Carrier 38HDL018 Скачать руководство пользователя страница 8

Table 2 — Electrical Data

UNIT SIZE

38HDL

V-PH-Hz

OPERATIONAL

VOLTAGE*

COMPRESSOR

POWER SUPPLY

Min

Max

RLA

LRA

Fan FLA

MCA

Max Fuse† or HACR-Type

Ckt Bkr Amps

018

208/230-1-60

187

254

10.7

47.0

.70

14.1

25

024

13.2

59.0

.70

17.2

30

030

15.7

73.0

.70

20.3

35

036

14.2

86.7

.70

18.5

30

048

24.3

131.0

1.45

31.8

50

060

28.6

170.0

1.45

37.2

65

LEGEND

FLA

— Full Load Amps

HACR — Heating, Air Conditioning, Refrigeration
LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps per NEC Section 430-24

NEC

— National Electrical Code

RLA

— Rated Load Amps (Compressor)

*Permissible limits of the voltage range at which unit will operate

satisfactorily.

†Time-delay fuse.
NOTES:
1. Control circuit is 24 v on all units and requires an external power

source.

2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

4. Motor RLA values are established in accordance with UL (Under-

writers’ Laboratories) Standard 465.

Low Pressure Switch

— This switch, mounted on the

suction line, has fixed non-adjustable settings. To check pres-
sure switch, attach pressure gage to suction service valve gage
port. Slowly close liquid shutoff valve and allow compres-
sor to pump down. Do not allow compressor to pump down
below 2 psig. Compressor should shut down when suction
pressure drops to cutout pressure in Table 1, and should re-
start when pressure builds up to cut-in pressure shown after
accessory CLO (compressor lockout) switch has been reset
and accessory Time Guard

t

II device has completed its tim-

ing cycle.

Service Valves

— The service valves in the outdoor unit

come from the factory frontseated. This means the refrig-
erant charge is isolated from the line-set connection ports.
To prevent damage to the valve, use a wet cloth or other
acceptable heat sink material on the valve before brazing.

The service valves must be backseated (turned counter-

clockwise until seated) before the service port caps can be
removed and the hoses of the gage manifold connected. In
this position, refrigerant has access from the through out-
door and indoor unit. The service valve cannot be field re-
paired; only a complete valve or valve stem seal and service
port caps are available for replacement.

AccuRater

T

(Bypass Type) Device

— See Fig. 4

for bypass type AccuRater device components. The piston
has a refrigerant metering hole through it. The retainer forms
a stop for the piston in the refrigerant bypass mode and a
sealing surface for liquid line flare connection. To check, clean
or replace piston:
1. Shut off power to unit.
2. Pump down using Pumpdown Procedure section on

page 7.

3. Remove liquid line flare connection from AccuRater

device.

4. Pull retainer out of body, being careful not to scratch flare

sealing surface. If retainer does not pull out easily, care-
fully use locking pliers to remove retainer.

5. Slide piston out by inserting a small soft wire, with small

kinks, through metering hole. Ensure metering hole, seal-
ing surface around piston cones, and fluted portion of pis-
ton are not damaged.

6. Clean piston refrigerant metering hole.

7. Replace retainer O-ring before reassembling AccuRater

device (O-ring part no. 99CC501052).

Refrigerant Charging

To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system
— this can cause compressor flooding.

NOTE: Do not vent or depressurize unit refrigerant to atmos-
phere. Remove and recover refrigerant following practice.

SUPERHEAT METHOD (COOLING, NON-TXV) — To
check and adjust charge during cooling season, use Tables 3
and 4 and the following procedure:

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure suction pressure by attaching a gage to suction

valve service port.

3. Measure suction line temperature by attaching a service

thermometer to unit suction line near suction valve. In-
sulate thermometer for accurate readings.

4. Measure outdoor coil inlet-air dry bulb temperature with

a second thermometer.

5. Measure indoor coil inlet-air wet bulb temperature with

a sling psychrometer.

6. Refer to Table 3. Find air temperature entering outdoor

coil and wet-bulb temperature entering indoor coil. At
this intersection, note the superheat temperature.

7. Refer to Table 4. Find superheat temperature and suc-

tion pressure and note suction line temperature.

8. If unit has higher suction line temperature than charted

temperature, add refrigerant until charted temperature is
reached.

9. If unit has lower suction line temperature than charted

temperature, remove and recover refrigerant until charted
temperature is reached.

10. If air temperature entering outdoor coil or pressure at

suction valve changes, charge to new suction line tem-
perature indicated on chart.

NOTE: The above procedure is independent of indoor air
quantity.

8

Содержание 38HDL018

Страница 1: ... for brazing operations Have a fire extinguisher available Read these instructions thor oughly Consult local building codes and National Electrical Code NEC for special installation requirements INSTALLATION Before installing or servicing system always turn off main power to system There may be more than one dis connect switch Turn off accessory heater power if applicable Electrical shock can caus...

Страница 2: ...185 83 9 048 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 2 55 8 752 5 2 83 16 817 6 1 17 8 352 4 0 81 4 209 5 0 4 406 4 0 07 8 22 22 222 100 5 060 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 2 55 8 752 5 2 83 16 817 6 1 111 16 347 7 0 81 8 206 4 0 37 8 403 2 0 07 8 22 22 249 112 9 UNIT SIZE 38HDL MINIMUM MOUNTING PAD DIM...

Страница 3: ...tes it must be evacuated to 1000 microns to eliminate contamination and moisture in the system Run refrigerant tubes as directly as possible avoiding un necessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure Also when passing refrigerant tubes through the wall seal opening so that vibration is not trans mitt...

Страница 4: ...d wiring must be in compliance with NEC and applicable local codes Use mini mum 60 C wire for field power connection Route power wires through opening in the unit side panel and connect in unit control box as shown on unit label dia gram and Fig 5 and 6 Unit must be grounded CONTROL CIRCUIT WIRING Control voltage is 24 v See Fig 5 and unit label diagram for field supplied wiring details Route cont...

Страница 5: ...7KC PFV Oil oz Initial Recharge 25 21 25 21 38 34 54 50 42 38 56 52 OUTDOOR FAN Propeller Type Direct Drive Horizontal Rpm 850 850 850 850 850 850 Diameter in No of Blades 18 3 18 3 18 3 18 3 24 3 24 3 Fan Pitch Deg 25 27 27 31 24 24 Motor Hp 1 8 1 8 1 8 1 8 1 4 1 4 Nominal Airflow Cfm 1720 1720 1720 1720 3900 3900 OUTDOOR COIL Copper Tube Aluminum Plate Fin Face Area sq ft No of Rows 6 1 1 6 1 1 ...

Страница 6: ... unit on heating cooling applications If accessory IFR is required for cooling only applic tions locate IFR in fan coil NOTE Refer to unit wiring label for wire colors BRN to BLU and C to Y connections Fig 5 Typical Control Circuit Connections Fig 6 Line Power Connections LEGEND NEC National Electrical Code TB Terminal Board TB Connections Field Wiring Factory Wiring 6 ...

Страница 7: ...may result in electrical shock or injury from rotating fan blade Outdoor Fan A reinforced wire mount holds the out door fan assembly in place See Fig 7 for proper mounting positions High Pressure Relief Valve Valve is located in compressor Relief valve opens at a pressure differential of approximately 450 50 psig between suction low side and discharge high side to allow pressure equalization Inter...

Страница 8: ...nt AccuRaterT Bypass Type Device See Fig 4 for bypass type AccuRater device components The piston has a refrigerant metering hole through it The retainer forms a stop for the piston in the refrigerant bypass mode and a sealing surface for liquid line flare connection To check clean or replace piston 1 Shut off power to unit 2 Pump down using Pumpdown Procedure section on page 7 3 Remove liquid lin...

Страница 9: ... 65 6 10 13 16 19 21 24 27 30 33 36 38 41 70 7 10 13 16 19 21 24 27 30 33 36 39 75 6 9 12 15 18 21 24 28 31 34 37 80 5 8 12 15 18 21 25 28 31 35 85 8 11 15 19 22 26 30 33 90 5 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29 100 8 12 15 20 23 27 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 23 LEGEND WB Wet Bulb Do not attempt to charge system under these conditions or refrig erant slugging may occu...

Страница 10: ... of the coils Clean coil annually or as required by location and outdoor air conditions Inspect coil monthly and clean as required Fins are NOT continuous through coil sections Dirt and de bris may pass through the first section become trapped be tween the rows of fins and restrict condenser airflow Use a flashlight to determine if dirt or debris has collected between coil sections Clean coil as f...

Страница 11: ...TROUBLESHOOTING TROUBLESHOOTING CHART COOLING CYCLE 11 ...

Страница 12: ...turer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 111 Catalog No 563 885 Printed in U S A Form 38HDL 2SI Pg 12 1 99 Replaces 38HDL 1SI ...

Отзывы: