Remove indoor coil piston if unit is to be installed on system
with a TXV metering device.

Step 4—Make Piping Connections

Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft (15.24m),
or 20 ft vertical differential, consult Long-Line Application
Guideline which is available at your local distributor.

NOTE:

In some cases, noise in the living area has been traced to

gas pulsations from improper installation of equipment.

INSTALLATION RECOMMENDATIONS

1. Locate unit away from windows, patios, decks, and so forth,

where unit-operation sound may disturb customer.

2. Ensure that vapor- and liquid-tube diameters are appropriate to

capacity of unit. (See Table 1.)

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal opening

with RTV or other pliable silicon-based caulk. (See Fig. 3.)

6. Avoid direct tubing contact with water pipes, duct work, floor

joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a

rigid wire or strap that comes in direct contact with tubing.
(See Fig. 3.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 3.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

If refrigerant tubes or indoor coil is exposed to atmospheric
conditions for longer than 5 minutes, it must be evacuated to 500
microns to eliminate contamination and moisture in the system.

Fig. 2—Unit Reference Drawing

UNITSIZE

A/B

C

D

E

F

G

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

024

22-1/2

571.5

3-11/16

93.6

18-1/8

460.4

14-3/8

365.1

5/8

15.9

21-15/16

557.2

036

22-1/2

571.5

3-11/16

93.6

18-1/8

460.4

14-3/8

365.1

3/4

19.1

33-15/16

862.0

048

30

762.0

6-1/2

165.1

23-1/2

596.9

20

508.0

7/8

22.2

27-15/16

709.6

060

30

762.0

6-1/2

165.1

23-1/2

596.9

20

508.0

7/8

22.2

39-15/16

1014.

A97003

AIR  DISCHARGE

F

 

DIA  SUCTION  LINE  CONN

FIELD  CONTROL 
SUPPLY  CONN
7/8 IN.

 

DIA (22.22)  HOLE

AIR 

DISCHARGE

AIR 

DISCHARGE

AIR IN

AIR  IN

NOTES:

FIELD  POWER   SUPPLY  CONN
7/8 IN.

 

DIA (22.22)  HOLE  WITH 

1 1/8 IN.

 

DIA (28.57)  KNOCKOUT

AND 1 3/8 IN.

 

DIA (34.92)  KNOCKOUT 

AIR  IN

AIR  IN

RATING  LABEL

3/8 IN.

 

DIA (9.53) 

LIQUID  LINE  CONN

E

D

C

B

G

A

1.  Allow 30 in. (762 mm) clearance to service end of unit, 48 in. (1219 mm) above
     unit, 6 in. (152 mm) on one side, 12 in. (305 mm) on remaining side, and
     24 in. (610 mm) between units for proper airflow.
2.  Minimum outdoor operating ambient in cooling mode is 55

°

 F (12.8

°

 C),

     MAX. 125

°

 F (51.7

°

 C).

3.  Dimensions in parentheses are in millimeters.
4.  Series designation is the 13th position of the unit model number.

2

Содержание 38CKX

Страница 1: ...cause personal injury or death INTRODUCTION These are the Installation and Start Up Instructions for the 38CKX 50 Hz Air Conditioning Unit INSTALLATION Step 1 Check Equipment and Job Site UNPACK UNIT...

Страница 2: ...and completely sur rounds vapor tube 9 When necessary use hanger straps which are 1 in wide and conform to shape of tubing insulation See Fig 3 10 Isolate hanger straps from insulation by using metal...

Страница 3: ...rsonal injury or death do not supply power to unit with compressor terminal box cover removed The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrica...

Страница 4: ...l compressors are rotation sensitive A flashing LED on phase monitor indicates reverse rotation See Fig 6 and Table 3 This will not allow contactor to be energized Disconnect power to unit and interch...

Страница 5: ...ust be performed on this equipment Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual Frequency of maintenance may vary depending on geo g...

Страница 6: ...RELAY LEGEND AIR COND COOLING ONLY R G C M M INDOOR FAN MOTOR Y Y AIR COND Y Y FB4ASX FAN COIL W2 C C R G THERMOSTAT W R G COOLING ONLY A97050 AIR COND Y Y FB4ASX FAN COIL W2 C C R G THERMOSTAT W R G...

Страница 7: ...7...

Страница 8: ...31 38ckxc2si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 85...

Отзывы: