Page 19
Outdoor Unit
Installation
NOTE:
The minimum distance between the
outdoor unit and walls described in the
installation guide does not apply to airtight
rooms. Be sure to keep the unit unobstructed
in at least two of the three directions (M, N, P)
(See Fig. 5.10)
M
N
P
30 cm / 11.8” from back wall
60 cm / 23.6”on right
60
cm
/ 2
3.
6”
ab
ov
e
30 cm / 11.8”on left
200 cm / 78” in fron
t
Fig. 5.10
D
W
Air inlet
Air inlet
Air inlet
Air inlet
(Wall or obstacle)
Table 5.2: Length Specifications of Vertical
Discharge Outdoor Unit (unit: mm/inch)
MODEL
DIMENSIONS
W
H
D
18
633/25
554/21.8
554/21.8
24
633/25
554/21.8
554/21.8
36
759/29.8
554/21.8
554/21.8
36
633/25
600/23.6
600/23.6
48
759/29.8
710/28
710/28
60
843/33
710/28
710/28
Fig. 5.8
Fig. 5.9
Fig. 5.11
L
H
300 cm / 118” or more
A
60 cm / 23.6”
or more
150 cm / 59”
or more
25 cm / 9.8”
or more
25 cm / 9.8”
or more
Rows of series installation
L
≤
H
L
≤
1/2H
L
A
25 cm / 9.8” or more
1/2H < L
≤
H
30 cm / 11.8” or more
L
>
H
Can not be installed
Table 5.3 The relations between H, A and L
are as follows.
Drain Joint Installation
If the drain joint comes with a rubber seal
(see Fig. 5.12 - A ), do the following:
1. Fit the rubber seal on the end of the drain joint
that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base
pan of the unit.
3. Rotate the drain joint 90° until it clicks in place
facing the front of the unit.
>45.7cm / 18”
>45.7cm / 18”
>45.7cm / 18”
>45.7cm / 18”