22
3 --- Water---level alarm --- diagnosis and solution
Error Code
E8
Malfunction conditions
If the sampling voltage is not 5V, the LED displays the failure.
Possible Causes
• Wiring mistake
• Water---level switch faulty
• Water pump faulty
• Indoor PCB faulty
If the water-level switch
is inserted well?
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Insert the water-level switch well
If the water-level switch
is broken?
If the water-level switch
is broken?
Yes
Replace the water-level switch
Replace the water-level switch
Replace the water pump, If
malfunction
is
still
not
solved
Replace the water pump, If
malfunction is still not
solved
Yes
No
Yes
Replace the indoor main PCB
Replace the indoor main PCB
Power off, then restart the unit 2 minutes
later. Is it still displaying the error code?
Power off, then restart the unit 2 minutes
later. Is it still displaying the error code?
Yes
ADDITIONAL INFORMATION FOR CRITICAL PARTS:
Temperature sensor troubleshooting
Disconnect the temperature sensor from the PCB, and measure the resistance value with a multimeter.
Temperature sensors:
1.
Room temperature (T1) sensor,
2.
Indoor coil temperature (T2) sensor,
3.
Outdoor coil temperature (T3) sensor,
4.
Outdoor ambient temperature (T4) sensor,
5.
Compressor discharge temperature (T5) sensor
Indoor Fan Motor
Measure the resistance value of each winding by using the multimeter.