12
Pressure differential (difference between cylinder
load point and unloader points)
Turn the adjusting screw
햵
counter-clockwise to its back stop
position. In this position the differential is 41 kPa. The pressure
differential is set by turning the adjusting screw clockwise. Each
full turn increases the differential by 10 kPa. Approximately 10
turns clockwise will increase the pressure to 152 kPa.
The capacity control factory settings for 4-cylinder units are:
475 kPa gauge control setpoint (cylinder load point), 70 kPa
differential, 405 kPa gauge cylinder unload point.
The settings for 6-cylinder units are: the left cylinder bank
setpoint is 482 kPa gauge (70 kPa differential); the right
cylinder bank setpoint is 469 kPa gauge (70 kPa differential).
Fig. 7 - Pressure-operated control valve
Modifications
It is possible to convert pressure-controlled capacity reductions to electrically controlled reductions or to add capacity reductions
in accordance with the table below.
38AJ/AZ
Pressure-controlled
Possibility of changing
Possibility of 2
unloader standard
press. to electric unloader
pressure-contr. unloaders
008
-
-
-
010
-
-
-
012
-
-
-
014
yes
yes
yes
018
yes
yes
yes
024
yes
yes
yes
030
yes
yes
yes
036
yes
yes
yes
046
yes
yes
yes
062
yes
yes
yes
074
yes
yes
yes
Low and high pressure switch control and condensing pressure pressostat control
Pressostat control:
High pressure, kPa
Low pressure, kPa
Condensing pressure, kPa
38AJ/AZ
Opens
Closes
Opens
Closes
Opens
Closes
008-012
2500
2150
50
150
014-036
2900
2200
50
150
870
1820
046-074
2900
2500
240
390
870
1820
Legend:
1
Control setpoint adjustment screw
2
Valve body
3
Sealing cap (covering the differential adjustment screw)
4
Differential pressure adjustment screw