GUIDE SPECIFICATIONS

INDOOR WALL--MOUNTED FLOOR CONSOLE DUCTLESS UNITS

Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity

Carrier Model Number: 40MB*F

PART 1 -- GENERAL

1.01 System Description

Indoor, wall--mounted floor console, direct--expansion fan coils are

matched with cooling only or heat pump outdoor unit .

1.02 Agency Listings

Unit shall be rated per AHRI Standards 210/240 and listed in the

AHRI directory as a matched system.

1.03 Delivery, Storage, And Handling

Units shall be stored and handled per unit manufacturer’s

recommendations.

1.04 Warranty (For Inclusion By Specifying

Engineer)

PART 2 -- PRODUCTS

2.01 Equipment

A. General:

Indoor, direct--expansion, floor--mounted fan coil. Unit shall be

complete with cooling/heating coil, fan, fan motor, piping

connectors, electrical controls, microprocessor control system, and

integral temperature sensing. Unit shall be furnished with integral

mounting bracket and mounting hardware.

B. Unit Cabinet:

Cabinet discharge and inlet grilles shall be attractively styled,

high--impact polystyrene. Cabinet shall be fully insulated for

improved thermal and acoustic performance.

C. Fans:

1. Fan shall be tangential direct--drive blower type with air

intake in the center of the unit and discharge at the top and

bottom front. Automatic, motor--driven vertical air sweep
shall be provided standard.

2. Air sweep operation shall be user selectable. The vertical

sweep may be adjusted (using the remote control) and the

horizontal air direction may be set manually.

D. Coil:

Coil shall be copper tube with aluminum fins and galvanized steel

tube sheets. Fins shall be bonded to the tubes by mechanical

expansion and specially blue hydrophilic pre--coated for enhanced

wet--ability. A drip pan under the coil shall have a drain connection

for hose attachment to remove condensate. Condensate pan shall

have internal trap.

E. Motors:

Motors shall be open drip--proof, permanently lubricated ball

bearing with inherent overload protection. Fan motors shall be

4--speed.

F. Controls:

Controls shall consist of a microprocessor--based control system

which shall control space temperature, determine optimum fan

speed, and run self diagnostics. The temperature control range

shall be from 62

_

F to 86

_

F (17

_

C to 30

_

C) in increments of 1

_

F

or 1

_

C, and have 46

_

F Heating Mode (Heating Setback). The

wireless remote controller shall have the ability to act as the

temperature sensing location for room comfort.

The unit shall have the following functions as a minimum:

1. An automatic restart after power failure at the same

operating conditions as at failure.

2. A timer function to provide a minimum 24--hour timer

cycle for system Auto Start/Stop.

3. Temperature--sensing controls shall sense return air

temperature.

4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and

operating conditions.

6. Automatic air sweep control to provide on or off activation

of air sweep louvers.

7. Dehumidification mode shall provide increased latent

removal capability by modulating system operation and set

point temperature.

8. Fan--only operation to provide room air circulation when no

cooling is required.

9. Diagnostics shall provide continuous checks of unit

operation and warn of possible malfunctions. Error

messages shall be displayed at the unit.

10. Fan speed control shall be user--selectable: high, medium,

low, or microprocessor controlled automatic operation
during all operating modes.

11. Automatic heating--to--cooling changeover in heat pump

mode. Control shall include deadband to prevent rapid
mode cycling between heating and cooling.

12. Indoor coil high temperature protection shall be provided to

detect excessive indoor discharge temperature when unit is

in heat pump mode.

G. Filters:

Unit shall have filter track with factory--supplied cleanable filters.

H. Electrical Requirements:

Indoor fan motor to operate on 208--230V as specified. Power is

supplied from the outdoor unit.

I. Operating Characteristics:

The 40MB*F system shall have a minimum SEER (Seasonal

Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed

on the specifications table.

J. Refrigerant Lines:

All units should have refrigerant lines that can be oriented to

connect from the left, right or back of unit. Both refrigerant lines

need to be insulated.

K. Special Features (Field Installed):

1. Condensate Pump:

-- The condensate pump shall remove condensate from the
drain pan when gravity drainage cannot be used. Pump
shall be designed for quiet operation. Pump shall consist of

two parts: an internal reservoir/sensor assembly, and a
remote sound--shielded pump assembly. A liquid level

sensor in the reservoir shall stop cooling operation if the
liquid level in the reservoir is unacceptable.

Содержание 38MAQB09 Series

Страница 1: ...mily room addition S Special space requirements S When changes in the load cannot be handled by the existing system S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structure is essential The ideal compliment to your ducted system when it is impractical or...

Страница 2: ...oor units service and maintenance expense is reduced due to easy to use cleanable filters In addition these floor console systems have extensive self diagnostics to assist in troubleshooting BUILT IN RELIABILITY Ductless split system indoor and outdoor units are designed to provide years of trouble free operation The floor console indoor units include protection against freeze up and high evaporat...

Страница 3: ... B Q MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B 1 1 SYSTEM TYPE Q HEAT PUMP NOT USED OUTDOOR UNIT 38 MA 3 09 38 OUTDOOR UNIT MA MODEL VOLTAGE 3 208 230 1 60 NOMINAL CAPACITY 09 3 4 TON 12 1 TON UNIT TYPE OUTDOOR UNIT Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual products g...

Страница 4: ...Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate Pumps A Crankcase Heater S Basepan Heater S Legend S Standard A Accessory INDOOR UNITS Fig 1 Condensate Pump Accessory On floor console fan coils the condensate pump has a lift capability of 12 ft 3 6 m on the discharge side with the pump mounted in the fan coil or 6 ft 1 8 m...

Страница 5: ...7 210 Width in mm 27 56 700 27 56 700 Depth in mm 23 62 600 23 62 600 Weight Net Lb kg 32 41 14 7 32 41 14 7 DIMENSIONS OUTDOOR Fig 3 Outdoor unit MODEL W in mm D in mm H in mm L1 in mm L2 in mm OPERATING WEIGHT lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 ...

Страница 6: ...6 CLEARANCES INDOOR Fig 4 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Страница 7: ...Design Pressure PSIG 550 550 Metering Device EEV EEV Charge Lb 2 76 2 76 Outdoor Coil Face Area Sq Ft 9 2 9 2 No Rows 2 2 Fins per inch 21 21 Circuits 4 4 Indoor Coil Face Area sq ft Sq Ft 2 1 2 1 No Rows 2 2 Fins per inch 19 19 Circuits 2 2 Compressor Type Hermetic Rotary DC Inverter Compressor Model ASM98D1UFZA ASM108D1UFZA Oil Type VG74 VG74 Oil Charge Fl Oz 12 5 12 5 Rated Current RLA 5 3 5 7 ...

Страница 8: ... 6F 7C 39 2F 4C 32F 0C 24 8F 4C 19 4F 7C 17F 8C 5F 15C 0F 17C 4F 20C 09 208 230V 59F 15C TC 11 18 11 08 10 89 10 65 9 87 9 11 8 27 6 71 6 21 5 80 Input 0 73 0 79 1 04 1 01 0 96 0 9 0 84 0 8 0 79 0 78 COP 4 49 4 11 3 07 3 09 3 01 2 97 2 88 2 46 2 30 2 18 64 4F 18C TC 11 06 10 82 10 65 10 54 9 63 8 84 8 01 5 46 5 02 4 60 Input 0 78 0 8 1 08 1 03 0 98 0 94 0 9 0 82 0 81 0 80 COP 4 15 3 96 2 89 3 00 2...

Страница 9: ...ne hole locations SUPPORT Adequate support must be provided to support the weight of all fan coils Refer to the Physical Data section for fan coil weights and the base unit dimensional drawings for the location of mounting brackets SYSTEM OPERATING CONDITIONS OPERATING RANGE Min Max F C Cooling Heating Outdoor DB 4 122 20 50 4 86 20 30 Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 NON OPE...

Страница 10: ...codes S Use copper conductors only with a 600 volt rating and double insulated copper wire CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S Every wire must be connected firmly Loose wiring may cause terminal to overheat or result in unit malf...

Страница 11: ...er dBa L M H 46 47 50 44 51 55 Heating operation Indoor Sound Power dBa L M H 46 47 50 44 51 55 Outdoor sound power level dBa 65 66 ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP V PH HZ RLA V PH HZ FLA HP W V PH HZ FLA HP W 9 253 187 208 230 1 60 5 3 208 230 1 60 3 0 053 40 208 230 1 60 0 21 0 027 20 15 15 12 5 7 3 0 053 40 0 21 0 027 20 15 15...

Страница 12: ...current Amps 0 21 0 21 Rated HP HP 0 027 0 027 Speed rev min 730 680 580 520 730 680 580 520 Rated RPM rev min 1062 1062 Max input W 66 6 66 6 Outdoor fan material AS AS Type ZL 421 117 8 3K ZL 421 117 8 3K Diameter inch 16 6 16 6 Height inch 4 6 4 6 Outdoor fan motor Model WZDK40 38G W 1 WZDK40 38G W 1 Phase DC DC FLA 3 3 Type 0 42 0 42 Insulation class E E Safe class IPX0 IPX0 Input W 46 46 Outp...

Страница 13: ...1 5VDC Connection of the Switch board CN16 Output 320VDC Connection of the Fan high voltage CN20 Output 5VDC Connection of the Net module CN23 Output 1 12VDC Connection of the Remote switch OUTDOOR UNIT CONTROL BOARD OUTDOOR UNIT CODE PART NAME CN31 Output Pin5 6 12V Pin1 Pin4 Pulse waveform 0 12V CN21 Input Pin3 4 3 3V Pin2 0V Pin1 Pin5 0 3 3V CN22 Input Pin1 3 3V Pin2 0 3 3V CN37 Output 230VAC H...

Страница 14: ...of 1_F or 1_C and have 46_F Heating Mode Heating Setback The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort The unit shall have the following functions as a minimum 1 An automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start ...

Страница 15: ... air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class E insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Fan blades shall be non metallic and shall be statically and dynamically balanced 5 Outdoor fan openings shall be equipped...

Страница 16: ...p D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40MBF 03PD Replaces 38 40MBF 02PD ...

Отзывы: