another polarity the pointer should return C12 C13 C...

Страница 92: ...of the outdoor fan motor 4 Motor drive circuit failure of the outdoor P C board 3 How to simply judge whether outdoor fan motor is good or bad NOTE However GND circuit error inside of the motor may be...

Страница 93: ...hed they may ignite any oil mixed with the refrigerant gas 2 Do not use welding equipment in an airtight room Carbon monoxide poisoning may result if the room is not properly ventilated 3 Do not bring...

Страница 94: ...screws 2 pcs 6 Take off three hooks of panel from rear side How to assemble the front panel 1 Press three center positions and two lower center positions of the air outlet and then hang the hanging ho...

Страница 95: ...on the back body and secure it using the fixing screw Now attach the display unit Connect the connectors for the fan motor and louver motor 2 Secure the grounding wire using the fixing screw Insert t...

Страница 96: ...2 Remove the pipe holder from the rear side of the main unit 3 Remove two fixing screws at the left side of the end plate of the heat exchanger Remarks 4 Remove one fixing screw on the heat exchage f...

Страница 97: ...Remove the two screws used to secure the bearing base 3 Remove the bearing base Caution at assembling If the bearing is out from the housing push it into the specified position and then incorporate it...

Страница 98: ...rew of the cross flow fan 3 Remove two fixing screws of the motor cover and them remove the motor cover 4 Remove two more fixing screws of the motor band and remove the motor band Remarks 5 Pull the f...

Страница 99: ...5 mm from wall of rear plate of the main unit Holding the set screw install the cross flow fan so that U groove of the fan motor comes to the mounting hole of the set screw Perform positioning of the...

Страница 100: ...er 2 Remove the front panel Remove the 2 fixing screws 3 Remove the electrical part base Remarks Replace terminal block microcomputer ass y and the P C board ass y 12 2 Microcomputer P C board layout...

Страница 101: ...101 42NQV045H 42NQV045M 12V GND 5V FILE NO SVM 07013...

Страница 102: ...e the indoor unit 2 Attach the upper cabinet ST1T 4 10L 5 pcs 3 Perform cabling of connecting cable and attach the cord clamp Fix the cord clamp by tightening the screws ST2T 4 x 14L 3 pcs fitting 2 c...

Страница 103: ...is fitted into the side cabinet left at the front left side so pull up the top of the front cabinet to remove it 2 Attachment 1 Insert the claw on the front left side into the side cabinet left 2 Hoo...

Страница 104: ...This capacitor is one with mass capacity Therefore it is dangerous that a large spark generates if short circuiting between Requirement As each connector has a lock mecha nism avoid to remove the con...

Страница 105: ...their housing must be released before they are disconnected 2 Remove the control board assembly from the P C board base Remove the heat sink and control board assembly while keeping them screwed toget...

Страница 106: ...heat exchanger Remarks Detail A Detail B Detail C 1 Perform work of item 1 of and 2 Remove the flange nut fixing the fan motor and the propeller Flange nut is loosened by turning clock wise To tighte...

Страница 107: ...d flames Otherwise it may malfunction 7 Remove the fixing screw of the bottom plate and heat exchanger ST1T 4 10L 1 pc 8 Remove the fixing screw of the bottom plate and valve fixing plate ST1T 4 10L 1...

Страница 108: ...Remove the front cabinet and put it down so that fan guard side directs downward Perform work on a corrugated cardboard cloth etc to prevent flaw to the product 3 Remove the hooking claws by pushing m...

Страница 109: ...bove figure is the model 38NYV035H and 38NYV045M The sensor mounting positions in the model 38NYV025H Detail C for 38NYV035H 38NYV045H Detail C for 38NYV025H TS sensor Suction pipe temperature sensor...

Страница 110: ...09413 GRILLE OF AIR INLET ORIGINAL 207 43T83003 REMOTE CONTROL HOLDER WHITE 42NQV045M 42NQV035M 208 43T60382 MOTOR CORD 224 43T09414 GRILLE OF AIR INLET OPTIONAL 209 43T82310 INSTALLATION PLATE WHITE...

Страница 111: ...60002 TERMINAL BLOCK 3P 42NQV035M 42NQV045M 403 43T50318 TEMPERATURE SENSOR 406 43T69635 PC BOARD 42NQV045M 404 43T62003 CORD CLAMP 406 43T69636 PC BOARD 42NQV045H 405 43T69634 PC BOARD ASSY WRS LED 4...

Страница 112: ...SVM 07013 8 8 For model 38NYV025H 38NYV035M For model 38NYV035H 38NYV045M 38NYV045H 19 BIMETAL THERMO 29 DRAIN NIPPLE 31 HOLDER SENSOR TE FOR PIPE O D 6 35 32 HOLDER SENSOR TD FOR PIPE O D 8 0 33 HOLD...

Страница 113: ...MOTOR 38NYV045H 38NYV045M 23 43T47001 NUT FLANGE 9 43T43410 CONDENSER ASSEMBLY 24 43T47354 BOLT COMPRESSOR M6 38NYV025H 38NYV035M 25 43T49335 RUBBER CUSHION 9 43T43411 CONDENSER ASSEMBLY 26 43T46343 4...

Страница 114: ...V035H 38NYV035M 703 43T60384 TERMINAL BLOCK 6P 701 43T62321 HEATSINKA 38NYV045H 704 43T60326 FUSE 38NYV045M 705 43T60377 TEMPERATURE SENSOR 702 43T69630 PC BOARD 38NYV025H 706 43T50304 SENSOR HEAT EXC...

Страница 115: ...56 FILE NO SVM 03005 TOSHIBA CARRIER THAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND...

Отзывы: