CL-1

START-UP CHECKLIST

I.  PRELIMINARY INFORMATION

COMPRESSOR BEARING UNIT:

MODEL NO. ___________________

SERIAL NO. ___________________

09AZ UNIT:

MODEL NO. ___________________

SERIAL NO. ___________________

FIELD-INSTALLED ACCESSORIES  ________________________________________________________________________
________________________________________________________________________________________________________

II. PRE-START-UP

INDOOR/COMPRESSOR UNIT

IS THERE ANY SHIPPING DAMAGE? ___________________    (Y/N) ________
IF SO, WHERE: __________________________________________________________________________________________

WILL THIS DAMAGE PREVENT UNIT START-UP?

(Y/N) ________

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

(Y/N) ________

HAS THE GROUND WIRE BEEN CONNECTED:

(Y/N) ________

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N) ________

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N) ________

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) ________
DO THE FAN BELTS HAVE PROPER TENSION?

(Y/N) ________

HAS CORRECT FAN ROTATION BEEN CONFIRMED?

(Y/N) ________

HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DAINAGE?

(Y/N) ________

ARE PROPER AIR FILTERS IN PLACE?

(Y/N) ________

CONTROLS

HAVE THERMOSTAT, INDOOR-FAN CONTROL AND CONDENSER FAN CONTROL RELAY WIRING 

CONNECTIONS BEEN MADE AND CHECKED?

(Y/N) ________

ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) ________
HAS CRANKCASE HEATER (IF EQUIPPED) ON UNIT BEEN ENERGIZED FOR 24 HOURS? (Y/N) ________

09AZ UNIT

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

(Y/N) ________

HAS THE GROUND WIRE BEEN CONNECTED?

(Y/N) ________

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N) ________

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N) ________

HAS UNIT BEEN PROPERLY SECURED TO BUILDING STRUCTURE?

(Y/N) ________

HAS CORRECT FAN ROTATION BEEN CONFIRMED?

(Y/N) ________

PIPING

HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR, TXV’s 

(Thermostatic Expansion Valve), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A 

LEAK DETECTOR?          (Y/N) ________
LOCATE, REPAIR, AND REPORT ANY LEAKS
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (Backseated)? (Y/N) ________
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED?

(Y/N) ________

IS THE OIL LEVEL IN THE COMPRESSOR CRANKCASE ON THE UNIT IN VIEW IN THE COMPRESSOR SIGHT

GLASS (IF APPROPRIATE)?

(Y/N) ________

HAS CONDENSER PRESSURE RELIEF BEEN PROVIDED? (Y/N) ________

Downloaded from 

ManualsNet.com

 search engine

Содержание 09AZ091-182

Страница 1: ...d fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Separate power sources main and control power circuits are used for these units Be sure both main and control power circuits are disconnected before servicing Electrical shock could cause personal injury DO NOT USE TORCH to remove any component System contains oil and refrigerant under pressure To remo...

Страница 2: ...ing weights dis tance between lifting holes center of gravity and spreader bar dimensions If overhead rigging is not possible place unit on skid or pad for rolling or dragging When dragging pull the pad Do not apply force to the unit When in final position raise from above to lift unit off skid PLACING UNIT The 09AZ units are designed for outdoor applications If the unit is mounted indoors provisi...

Страница 3: ...th Contactors D Fan Cycling TEAO Circuiting Option A Single Circuit Subcooling E Dual Circuit Subcooling Factory Options A Aluminum Cabinet B Fused Disconnect D Aluminum Cabinet Fused Disconnect F Fused Disconnect 115 Volt Transformer Packaging 1 Standard Design Series 0 First Design V Ph Hz 1 575 3 60 3 208 230 1 60 5 208 230 3 60 6 460 3 60 Coil Construction Option Aluminum Fin Copper Tube C Cop...

Страница 4: ... 3164 2590 4032 3110 3081 3730 3820 Shipping Weight 2705 3374 2800 4242 3370 3450 4040 4130 REFRIGERANT Type 134a FAN Type Direct Drive Vertical Discharge Quantity 8 10 8 10 10 12 12 12 Diameter in 26 26 26 26 26 26 26 26 No of Blades 4 4 4 4 4 4 4 4 Max Rpm 1140 1140 1140 1140 1140 1140 1140 1140 Total Airflow Cfm 124 000 155 000 124 000 155 000 155 000 186 000 186 000 186 000 Motor Hp 11 2 11 2 ...

Страница 5: ...YP 194 1 4 96 TYP 1 1 8 TYP 15 6 6 242 1 4 48 96 TYP 1 1 8 TYP 15 CONTROL PANEL RETURN BEND COVER LIFTING HOLE 1 1 2 DIA TYP 6 290 1 4 96 TYP 1 1 8 TYP 15 6 IN DISCHARGE GAS 3 1 8 DIA LIQUID 2 5 8 DIA AIRFLOW 47 000 60 20 20 20 09AZV 1 A Single Circuit NOTES 1 Service clearances must be at least 48 in on all sides 2 Field assembly of discharge liquid headers required 09AZV091 101 09AZV151 09AZV171...

Страница 6: ... 1 1 2 DIA TYP 194 1 4 96 TYP 1 1 8 TYP 6 6 242 1 4 48 96 TYP 1 1 8 TYP CONTROL PANEL RETURN BEND COVER LIFTING HOLE 1 1 2 DIA TYP 6 290 1 4 96 TYP 1 1 8 TYP 6 6 IN 46 DISCHARGE GAS 2 5 8 DIA DISCHARGE GAS 2 5 8 DIA 94 LIQUID 2 1 8 DIA LIQUID 2 1 8 DIA AIRFLOW 6 5 5 6 6 5 5 09AZV 2 E Dual Circuit NOTE Service clearances must be at least 48 in on all sides 09AZV102 122 09AZV112 132 142 09AZV162 172...

Страница 7: ...02 605 467 462 560 573 H 308 373 377 316 403 311 308 373 382 1 2 LEG BOLTS Fig 4 Unit Rigging A ROTATE UNIT FLAT 1 Gently pull top of unit over maintaining cable tension as unit is rotated from vertical to horizontal position B LOWERING LEGS INTO POSITION 1 Reattach lifting hooks into lifting eyes in the perma nently attached leg channels One set of hooks at each leg position 2 Remove the four 1 2...

Страница 8: ...nual Part 3 or the Carrier E20 II Software Refrigerant Piping program for proper piping sizes and design 4 Hot gas lines should rise above refrigerant level in condenser circuit 5 Trap should be installed on hot gas lines to prevent condenser oil and refrigerant vapor migration from accumulating on com pressor heads during off cycle 6 For piping lengths greater than 50 ft 15 2 m provide support to...

Страница 9: ...ing speed control head pressure control winter start control fan cycling and electrical interlock may affect wiring connec tions Refer to Fig 7 9 for typical unit wiring 1 Power entry is at one end only 2 Fan motors are thermally protected All 3 phase motors are protected against primary single phasing conditions 3 Replacement of factory wires must be with appliance wiring material rated 105 C or ...

Страница 10: ...5 1 60 09AZV SIZE 208 230 3 60 460 3 60 575 3 60 CONTROL CIRCUIT V Ph Hz FLA MCA MOCP Min Max Volts FLA MCA MOCP Min Max Volts FLA MCA MOCP Min Max Volts 102 6 5 53 6 60 0 187 253 3 3 27 2 30 0 414 506 2 4 19 8 20 0 518 632 115 1 60 112 6 5 66 0 70 0 187 253 3 3 33 8 35 0 414 506 2 4 24 6 25 0 518 632 115 1 60 122 6 5 56 3 60 0 187 253 3 3 27 2 30 0 414 506 2 4 19 8 20 0 518 632 115 1 60 132 6 5 6...

Страница 11: ...60 C copper conductors only 2 See nameplate for branch circuit fuse size use time delay fuse only 3 Motors 1 and 2 are located at header end of unit 4 All wire is 14 ga except as noted C Contactor FB Fuse Block MTR Motor Downloaded from ManualsNet com search engine ...

Страница 12: ...tor FB Fuse Block NOTES 1 Use 60 C copper conductors only 2 See nameplate for branch circuit fuse size use time delay fuse only 3 Motors 1 and 2 are located at header end of unit 4 All wire is 14 ga except as noted Downloaded from ManualsNet com search engine ...

Страница 13: ...the key 6 Replace the permagum sealing material and the rubber cap over the end of the motor shaft to prevent moisture from causing fan to rust on the shaft 7 Replace the fan guard Fan Motor Removal 1 Make certain condenser power is off 2 Remove fan guard and fan 3 Loosen nut on the motor holding clamp that secures mo tor to motor support 4 Lift motor upward Remove the fan wheel through the fan di...

Страница 14: ...not operating correctly 1 Check head pressure control and be sure it is operating properly Install if not provided 2 Check wind baffles apply if required 3 Check operation of fan cycling control on two fan units Unit trips on low pressure at start up with low outdoor temperatures 1 Winterstart kit not installed or not working correctly 2 Fan cycling control for two fan units is not installed or no...

Страница 15: ... TO CONFIRM PROPER DAINAGE Y N ________ ARE PROPER AIR FILTERS IN PLACE Y N ________ CONTROLS HAVE THERMOSTAT INDOOR FAN CONTROL AND CONDENSER FAN CONTROL RELAY WIRING CONNECTIONS BEEN MADE AND CHECKED Y N ________ ARE ALL WIRING TERMINALS including main power supply TIGHT Y N ________ HAS CRANKCASE HEATER IF EQUIPPED ON UNIT BEEN ENERGIZED FOR 24 HOURS Y N ________ 09AZ UNIT CHECK POWER SUPPLY DO...

Страница 16: ...FTER AT LEAST 15 MINUTES RUNNING TIME RECORD THE FOLLOWING MEASUREMENTS OIL PRESSURE Where Appropriate ________ ________ SUCTION PRESSURE ________ ________ SUCTION LINE TEMP ________ ________ DISCHARGE PRESSURE ________ ________ DISCHARGE LINE TEMP ________ ________ ENTERING CONDENSER AIR TEMP ________ ________ LEAVING CONDENSER AIR TEMP ________ ________ EVAP ENTERING AIR DB dry bulb TEMP _______...