7
Table 3 — Leg Weight Distribution
(Single and Dual Circuit Units)
09AZV
SINGLE CIRCUIT
DUAL CIRCUIT
091 101 151 171 181 102 112 122 132 142 162 172 182
A
268 302 308 373 377 291 316 302 403 311 308 373 382
B
613 691 462 560 566 665 475 691 605 467 462 560 573
C
268 302 462 560 566 291 475 302 605 467 462 560 573
D
—
—
308 373 377
—
316
—
403 311 308 373 382
E
268 302 308 373 377 291 316 302 403 311 308 373 382
F
613 691 462 560 566 665 475 691 605 467 462 560 573
G
268 302 462 560 566 291 475 302 605 467 462 560 573
H
—
—
308 373 377
—
316
—
403 311 308 373 382
1/2” LEG BOLTS
Fig. 4 — Unit Rigging
A. ROTATE UNIT FLAT
1. Gently pull top of unit over, maintaining cable tension as unit is
rotated from vertical to horizontal position.
B. LOWERING LEGS INTO POSITION
1. Reattach lifting hooks into lifting eyes in the perma-
nently attached leg channels. (One set of hooks at
each leg position).
2. Remove the four
1
/
2
bolts that hold each leg in
telescoped position.
3. Lift unit about 18
so that each leg can drop down
and be reattached with the four bolts removed in
Step 2. Tighten bolts securely.
4. Continue lifting unit to its new home.
A
C
D
H
G
E
F
B
HEADER END