9

UNIT MOUNTING (INDOOR)

Mounting template

– The fan coil units are furnished with

mounting bracket to hang the unit and mark the location of the

wiring, and refrigeration line hole locations.

Support

– Adequate support must be provided to handle the

weight of all fan coils. Refer to the Physical Data section for

weights, and the base unit dimensional drawings for the location of

mounting bracket.

Unit Leveling

– For reliable operation, units should be level in all

planes.

Clearances

– Minimum clearance as shown in Fig. 4.

Unit location

– Select a location which will provide the best air

circulation for the room. These units should be positioned as high

as possible on the wall for the best air circulation. The unit return

and discharge should not be obstructed by furniture, curtains, or

anything which may cause the unit to short cycle or air to recycle.

Place the unit in the middle of the selected wall (if possible). Use

an outside wall, if available, to make piping easier, and place the

unit so it faces the normal location of room occupants.

UNIT MOUNTING (OUTDOOR)

Support

– A location which can bear the weight of outdoor unit.

Refer to the Physical Data section for weights, and base

dimensional drawings.

Unit Leveling

– For reliable operation, units should be level in all

planes.

Clearances

– Minimum clearances, as shown in Fig. 5, must be

provided for airflow. The outdoor units are designed for free--blow

applications. Air inlets and outlets should not be restricted.

Unit location

– A location which is convenient to installation and

not exposed to strong wind. If unit is exposed to strong winds, it is

recommended that a wind baffle be used. Contact your Carrier

representative for drawings. Do not install the outdoor or indoor

units in a location with special environmental conditions.

SYSTEM OPERATING CONDITIONS

Cooling operating range:

Maximum

Minimum

DB

_

F (

_

C)

WB

_

F (

_

C)

DB

_

F (

_

C)

WB

_

F (

_

C)

Outdoor Unit

115

(46.1)

---

55

(12.78)

---

Indoor Unit

95

(35)

---

55

(12.78)

---

Heating operating range:

Maximum

Minimum

DB

_

F (

_

C)

WB

_

F (

_

C)

DB

_

F (

_

C)

WB

_

F (

_

C)

Outdoor Unit

75

(23.9)

---

14

(---10)

---

Indoor Unit

80

(26.7)

---

55

(12.78)

---

METERING DEVICES

These units have capillary tube metering devices in the outdoor

unit.

REFRIGERANT LINES

Routing

– Refrigerant lines can be routed in any of the four

directions shown in Fig. 10.

1 Right Exit

2 Right Rear Exit

3 Left Exit

4 Left Rear Exi

( a )

( b )

As viewed from front

Fig. 10 – Refrigerant Line Routing

A08281

General Guidelines:

1. The 38GXQ units are shipped with full charge of R--410A

refrigerant. All charges, line sizing, and capacities are based
on runs of 25ft (7.6 m). For runs over 25ft (7.6 m), consult

long line section for charge adjustments.

2. Refrigerant lines should not be buried in the ground. If it is

necessary to bury the lines, not more than 36 inches (914

mm) should be buried. Provide a minimum of 6 inch (152
mm) vertical rise to service valves to prevent refrigerant

migration.

3. Both lines must be insulated. Use a minimum of 1/2 inch

(12.7 mm) thick insulation. Closed--cell insulation is

recommended in all long--line applications.

4. Special consideration should be given to isolating

interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into

the structure.

Long Line Applications:

1. A field fabricated wind baffle is recommended.
2. No change in line sizing is required.
3. Add refrigerant per table below.

ADDITIONAL CHARGE TABLE

Unit Size

Additional Charge, oz./ft

ft (m)

10 --- 25

(3.05 --- 7.62)

>25 --- 65

(7.62---19.81)

9K hp

None

0.48

12K hp

4. Reduction in capacity due to long lines can be calculated

from the chart below.

CAPACITY LOSS

Capacity, % Loss

Line Length, ft (m)

Cooling:

25

(7.62)

45

(13.7)

65

(19.8)

9 & 12 KBTU/H models

0%

2%

5%

Heating:

9 & 12 KBTU/H models

0%

7%

11%

38/

40GX

Q

Содержание 38GXQ

Страница 1: ...ounted on the wall near the ceiling This selection of fan coils permits inexpensive and creative solutions to design problems such as S Add ons to current space sun room S Special space requirements S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structur...

Страница 2: ... the user and the unit SECURE OPERATION If security is an issue outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings In addition since the 38GXQ can be installed close to an outside wall coils are protected from vandals and severe weather FAST INSTALLATION This compact duct free split system is simple to i...

Страница 3: ...XQ 1 01 009 Air Cooled Condenser Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton INDOOR UNIT 40 GXQ 1 01 009 Fan Coil Unit Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton 38 40GXQ ...

Страница 4: ...1 year for parts and 5 years for compressor INDOOR UNITS A07892 Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump accessory is recommended when adequate drain line pitch cannot be provided or when the condensate must move up to exit The pump has a lift capability of 12 ft 3 6 m on the discharge side if the pump is mounted in the fan coil or 6 ft 1 8 m on the suction side i...

Страница 5: ...bs Kg 9k 30 3 770 9 8 250 7 84 1 99 18 7 8 5 12k 32 7 830 11 2 285 8 9 225 24 2 11 Fig 2 Dimensions of Indoor Unit DIMENSIONS OUTDOOR W D H A08290 Unit Size W In mm D In mm H In mm Net Operating Weight Lbs Kg 9k 12k 33 4 848 12 6 320 21 3 540 88 40 Fig 3 Dimensions of Outdoor Unit 38 40GXQ ...

Страница 6: ...5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR A07891 Fig 4 Indoor unit clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 UNIT 12k in mm A 20 508 B 20 508 C 24 610 D 12 305 E 12 305 Fig 5 Outdoor Unit Clearance 38 40GXQ ...

Страница 7: ...lse DC Rated Cooling Capacity Btuh 12 000 Rated Heating Capacity Btuh 11 200 Operating Weight lb kg Refrigerant Type R 410A Metering Device Capillary Tube at Outdoor Unit Moisture Removal Rate pints hr Indoor Fan RPM CFM High 1200 290 1350 315 RPM CFM Medium 1060 245 1200 268 RPM CFM Low 700 224 1100 245 Motor Watts 13 20 Blower Quantity Size in 1 3 8 x 23 1 3 6 x 24 3 Indoor Coil Face Area sq ft ...

Страница 8: ... 7 Indoor Temp 80 67_F 26 7 19 4_C db wb Indoor Fan High Speed D Rating Point A09176 Fig 6 38GXQ009 40GXQ009 Cooling 0 20 40 60 80 100 120 17 15 8 3 9 4 35 33 1 7 0 6 45 43 7 2 6 1 62 57 16 7 13 9 Capacity Ratio Outdoor Temperature F C DB WB Indoor temperature 75_F 23 4_C db Indoor Fan High Speed D Rating Point A09178 Fig 7 38GXQ009 40GXQ009 Heating 0 20 40 60 80 100 120 140 Capacity Ratio Outdoor...

Страница 9: ...l environmental conditions SYSTEM OPERATING CONDITIONS Cooling operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 115 46 1 55 12 78 Indoor Unit 95 35 55 12 78 Heating operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 75 23 9 14 10 Indoor Unit 80 26 7 55 12 78 METERING DEVICES These units have capillary tube metering devices in the outdoo...

Страница 10: ... not take place of a dehumidifier In addition to the above modes that are selected by using the remote control the unit can run in emergency mode by using a manual button This mode is used when the remote is misplaced or the batteries in the remote died In this mode the unit will run in AUTO mode with a predetermined set point 76_F 24 4_C For more details on the sequence of operation please refer ...

Страница 11: ...0 42 29 31 40GXQ012 1 55 54 44 43 51 51 40 40 48 50 37 39 NOTES 1 Sound power ratings are per ARI 270 and ARI 350 2 Sound pressure ratings are estimated sound pressure 3 feet 91 m from the unit based on sound power data ELECTRICAL DATA UNIT SIZE SYSTEM VOLTAGE OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP VOLTS PH HZ MAX MIN RLA LRA FLA HP W VOLTS FLA HP W 009 115 1 60 12...

Страница 12: ... propeller type and shall discharge air horizontally Fan shall draw air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class B insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Outdoor fan openings shall be equipped with PVC metal m...

Страница 13: ...stics The temperature control range shall be from 62_F to 84_F 16 7_C to 28 9_C The unit shall have the following functions as a minimum 1 Automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing control to enter set points and operating conditions 4 Wireless inf...

Страница 14: ...0 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40GX 1PD Replaces New Printed in U S A Edition Date 03 09 38 40GXQ ...

Отзывы: