background image

7

Airflow Selection for FV4C Fan Coils

(non

communicating)

The FV4 provides high

 and low

stage blower operation to match

the capacities of the compressor at high

 and low

stage.

To select recommended airflow, refer to the FV4C Installation

Instructions. The FV4C utilizes an Easy Select control board that

allows the installing technician to select proper airflows. This fan

coil has an adjustable blower

off delay factory set at 90 sec. for

high

 and low

stage blower operation.

Start

Up

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal 

injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

 Front seating service valves are equipped with Schrader valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury,

equipment damage or improper operation.

S

 Do not overcharge system with refrigerant.

S

 Do not operate unit in a vacuum or at negative pressure.

S

 Do not disable low pressure switch in scroll compressor

applications.

S

 Compressor dome temperatures may be hot.

Follow these steps to properly start up system:

1. After system is evacuated, fully  open liquid and vapor ser-

vice valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to

refrigerant flow (back seated). Replace caps finger

tight and

tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control to

ON or AUTO mode, as desired. Operate unit for 15

minutes. Check system refrigerant charge.

Sequence of Operation
NOTE

:  Defrost control board is equipped with 5 minute lockout

timer that is initiated upon any interruption of power.
Turn on power to indoor and outdoor units. Transformer is

energized.
These models utilize a 2

stage indoor thermostat.  With a call for

first (low) stage cooling or heating, the outdoor fan and low

stage

compressor are energized.  If low

stage cannot satisfy cooling or

heating demand, high

stage is energized by the second (high) stage

of the indoor thermostat.  After the second stage is satisfied, the

unit returns to low

stage operation until second stage is required

again.  When both, first and second stage cooling or heating are

satisfied, the compressor will shut off.

Cooling

With first stage cooling,  Y and O are powered on; and with second

stage cooling,  Y2, Y and O are powered on.  The O energizes the

reversing valve, switching it to cooling position.  The Y signal

sends low voltage through the safeties and energizes the T1

terminal on the circuit board.  If the compressor has been off for 5

minutes, or power has not been cycled for 5 minutes, the OF2 relay

and T2 terminal will energize.  This will close the contactor and

start the outdoor fan motor and compressor.  When the cycle is

complete, Y is turned off, stopping the compressor and outdoor

fan.  The 5 minute time guard begins counting.  Compressor will

not come on until this delay expires.  In the event of a power

interruption, the time guard will not allow another cycle for 5

minutes.

Heating

With first stage heating, Y is powered on; with second stage

heating, Y2 and Y are powered on.  The Y signal sends low

voltage through the safeties and energizes the T1 terminal on the

circuit board.  If the compressor has been off for 5 minutes or

power has not been cycled for 5 minutes, the OF2 relay and T2

terminal will energize.  This will close the contactor and start the

outdoor fan motor and compressor.
When the cycle is complete, Y is turned off, stopping the

compressor nd outdoor fan.  The 5 minute time guard begins

counting.  Compressor will not come on until this delay expires.  In

the event of a power interruption, the time guard will not allow

another cycle for 5 minutes.

Compressor Operation

The basic scroll design has been modified with the addition of an

internal unloading mechanism that opens a by

pass port in the first

compression pocket, effectively reducing the displacement of the

scroll.  The opening and closing of the by

pass port is controlled

by an internal electrically operated solenoid.  The modulated scroll

uses a single step of unloading to go from full capacity to

approximately 67% capacity.
A single speed, high efficiency motor continues to run while the

scroll modulates between the two capacity steps.  Modulation is

achieved by venting a portion of the gas in the first suction pocket

back to the low side of the compressor, thereby reducing the

effective displacement of the compressor.
Full capacity is achieved by blocking these vents, thus increasing

the displacement to 100%.  A DC solenoid in the compressor

controlled by a rectified 24 volt AC signal in the external solenoid

plug moves the slider ring that covers and uncovers these vents.
The vent covers are arranged in such a manner that the compressor

operates at approximately 67% capacity when the solenoid is not

energized and 100% capacity when the solenoid is energized.  The

loading and unloading of the two step scroll is done ”on the fly”

without shutting off the motor between steps.

NOTE

:  67% compressor capacity translates to approximately

75% cooling or heating capacity at the indoor coil.

25HCB6

Содержание 25HCB6 Performance Series

Страница 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Страница 2: ...uding adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end...

Страница 3: ...914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft...

Страница 4: ...e BEFORE bolting adapter to valve This helps prevent overheating and damage to plastic washer or o ring For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing Thi...

Страница 5: ...sconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or d...

Страница 6: ...Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on th...

Страница 7: ...f Cooling With first stage cooling Y and O are powered on and with second stage cooling Y2 Y and O are powered on The O energizes the reversing valve switching it to cooling position The Y signal send...

Страница 8: ...IN HIGH STAGE ONLY Factory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit To properly check or adjust charge conditions...

Страница 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Страница 10: ...hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materia...

Отзывы: