Accessory description and usage (continued)

 

8.

 

Filter Drier

 

A device for removing contaminants from refrigerant circulating in a heat pump system: two-direction flow.

Usage Guideline:

Suggested in all field-connected split-system heat pumps.

 

9.

 

High-Pressure Switch

 

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 426 ± 10 psig
and resets at 320 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow.

Usage Guideline:

Suggested in installations exposed to "very dirty" outdoor air.
Suggested in installations where condenser inlet air temperature exceeds 125°F (51.7°C).

 

10.

 

Isolation Relay 

 

An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low-ambient kit has been added.

 

11.

 

Liquid-Line Solenoid Valve (LLS)

 

An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It maintains a column of refrigerant
liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle refrigerant migration. 

Note: 

When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in all heat pump long line applications to control refrigerant off cycle migration in the heating mode. A second LLS or hard shut off 
TXV is required in heat pump long line applications for refrigerant off cycle migration in the cooling mode. See Long Line Application Guide-
line.

12.

Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure
within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F
(–17.8°C) when properly installed.

Usage Guideline:

A Low-Ambient Pressure Switch or MotorMaster ®—Low-Ambient Controller must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 

13.

MotorMaster®—Low-Ambient Controller

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temper-
ature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C
± –12°C).

Usage Guideline:

A MotorMaster ®—Low-Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C).
Suggested for all commercial applications.

14.

Outdoor Air Temperature Sensor

Designed for use with Carrier Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also is
required to enable special thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this publication.

15.

Outdoor Thermostat 

An SPDT temperature-actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below a user-selected set point.

Usage Guideline:

Electric supplemental heat applications in non-variable speed indoor units when electric heat staging is desired.

16.

Secondary Outdoor Thermostat

An SPDT temperature-actuated switch which turns on third-stage of supplemental electric heaters when outdoor air temperature drops below the second-stage
set point.

Usage Guideline:

Outdoor Thermostat applications where electric heater is capable of 3-stage operation.

17.

Sound Hood

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft to quiet areas—bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft apart.

18.

Thermostatic Expansion Valve (TXV) Bi-Flow

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.  

Note:

 

When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist — Capacitor and Relay is required

Usage Guideline:

Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings. 
Required for use on all zoning systems.
See long line guideline.

19.

Time-Delay Relay 

An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.

Note:

 

Most indoor unit controls include this feature.  For those that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Содержание 38BYG Series

Страница 1: ...ng season All models are listed with UL U S and Canada CEC and ARI FEATURES BENEFITS Electrical Range All units are offered in single phase 208 230v Size Range 38BYG is available in 7 nominal sizes fr...

Страница 2: ...ischarge Muffler Incorporated to minimize low frequency sound and pressure pulsation generated by compressor discharge gas Weather Protective Cabinet Steel is protected with a galvanized coating and t...

Страница 3: ...2 5 22 40 20 2 6 CONNECTION VALVE In ID Sweat Liquid 5 8 3 4 3 4 3 4 7 8 7 8 7 8 Vapor 3 8 3 8 3 8 3 8 3 8 3 8 3 8 REFRIGERANT TUBES In OD Vapor 5 8 3 4 3 4 3 4 7 8 1 1 8 1 1 8 Liquid 3 8 3 8 3 8 3 8...

Страница 4: ...Thermostatic Expansion Valve Hard Shutoff Size 060 Standard Low Pressure Switch All Sizes KHAHI0101HPS High Pressure Switch All Sizes P504 8083S RCD Liquid Line Filter Drier Bi flow Sizes 018 036 P504...

Страница 5: ...indoor coil 5 Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles Improves compressor lubrication on restart and mini...

Страница 6: ...during operation in cooling mode only For outdoor temperatures down to 20 F 28 9 C it maintains condensing temperature at 100 F 10 F 37 8 C 12 C Usage Guideline A MotorMaster Low Ambient Controller or...

Страница 7: ...ce Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection A weighted sound power dBA NOTE Tested in accordance with ARI Standard 270 95 No...

Страница 8: ...16 3 3 16 5 8 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 10 3 4 11 14 1 4 22 1 2 x 22 1 2 024 30 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16 15 1 2 15 11 3 4 30 x 30 0...

Страница 9: ...DOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 70 60 50 40 30 20 10 80 38BYG024 F A B 4ANF030 38BYG036 F A B 4AN F B 042 38BYG048 FK4CNB005 38BYG060 FK4CNB006 BASED ON INDOOR ENT AIR AT 70 F AND AT R...

Страница 10: ...80 10 65 23 600 3 24 14 100 2 20 7 3 CE3AA030 23 000 NONE 12 00 10 80 23 600 3 32 14 200 2 24 7 5 CF5AA024 22 600 NONE 11 80 10 60 23 600 3 18 14 100 2 18 7 3 CK3BA024 22 400 NONE 11 70 10 75 23 600...

Страница 11: ...AA036 28 400 TDR 13 00 11 15 29 000 3 32 17 900 2 38 7 8 CK3BA036 28 800 TDR 13 00 11 35 29 000 3 46 18 000 2 42 7 8 CK5A CK5BA036 28 800 TDR 13 00 11 35 29 000 3 46 18 000 2 42 7 8 CK5A CK5BT036 28 8...

Страница 12: ...5A CK5BA042 33 800 TDR 13 50 11 50 35 200 3 60 22 000 2 56 8 0 CK5A CK5BT042 33 800 TDR 13 50 11 50 35 200 3 60 22 000 2 56 8 0 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 33 800 TDR 13...

Страница 13: ...00 11 50 42 000 3 52 26 600 2 64 8 0 COILS 58CV A X 110 22 VARIABLE SPEED FURNACE CC5A CD5AC048 39 000 TDR 13 00 11 50 42 000 3 28 26 200 2 56 7 8 CC5A CD5AW048 39 000 TDR 13 00 11 65 42 000 3 44 26...

Страница 14: ...0 3 62 32 800 2 60 8 0 FC4CN F B 048 46 000 TDR TXV 11 50 9 90 48 000 3 40 32 600 2 50 7 6 FC4CN F B 060 47 500 TDR TXV 11 70 10 00 48 000 3 48 33 000 2 52 7 8 FC4CNB054 48 000 TDR TXV 12 10 10 45 48...

Страница 15: ...000 2 40 7 5 CK5A CK5BA060 54 500 TDR 11 50 9 90 60 000 3 28 39 000 2 40 7 5 CK5A CK5BT060 54 500 TDR 11 50 9 90 60 000 3 28 39 000 2 40 7 5 CK5A CK5BX060 56 500 TDR 12 00 10 20 60 000 3 30 38 500 2 4...

Страница 16: ...7 5 1 53 17 2 17 1 1 71 16 5 16 5 1 92 15 8 15 8 2 14 15 0 15 0 2 37 57 17 8 17 8 1 53 17 2 17 2 1 72 16 5 16 5 1 91 15 8 15 8 2 12 15 0 15 0 2 38 72 21 6 11 7 1 58 20 7 11 4 1 78 19 7 11 1 1 98 18 7...

Страница 17: ...26 3 24 2 22 5 22 5 22 5 14 0 18 5 17 9 22 4 22 5 2 01 2 01 2 01 2 01 2 01 25 2 23 2 21 6 21 7 21 7 13 6 18 2 17 5 21 7 21 7 2 22 2 21 2 21 2 21 2 21 24 2 22 2 20 6 20 9 20 9 13 3 17 8 17 1 20 9 20 9...

Страница 18: ...77 25 6 25 6 3 07 24 5 24 5 3 40 23 2 23 2 3 76 27 7 27 7 2 48 26 7 26 7 2 77 25 6 25 6 3 07 24 5 24 5 3 40 23 3 23 3 3 76 Multipliers for Determining the Performance With Other Indoor Sections Indoo...

Страница 19: ...31 8 3 28 30 6 30 6 3 60 29 2 29 2 3 94 27 8 27 8 4 32 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Ca...

Страница 20: ...3 87 26 6 22 6 4 24 32 5 31 6 2 92 31 2 30 8 3 21 29 8 29 8 3 53 28 5 28 5 3 87 27 1 27 1 4 25 32 2 32 2 2 92 31 0 31 0 3 21 29 8 29 8 3 53 28 5 28 5 3 87 27 1 27 1 4 25 1350 72 67 63 62 57 39 2 21 5...

Страница 21: ...4 35 2 35 2 4 64 4 59 4 54 4 57 4 57 37 4 34 5 32 1 33 6 33 6 22 5 30 8 29 5 33 6 33 6 5 07 5 01 4 96 4 99 4 99 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Si...

Страница 22: ...4 17 4 11 4 07 4 08 4 08 39 4 36 2 33 7 34 4 34 4 22 1 29 6 28 6 34 4 34 4 4 56 4 50 4 45 4 47 4 47 37 3 34 2 31 9 32 8 32 8 21 3 28 9 27 8 32 8 32 8 4 98 4 92 4 87 4 89 4 89 1675 72 67 63 62 57 45 8...

Страница 23: ...Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 96 1 05 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AC 048 0 93 1...

Страница 24: ...6 32 49 2 49 2 6 98 46 6 46 6 7 70 2000 72 67 8 35 6 5 39 64 7 34 5 5 96 61 5 33 4 6 59 58 1 32 2 7 26 54 4 31 0 7 99 67 62 6 46 3 5 31 59 7 45 2 5 87 56 6 44 0 6 49 53 4 42 7 7 15 50 0 41 4 7 87 63...

Страница 25: ...36 13 1 11 6 1 41 15 3 13 9 1 49 17 8 17 8 1 58 20 5 20 5 1 71 23 6 23 6 1 88 550 8 01 7 37 1 29 9 58 8 81 1 33 11 4 10 4 1 37 13 3 11 8 1 42 15 5 14 1 1 49 18 0 18 0 1 59 20 7 20 7 1 71 23 9 23 9 1...

Страница 26: ...5 31 8 31 1 31 5 31 8 2 30 2 25 2 23 75 725 825 925 9 25 9 44 9 61 8 51 8 68 8 84 1 86 1 88 1 91 11 9 12 1 12 2 10 9 11 1 11 2 1 93 1 94 1 96 14 4 14 6 14 8 13 2 13 3 13 5 1 99 2 00 2 01 17 1 17 2 17...

Страница 27: ...9 3 29 3 2 76 34 1 34 1 2 98 38 6 38 6 3 12 12 0 11 0 2 22 14 9 13 7 2 30 18 0 16 5 2 37 21 5 19 1 2 47 25 4 23 1 2 60 29 5 29 5 2 76 34 3 34 3 2 93 38 2 38 2 3 07 Multipliers for Determining the Perf...

Страница 28: ...2 61 22 1 20 2 2 71 26 2 23 3 2 83 30 7 27 9 2 97 35 7 35 7 3 16 40 6 40 6 3 28 43 6 43 6 3 39 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoo...

Страница 29: ...39 18 4 16 9 2 48 22 1 20 2 2 57 26 2 23 3 2 70 30 7 27 9 2 84 35 8 35 8 3 03 40 9 40 9 3 17 44 8 44 8 3 32 15 2 14 0 2 43 18 7 17 1 2 51 22 4 20 4 2 60 26 5 23 5 2 72 31 0 28 2 2 86 36 1 36 1 3 03 40...

Страница 30: ...3 58 3 60 41 9 42 5 43 0 41 9 42 5 43 0 3 79 3 78 3 79 49 0 49 7 50 3 49 0 49 7 50 3 4 08 4 05 4 05 56 5 57 3 57 9 56 5 57 3 57 9 4 42 4 38 4 38 Multipliers for Determining the Performance With Other...

Страница 31: ...16 3 20 31 6 32 0 32 4 28 1 28 4 28 8 3 27 3 28 3 32 36 5 37 0 37 4 33 2 33 7 34 0 3 42 3 43 3 45 42 4 43 0 43 5 42 4 43 0 43 5 3 63 3 62 3 64 49 7 50 4 51 0 49 7 50 4 51 0 3 91 3 89 3 89 57 3 58 1 58...

Страница 32: ...rs for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 10 COILS 58CV A X 135 22 VARIA...

Страница 33: ...5 57 69 3 69 3 5 97 79 7 79 7 6 41 2000 28 1 25 9 4 41 33 5 30 8 4 59 39 2 35 7 4 77 45 3 40 2 4 96 52 5 47 8 5 20 60 6 60 6 5 49 70 1 70 1 5 87 79 2 79 2 6 18 2250 28 5 26 2 4 45 33 8 31 1 4 61 39 5...

Страница 34: ...unit should be level in all horizontal planes 7 Maximum elevation of indoor coil above or below base of outdoor unit is indoor coil above 50 ft indoor coil below 150 ft See items 8 and 9 following 8...

Страница 35: ...35...

Страница 36: ...d start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upwar...

Отзывы: