background image

6

  LEGEND

 

24v Factory Wiring

 

24v Field Wiring

 

Field Splice Connection

A09306

Fig. 9 

 

Thermidistat Model TP

PRH

01 or TP

NRH

01 

Wiring with Fan Coil and 25HCB6 2

Stage Heat Pump

 (non

communicating)

Fig. 10 

 

Thermidistat Model TP

PRH

01 or TP

NRH

01 

with Variable Speed Furnace and 25HCB6 2

Stage Heat Pump

(non

communicating)

O

O

RVS Cooling

O/B W2

W1

W2

Heat Stage 3

W/W1

W2

Heat/Cool Stage 1

Y1 / W2

Y1

Y

Heat/Cool Stage 2

Y/Y2

Y/Y2

Y2

Fan

G

G

24VAC Hot Heating

Rh

R

R

24VAC Hot Cooling

Rc

J2 Jumper
on Control Board

Dry Contact 1

D1

Dry Contact 2

D2

DH

24VAC Common

C

C

C

Humidify

HUM

Outdoor Air Temp

OAT

Remote Room Sensor

RRS

OAT/RRS Com

SRTN

Thermidistat

Fan Coil

Heat Pump

Outdoor Sensor

Humidifier Solenoid 

Valve

Remote Room 

Sensor

Remove J1 Jumper
for Dehumidify modes

Thermidistat

Furnace

Heat Pump

O

RVS Cooling

O/B W2

W2

Heat Stage 3 

(furnace)

W/W1

W/W1

W2

Heat/Cool Stage 1

Y1 / W2

Y

Heat/Cool Stage 2

Y/Y2

Y/Y2

Y2

Fan

G

G

24VAC Hot Heating

Rh

R

R

24VAC Hot Cooling

Rc

Dry Contact 1

D1

Dry Contact 2

D2

DHUM

24VAC Common

C

COM

C

Humidify

HUM

Outdoor Air Temp

OAT

Remote Room Sensor

RRS

OAT/RRS Com

SRTN

Outdoor Sensor

Humidifier Solenoid 

Valve

Remote Room 

Sensor

Y1

A12258

A12259

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

All sizes are equipped with a crankcase heater. Furnish power to

heater a minimum of 24 hours before starting unit. To furnish

power to heater only, set thermostat to OFF and close electrical

disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. (24.4 m), or when outdoor unit is 20 ft. (6.1 m) below the

indoor unit.  Refer to the 

Residential Piping and Long Line

Guideline

.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.

Airflow Selections (ECM Furnaces)

The ECM Furnaces provide blower operation to match the

capacities of the compressor during high and low stage cooling

operation. Tap selections on the furnace control board enable the

installing technician to select the proper airflows for each stage of

cooling. Below is a brief summary of the furnace airflow

configurations

1. The Y2 call for high stage cooling energizes the “Cool” tap

on the control board. The grey wire from cool tap is connec-

ted to tap 5 on the motor. Refer to the furnace Product Data

to find the corresponding airflow. If the airflow setting for

high cooling needs to be switched from tap 5 to a different

tap, jumper a connection from the cool tap to the desired tap

so that the Y2 signal is communicated via the cool tap to the

desired speed tap.

2. The Y1 call for low stage cooling energizes the “Fan” tap

on the control board. The red wire from the fan tap is con-

nected to tap 1 on the motor. Refer to the furnace Product

Data to find the corresponding airflow. If the airflow setting

for low cooling needs to be switched from tap 1 to a differ-

ent tap, jumper a connection from the Fan  tap to the desired

tap so that the Y1 signal is communicated via the Fan tap to

the desired speed tap. The Y1 setting will also govern the

continuous fan airflow for the furnace.

Refer to the literature for the furnace for further details.

Airflow Selection for Variable Speed Furnaces

(non

communicating)

The variable speed furnaces provide blower operation to match the

capacities of the compressor during high and low stage cooling

operation. The furnace control board allows the installing

technician to select the proper airflows for each stage of cooling.

Below is a summary of required adjustments. See furnace

installation instructions for more details:

1. Turn SW1

5 ON for 400 CFM/ton airflow or OFF for 350

CFM/ton airflow.  Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high

stage cooling operation. Select the A/C DIP switch setting

corresponding to the available airflow shown in the furnace

Installation Instructions that most closely matches the re-

quired airflow shown in the air conditioning Product Data

for HIGH speed.

3. The CF DIP switch setting determines airflow during low

stage cooling operation. Select the CF DIP switch setting

corresponding to the available airflow shown in the furnace

installation instructions that most closely matches the re-

quired airflow shown in the air conditioning Product Data

for LOW speed. If a higher or lower continuous fan speed is

desired, the continuous fan speed can be changed using the

fan switch on the thermostat. Refer to the furnace Installa-

tion Instructions for details of how to use this feature.

25HCB6

Содержание 25HCB6 Performance Series

Страница 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Страница 2: ...uding adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end...

Страница 3: ...914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft...

Страница 4: ...e BEFORE bolting adapter to valve This helps prevent overheating and damage to plastic washer or o ring For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing Thi...

Страница 5: ...sconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or d...

Страница 6: ...Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on th...

Страница 7: ...f Cooling With first stage cooling Y and O are powered on and with second stage cooling Y2 Y and O are powered on The O energizes the reversing valve switching it to cooling position The Y signal send...

Страница 8: ...IN HIGH STAGE ONLY Factory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit To properly check or adjust charge conditions...

Страница 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Страница 10: ...hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materia...

Отзывы: