60
Specifications subject to change without notice. SG-38MARB-01
EXV Check
1. Disconnect the connector from the outdoor PCB.
2. Measure the resistance value of each winding using a multi-meter.
3. Check the resistance value of each winding in Table 22.
Fig. 48 — EXV Check
Table 22 — Winding Colors
LEAD WINDING COLOR
NORMAL VALUE
Red-Blue
About 50
Red-Yellow
Brown-Orange
Brown-White
ELECTRICAL SHOCK HAZARD
Electricity remains in the capacitors even when the power is
off.
Ensure the capacitors are fully discharged before
troubleshooting.
WARNING
6 5 4 3 2 1
Red Brown Blue Orange Y
ellow White