Applicable controls
REQUIREMENT
When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
Use the wired remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, sub remote controller,
or remote-controller-less system (for central
remote controller only). Therefore, install the
wired remote controller to change the settings.
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working.
(Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT31E). (There are more CODE No.)
1
Push and hold
button and “TEMP.”
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
If the CODE No. is not [01], push
button to
clear the display content, and repeat the
procedure from the beginning. (No operation of
the remote controller is accepted for a while
after
button
is
pushed.)
(While air conditioners are operated under the
group control, “ALL” is displayed first. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 5 minutes
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 1 minutes
1
6
1
3
2
5
4
(* Display content varies with the indoor unit
model.)
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with “TEMP.”
/ buttons.
4
Select SET DATA [
] with “TIME”
/ buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
To change settings of another indoor unit,
repeat from Procedure
2
.
To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
Installing indoor unit on high
ceiling
When the height of the ceiling to be installed exceeds
3.5 m, adjustment of air volume is necessary.
Set up the high ceiling.
Set according to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
CODE No. in Procedure specifies [5d].
Select [SET DATA] in Procedure from “List of
installable ceiling height” in this Manual.
For the CODE No. in Procedure
3
, specify [5d].
For the CODE No. in Procedure
4
, select the SET
DATA of ceiling height to be set up from the table on
the below.
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the indoor unit P.C. board.
* Once the setting is changed, setting to 0001 is
possible, however setting to 0000 requires a setting
data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to “
0000
”.
SET DATA
SW501-1
SW501-2
0000
(Factory default)
OFF
OFF
0003
OFF
ON
SW501-2
MCU(IC501)
SW501-1
– 16 –
31-EN
32-EN
Model
SET
DATA
Standard
(Factory default)
Up to 3.5 m
Up to 3.5 m
0000
High ceiling (1)
Up to 4.0 m
Up to 4.3 m
0003
0131CP,
0181CP,
0241CP
0301CP,
0361CP,
0401CP,
0481CP,
0601CP
1115652934_EN_TH.indd 16
1115652934_EN_TH.indd 16
5/12/20 3:02 PM
5/12/20 3:02 PM