INSTALL ALL POWER AND INTERCONNECTING 
WIRING TO OUTDOOR UNITS

1. Mount the outdoor power disconnect.

2. Run the power wiring from the main box to disconnect per

NEC and local codes.

3. Remove the field wiring cover from the unit by loosening

the screws.

4. Remove the caps on the conduit panel.

5. Connect the conduit to conduit panel (see Fig. 11).

6. Properly connect both the power supply and control lines

to the terminal block per the connection diagram for the
appropriate unit capacity and voltage.

7. Ground the unit in accordance with NEC and local electrical

codes.

8. Use the lock nuts to secure the conduit.

9. Reinstall the field wiring cover.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

S

  Be sure to comply with local codes while running wire

from indoor unit to outdoor unit.

S

  Every wire must be connected firmly. Loose wiring may

cause the terminal to overheat or result in unit
malfunction. A fire hazard may also exist. Therefore,
ensure all wiring is tightly connected.

S

  No wire should be allowed to touch the refrigerant

tubing, compressor or any moving parts.

S

  Disconnecting means must be provided and shall be

located within sight and readily accessible from the air
conditioner.

S

  Connecting cable with the conduit shall be routed

through hole in the conduit panel.

Over

1.57" (40mm)

Terminal Block

Conduit panel

Conduit

Outdoor unit

A07455

Fig. 11

 - 

Field Wiring

DRAIN CONNECTIONS

Install drains must meet local sanitation codes.

Install the outdoor unit drain joint

Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of the outdoor unit. Rotate 90

_

 to securely assemble

them. Connect the drain joint with an extension drain hose to avoid
condensate from draining off the outdoor unit during heating
mode.

Seal

Base pan hole

Drain joint

Seal

Base pan 

Drain 

joint

Fig. 12

 - 

Drain Joint

Images are for illustration purposes only.

CAUTION

!

In cold climates, ensure the drain hose is as vertical as
possible to ensure swift water drainage.

If water drains too slowly, it can freeze in the hose and flood
the unit.

Содержание 38MHR series

Страница 1: ...ual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS OUTDOOR 5 CLEARANCES OUTDOOR 8 INSTALLATION TIPS 9 OUTDOOR UNIT INSTAL...

Страница 2: ...hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in...

Страница 3: ...rips from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied The illustration above is only a sketch Different models may be slightly different The...

Страница 4: ...il connected Wiring All wires must be sized per NEC National Electrical Code or CEC Canadian Electrical Code and local codes Use the Electrical Data table MCA minimum circuit amps and MOCP maximum ove...

Страница 5: ...88 6 40 2 Heat Pump System Size Height H in mm Width W in mm Depth D in mm Weight Net lbs kg 9K 115 21 85 555 30 31 770 11 81 300 61 5 27 9 12K 115V 21 85 555 30 31 770 11 81 300 65 0 29 5 9K 208 230V...

Страница 6: ...800 20 24 514 21 81 554 2 36 6 0 3 37 8 5 5 13 39 340 0 47 1 2 12 24 311 12 80 325 13 11 333 2 76 7 0 H H1 H2 D1 D2 D3 2 43 6 1 8 4 17 1 06 0 87 2 2 R 0 79 R 20 R 0 24 R 6 2 43 6 1 6 D W W1 W2 B1 B2 A...

Страница 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 4 Size 24K...

Страница 8: ...C E A07894 Fig 5 Outdoor Unit Clearance Table 5 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101 NOTE The outdoor unit must be mounted at least 2i...

Страница 9: ...ntaminants to avoid damaging the refrigerant system Avoid sags in the suction line to prevent the formation of oil traps Insulate each tube with a minimum 3 8 in 10 mm wall thermal pipe insulation Ins...

Страница 10: ...malfunction A fire hazard may also exist Therefore ensure all wiring is tightly connected S No wire should be allowed to touch the refrigerant tubing compressor or any moving parts S Disconnecting mea...

Страница 11: ...ble limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps MOCP Maximum Over Current Protection RLA Rated Load Amps CONNECTION DIA...

Страница 12: ...acuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the...

Страница 13: ...r unit s problems If possible always check the diagnostic codes displayed on the indoor unit first The diagnostic codes displayed on the outdoor units are listed on Table 10 Table 10 Unit Diagnostic G...

Страница 14: ...BDP S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 38MHR 01 Replaces N...

Отзывы: