Carrier 38HDL018 Скачать руководство пользователя страница 7

START-UP

Preliminary Checks

1. Check that all internal wiring connections are tight and

that barriers, covers, and panels are in place.

2. Make certain field electrical power source agrees with unit

nameplate rating.

3. Open all service valves.

Leak Test —

Field piping and fan coil must be leak tested

by pressure method described in Carrier Standard Service
Techniques Manual, Chapter 1, Section 1-6. Use R-22 at
approximately 25 psig backed up with an inert gas to a total
pressure not to exceed 245 psig.

Evacuate and Dehydrate —

Field piping and fan coil

must be evacuated and dehydrated by either of the methods
described in Carrier Standard Service Techniques Manual,
Chapter 1, Section 1-7.

Charge System —

Release factory charge into sys-

tem by opening (backseating) liquid and suction line service
valves. Add charge amount as required for the total system.
Refer to separate indoor unit installation instructions for the
required total system charge when connected to the indoor
unit.

To Start Unit

NOTE: When using in conjunction with 40QAB, 40QKB,
or 40QNB fan coils, refer to start-up instructions included
with fan coil for correct start-up procedures.

Be sure that field disconnect is closed. Set room thermo-

stat below ambient temperature. Operate unit for 15 min-
utes, then check system refrigerant charge. See Refrigerant
Charging section on page 8.

Unit compressor starts after a 5-minute delay if equipped

with accessory Time Guard

t

II device.

SERVICE

Before performing recommended maintenance, be
sure unit main power switch is off. Failure to do so may
result in electrical shock or injury from rotating fan blade.

Outdoor Fan —

A reinforced wire mount holds the out-

door fan assembly in place. See Fig. 7 for proper mounting
positions.

High-Pressure Relief Valve —

Valve is located in

compressor. Relief valve opens at a pressure differential of
approximately 450 ± 50 psig between suction (low side) and
discharge (high side) to allow pressure equalization.

Internal Current and Temperature Sensitive Over-
load —

Control resets automatically when internal com-

pressor motor temperature drops to a safe level (overloads
may require up to 45 minutes to reset). When an internal
overload is suspected of being open, check by using an ohm-
meter or continuity tester. If necessary, refer to Carrier Stand-
ard Systems Techniques Manual, Chapter 2, for complete
information.

Pumpdown Procedure —

The system may be pumped

down in order to make repairs on low side without losing
complete refrigerant charge.
To pumpdown:
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line valve.

The 38HDL unit coils hold only the factory-designated
amount of refrigerant. Additional refrigerant may cause
units to relieve pressure through compressor inter-
nal pressure relief valve (indicated by sudden rise
of suction pressure) before suction pressure reaches
5 psig. If this occurs, shut off unit immediately, then
frontseat the suction valve and remove and recover
excess refrigerant following accepted practice.

3. Start unit and run until suction pressure reaches 5 psig.
4. Shut unit off and frontseat suction valve.
5. Depressurize low side of unit and recover refrigerant fol-

lowing accepted practice.

DIMENSIONS (in.)

38HDL018

38HDL024-036

38HDL048-060

0.433

0.709

0.16

Fig. 7 — Condenser Fan Mounting Positions

7

Содержание 38HDL018

Страница 1: ... for brazing operations Have a fire extinguisher available Read these instructions thor oughly Consult local building codes and National Electrical Code NEC for special installation requirements INSTALLATION Before installing or servicing system always turn off main power to system There may be more than one dis connect switch Turn off accessory heater power if applicable Electrical shock can caus...

Страница 2: ...185 83 9 048 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 2 55 8 752 5 2 83 16 817 6 1 17 8 352 4 0 81 4 209 5 0 4 406 4 0 07 8 22 22 222 100 5 060 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 2 55 8 752 5 2 83 16 817 6 1 111 16 347 7 0 81 8 206 4 0 37 8 403 2 0 07 8 22 22 249 112 9 UNIT SIZE 38HDL MINIMUM MOUNTING PAD DIM...

Страница 3: ...tes it must be evacuated to 1000 microns to eliminate contamination and moisture in the system Run refrigerant tubes as directly as possible avoiding un necessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure Also when passing refrigerant tubes through the wall seal opening so that vibration is not trans mitt...

Страница 4: ...d wiring must be in compliance with NEC and applicable local codes Use mini mum 60 C wire for field power connection Route power wires through opening in the unit side panel and connect in unit control box as shown on unit label dia gram and Fig 5 and 6 Unit must be grounded CONTROL CIRCUIT WIRING Control voltage is 24 v See Fig 5 and unit label diagram for field supplied wiring details Route cont...

Страница 5: ...7KC PFV Oil oz Initial Recharge 25 21 25 21 38 34 54 50 42 38 56 52 OUTDOOR FAN Propeller Type Direct Drive Horizontal Rpm 850 850 850 850 850 850 Diameter in No of Blades 18 3 18 3 18 3 18 3 24 3 24 3 Fan Pitch Deg 25 27 27 31 24 24 Motor Hp 1 8 1 8 1 8 1 8 1 4 1 4 Nominal Airflow Cfm 1720 1720 1720 1720 3900 3900 OUTDOOR COIL Copper Tube Aluminum Plate Fin Face Area sq ft No of Rows 6 1 1 6 1 1 ...

Страница 6: ... unit on heating cooling applications If accessory IFR is required for cooling only applic tions locate IFR in fan coil NOTE Refer to unit wiring label for wire colors BRN to BLU and C to Y connections Fig 5 Typical Control Circuit Connections Fig 6 Line Power Connections LEGEND NEC National Electrical Code TB Terminal Board TB Connections Field Wiring Factory Wiring 6 ...

Страница 7: ...may result in electrical shock or injury from rotating fan blade Outdoor Fan A reinforced wire mount holds the out door fan assembly in place See Fig 7 for proper mounting positions High Pressure Relief Valve Valve is located in compressor Relief valve opens at a pressure differential of approximately 450 50 psig between suction low side and discharge high side to allow pressure equalization Inter...

Страница 8: ...nt AccuRaterT Bypass Type Device See Fig 4 for bypass type AccuRater device components The piston has a refrigerant metering hole through it The retainer forms a stop for the piston in the refrigerant bypass mode and a sealing surface for liquid line flare connection To check clean or replace piston 1 Shut off power to unit 2 Pump down using Pumpdown Procedure section on page 7 3 Remove liquid lin...

Страница 9: ... 65 6 10 13 16 19 21 24 27 30 33 36 38 41 70 7 10 13 16 19 21 24 27 30 33 36 39 75 6 9 12 15 18 21 24 28 31 34 37 80 5 8 12 15 18 21 25 28 31 35 85 8 11 15 19 22 26 30 33 90 5 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29 100 8 12 15 20 23 27 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 23 LEGEND WB Wet Bulb Do not attempt to charge system under these conditions or refrig erant slugging may occu...

Страница 10: ... of the coils Clean coil annually or as required by location and outdoor air conditions Inspect coil monthly and clean as required Fins are NOT continuous through coil sections Dirt and de bris may pass through the first section become trapped be tween the rows of fins and restrict condenser airflow Use a flashlight to determine if dirt or debris has collected between coil sections Clean coil as f...

Страница 11: ...TROUBLESHOOTING TROUBLESHOOTING CHART COOLING CYCLE 11 ...

Страница 12: ...turer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 111 Catalog No 563 885 Printed in U S A Form 38HDL 2SI Pg 12 1 99 Replaces 38HDL 1SI ...

Отзывы: