Example 1: Parameter 100 – SYSTEM TYPE
Selections:
1 = Heat Pump fixed Water Temperature Value (dry contacts)
— Default is “1”
2 = Heat Pump Climatic Curve setup (dry contacts)
3 = Heat Pump Comfort with NUI
4, 5, 6, 7 = Blank
Procedure to change the settings
Press zone (
) and hold ( ) simultaneously for 3
seconds, the parameter number will be flashing on the
timing-zone. Press up or down buttons to change the
parameter number to 100. Then press mode (M) button, the
parameter value will be flashing in the temperature-zone of
the display. Press up or down buttons to change the value
from 1 to 7. Press the mode (M) button or OK button to
freeze the settings.
Pressing OK button will save your settings and
t
parameter value will be flashing, you can change the
value
further.
Pressing mode (M) button will save the settings and it
t
will enable the next parameter to be changed. The
parameter number will be flashing.
Pressing zone (
t
) button will not save the settings
and normal display screen will be displayed.
Once completed, press OK button to save the settings
and will return to the normal display screen (If the current
display is at parameter number).
Installation
100
100
1
100
3
Enter par. Setting
Go to param. Nr.
Go to par. Value
Change par. value
Save change
3 sec