GB - 4
Type B Electronic Control
Control
Temperature selector
Its purpose is to maintain the temperature at the desired level. The
reference value at the centre of the range is 20°C.
By turning the knob towards the symbol ( – ) the temperature is
reduced from the original setting (minimum value is 10°C).
By turning the knob towards the symbol ( + ), the temperature is
raised from the original setting (maximum value is 30°C).
Energy saving button
This button activates the energ
[UCXKPIHWPEVKQPYJKEJOQFKſGU
room temperature as follows: in heating, the selected temperature is
TGFWEGFD[u%KPEQQNKPIVJGUGNGEVGFVGORGTCVWTGKUTCKUGFD[u%
Light indicators
Blue LED
ON
Indicates that the control is in
cooling
mode
Flashing
Indicates that the control is in frost
protection
mode
(
).
5HG/('JURXSRQWKHULJKW
ON
Indicates that the control is in
heating
mode (
).
Flashing
Indicates the presence of a fault (sensor failed or
not connected)
<HOORZ
LED
JURXSRQWKHULJKW
ON
Indicates that the control is in
automatic
mode ( ).
Blue LED +
<HOORZ
LED
Both ON
Indicates that the control is in
automatic
mode
( ) -
cooling
mode
.
Red LED
<HOORZ
LED
Both ON
Indicates that the control is in
automatic
mode
( ) -
heating
mode (
)
5HG/('VJURXSRQWKHOHIW
ON
Indicates that the fan is operating at the selected
speed.
<HOORZ/(' JURXSRQWKHOHIW
ON
Indicates that the selection of the fan speed is
set automatically.
Red / Blue LED
Flashing
Indicates that the control is in
“Autotest”
mode.
*UHHQ/('
ON
Indicates that the control is in Energy Saving mode.
Flashing
External contact is open.
'LSVZLWFKIXQFWLRQVPLFURVZLWFK
'LSVZLWFK
In open contact position, it allows to activate the frost protection
function
'LSVZLWFK
In open contact position, it permits the fan operation at the selected
URGGFGXGPKHVJGUGVRQKPVVGORGTCVWTGKUUCVKUſGF
'LSVZLWFK
In open contact position, it restricts the range of the temperature
selection knob according to the following limits:
Cooling:
minimum selectable temperature: 23°C.
+HDWLQJ
maximum selectable temperature: 21°C.
'LSVZLWFK
In open contact position, it permits to activate the fan periodically
GXGPKHVJGUGVRQKPVVGORGTCVWTGKUUCVKUſGFCKTUCORNKPI
'LSVZLWFK
In open contact position, it permits to activate the Booster Heating
function (additional heating).
'LSVZLWFKHVDQG
0QHWPEVKQPHQTVJKUOQFGN
NOTE:
)DFWRU\VHWWLQJLVZLWKDOOGLSVZLWFKHVLQFORVHSRVLWLRQ
8VHRIWHPSHUDWXUHVHQVRU
Internal sensor:
This is used in all installations where the control is wall-mounted. To
CEVKXCVGKVENQUGLWORGT,2CUUJQYPKPſIWTG#CPFQPVJGGNGEVTQPKE
board screenprint.
Remote sensor:
This is used on all installations with unitmounted control. It is
positioned on the return air, close to the fan. To activate it, close
LWORGT,2CUUJQYPKPſIWTG$CPFQPVJGGNGEVTQPKEDQCTF
screenprint.
127()DFWRU\VHWWLQJLVZLWKDFWLYDWHGLQWHUQDOVHQVRU
'LDJQRVWLFZDUQLQJV
The following alarm situations are indicated:
'HIHFWLYHVHQVRUVWKHUHG/('ÁDVKHV
Possible causes:
ŖHCKNWTGQTUJQTVEKTEWKVQHKPVGTPCNUGPUQT
ŖHCKNWTGQTUJQTVEKTEWKVQHYCVGTVGORGTCVWTGUGPUQT
Autotest
The autotest function is activated by holding the seasonal
changeover button pressed and at the same time pressing the “
” button three times within 1 second. In this way it is possible to
check the starting of all fan coils. The blue and red LEDs will begin
VQƀCUJ
Each of the various units will be activated for 10 seconds in the
following sequence:
Low fan speed.
Medium fan speed.
High fan speed.
&9
Motorized cold-water valve.
+9
Motorized hot-water valve.
X3
X3
Internal sensor
4GOQVGUGPUQT
Fig. A
Fig. B
)LJ
)LJ