APPLICATION DATA
UNIT SELECTION
Select equipment to either match or is slightly less than the
anticipated peak load. This provides better humidity control, fewer
unit cycles, and less part--load operation.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load. Adjust
for anticipated room wet bulb temperature to avoid undersizing
equipment.
UNIT MOUNTING (INDOOR)
Refer to unit Installation Instructions for further details.
Unit leveling
-- For reliable operation, units should be level in all
planes.
Clearance
-- Provide adequate clearance for airflow as shown in
Fig. 4.
Unit location
-- Select a location which will provide the best air
circulation for the room.
These units should be positioned on the floor, against the wall for
best air circulation. The unit return and discharge should not be
obstructed by furniture, curtains, or anything which may cause unit
short cycling or air recirculation. Place the unit in the middle of the
selected wall (if possible). Use an outside wall, if available, to
make piping easier, and place the unit so it faces the normal
location of room occupants.
UNIT MOUNTING (OUTDOOR)
Refer to unit Installation Instructions for further details.
Unit leveling
-- For reliable operation, units should be level in all
planes.
Clearance
-- Minimum clearance, (see Fig. 5), must be provided
for airflow. The condensing units are designed for free--blow
application. Air inlets and outlets should not be restricted.
Unit location
-- A location which is convenient to installation and
not exposed to strong wind.
A location which can bear the weight of outdoor unit and where
the outdoor unit can be mounted in a level position.
Do not install the indoor or outdoor units in a location with special
environmental conditions. For those applications, contact your
ductless representative.
MOUNTING TEMPLATE
Refer to unit Installation Instructions for further details.
The fan coil units are furnished with mounting to mark the location
of the wiring, and refrigeration line hole locations.
SUPPORT
Adequate support must be provided to support the weight of all fan
coils. Refer to the Physical Data section for fan coil weights, and the
base unit dimensional drawings for the location of mounting brackets.
SYSTEM OPERATING CONDITIONS
OPERATING RANGE
Min / Max ° F (° C)
Cooling
Heating
Outdoor DB
--- 4 / 122 (---20 / 50)
--- 4 / 86 (---20 / 30)
Indoor DB
63 / 90 (17 / 32)
32 / 86 (0 / 30)
Indoor WB
59 / 84 (15 / 29)
NON---OPERATING TEMPERATURE RANGE
Min / Max ° F (° C)
Indoor/Outdoor DB
32 / 86 (0 / 30)
NOTE
: Reference the Product Installation Instructions for more
information.
METERING DEVICES
The outdoor unit has an electronic expansion valve to manage the
refrigerant flow of the fan coil connected.
DRAIN CONNECTIONS
Install drains to meet local sanitation codes. If adequate gravity
drainage cannot be provided, the unit should be equipped with an
accessory condensate pump. The floor console fan coil unit
condensate pumps have a maximum lift of 10’ (3.05 m) for 9k and
12k units and 25’ (7.62 m) for 18k and 30k units.
See the physical dimension tables for drain sizes.
NOTE
:
Floor console fan coil units have internal condensate
traps. A trap is not required.
REFRIGERANT LINES
General refrigerant line sizing:
1. The outdoor units are shipped with a full charge of R410A
refrigerant. All charges, line sizing, and capacities are based
on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m),
consult long--line section on this page for the proper
charge adjustments.
2. Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36--in (914 mm)
should be buried. Provide a minimum 6--in (152 mm)
vertical rise to the service valves to prevent refrigerant
migration.
3. Both lines must be insulated. Use a minimum of 1/2--in.
(12.7 mm) thick insulation. Closed--cell insulation is
recommended in all long--line applications.
4. Special consideration should be given to isolating the
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
Long Line Applications
1. No change in line sizing is required.
2. Add refrigerant per table below.
ADDITIONAL CHARGE TABLE
UNIT SIZE
TOTAL LINE
LENGTH ft
ADDITIONAL CHARGE,
oz/ft. ft (m)
Min
Max
10 --- 25
(3 --- 8)
>25 --- 82
(8 --- 25)
9
10
82
None
0.16
12