TABLE 1 SPECIFICATIONS
mm
07KHP
012
07KHP
018
07KHP
024
07KHP
040
07KHP
060
07KHP
090
H
508.0 623.0
H1
355.0 549.0
H2
254.0
H3
179.0
H4
105.0
L
569.0
W
680.0
W1
329.0
W2
179.0
W3
130.0
W4
420.0
07KHP
MODEL
013
018
024
040
060
090
RATED CAPACITY
(TONS)
1.0 1.5 2.0 3.0 5.0 7.5
CDU POWER INPUT
(kW)
1.08
1.75
2.22
3.15
5.15
6.45
NET WEIGHT
(kg)
52 54 63 70 78 93
Type
R-22
REFRIGERANT
Charging method
By Superheat Method
Type
Rotary Scroll
Compr. Model
RH189NRAT
RH277NHDT
PH39NPBT
NH52NAHT
ZR61KC-TF5 ZR81KC-TF5
RLA (A)
4.8
7.8
12.6
16.8
20.7
25.0
LRA (A)
35
47
66
91
139
179
COMPRESSORS
Refill Oil Charged (lit. / oz)
0.52 / 17.6
0.52 / 17.6
0.90 / 30
1.30 / 44
1.83 / 62
1.66 / 56
Quantity
1
PLATE HEAT EXCHANGER
(STAINLESS STEEL)
Water Inlet / Outlet ,mm (in.)
25.4 (1”) FPT
Suction,mm (in.) Flare Type
12.7 (1/2)
12.7 (1/2)
15.8 (5/8)
15.8 (5/8)
19.05 (3/4)
S-28.6
(1-1/8)
REFRIGERANT CONNECTIONS
Liquid, mm (in.) Flare Type
6.35 (¼)
6.35 (¼)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
S-15.8 (5/8)
High Press (PSIG)
426 ± 7 / 320 ± 20
CONTROL PRESSURESTAT SETTINGS
(Open / Close pressure settings)
Low Press (PSIG)
n.a.
27 ± 4 / 67 ± 7
POWER SOURCE (V-Ph-Hz) NOMINAL
(V)
208/230 - 1 - 60
230 - 3 - 60
PERMISSIBLE MIN-MAX VOLTAGE
(V)
197 - 253
REFRIGERANT CONTROL DEVICE IN UNIT
Capillary Tube
Capillary*/Accurator**
RLA : Rated Load Amps LRA : Locked Rotor Amps
Data rated at 29.5° Water Out, 27°C/19°C Indoor Condition
* - Capillary tube located at FCU on model ASBFM0360-060 (Floor Standing)
** - Accurator is located at FCU on model 42AR0036-060 (Ceiling Type), 42GKX036-060(Cassette
type), 42LX036-060(Ceiling-Ducted). 7.5TR system normally uses TXV metering device.
Note: Refill oil charge is for service use after compressor has been drained. This value is different
and less than Factory oil charged. Use only corresponding compressor maker approved specs.
(S) under refrigerant connections section means Sweat Type connection.
FIG. 2 DIMENSIONAL DRAWING
FRONT VIEW
TOP VIEW
Содержание 07KHP
Страница 5: ...5 FIG 6 CEILING MOUNTED INSTALLATION FIG 7 FLOOR MOUNTED INSTALLATION ...
Страница 8: ......
Страница 10: ...10 FIG 8 WIRING DIAGRAM 07KHP012 FIG 9 WIRING DIAGRAM 07KHP018 024 ...
Страница 11: ...11 FIG 10 WIRING DIAGRAM 07KHP040 050 FIG 11 WIRING DIAGRAM 07KHP060 ...
Страница 12: ...12 FIG 12 WIRING DIAGRAM 07KHP090 FIG 13 RECOMMENDED SERVICE CLEARANCES ...