Connect Control Wiring

Route 24v control wires through control wiring grommet and

connect leads to control wiring. See Thermostat Installation
Instructions for wiring specific unit combinations. (See Fig. 10.)
Use No. 18 AWG color--coded, insulated (35

°

C minimum) wire.

If thermostat is located more than 100 ft from unit, as measured

along the control voltage wires, use No. 16 AWG color--coded

wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load
with an accessory transformer as required.

Final Wiring Check
IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing
to ensure wires are not in contact with tubing, sheet metal, etc.

STEP 9

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater

only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. Refer to the Long Line Guideline--Residential Split--System
Air Conditioners and Heat Pumps.

STEP 10

Install Electrical Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.

STEP 11

Start--Up

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal

injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader

valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in minor personal

injury, equipment damage or improper operation.
To prevent compressor damage or personal injury,

observe the following:

S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Do not disable low pressure switch in scroll compressor

applications.

S

Dome temperatures may be hot.

S

In 3 phase applications, incorrect phasing will cause reverse

rotation, resulting in elevated noise levels, equalized
pressures and reduced current draw. Correct by reversing
power connection L1 and L2 on contactor.

Follow these steps to properly start up system:

1. After system is evacuated, fully open liquid and vapor

service valves.

2. Unit is shipped with valve stem(s) front seated (closed)

and caps installed. Replace stem caps after system is
opened to refrigerant flow (back seated). Replace caps

finger--tight and tighten with wrench an additional 1/12
turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control to

ON or AUTO mode, as desired. Operate unit for 15
minutes. Check system refrigerant charge.

25H

B

R

25H

B

R

Содержание 25HBR

Страница 1: ...LLATION RECOMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Chec...

Страница 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Страница 3: ...ve roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating...

Страница 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Страница 5: ...ciency Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on liquid service valve Use refrige...

Страница 6: ...ing Set lengths between 80 and 200 ft horizontal or 20 ft vertical differential 250 ft Total Equivalent Length refer to the Longline Guideline Air Conditioners and Heat Pumps using R 22 IMPORTANT Chec...

Страница 7: ...t must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance...

Страница 8: ...Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury Wear safety glasses protective clothing and gloves when handling refrigerant and observe the following S...

Страница 9: ...to complete circuit and bring on second bank of supplemental electric heat When thermostat is satisfied its contacts open de energizing contactor and relay All heaters and motors should stop Defrost T...

Страница 10: ...an indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on ou...

Страница 11: ...11...

Страница 12: ...10 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HBR 2SI Replaces 25HBR 1SI P...

Отзывы: