General Data-39TF-S
Fresh air condition
Model
Air
Flow
4Rows
6Rows
Condensate
Water Pipe
Power
Supply
Drive
Type
Rated
Cooling
Capacity
Rated
Heating
Capacity
Water
Flow
Water
Pressure
Drop
Motor
Power
Chilled
Water
Pipe
Rated
Cooling
Capacity
Rated
Heating
Capacity
Water
Flow
Water
Pressure
Drop
Motor
Power
Chilled
Water
Pipe
39TF
m
3
/h
kW
kW
I/s
kPa
kW
DN
kW
kW
I/s
kPa
kW
DN
DN
010
1000
5.1
10.2
0.24
3.0
0.18
32
7.2
12.4
0.34
8.8
0.18
32
25
380V
3N~
50Hz
Direct
Drive
020
2000
11.5
21.2
0.55
11.0
0.32
32
14.9
25.3
0.71
26.0
0.32
32
25
030
3000
17.5
32.0
0.83
31.0
1.1
32
22.0
37.3
1.05
62.0
1.1
32
25
Belt
Drive
040
4000
23.4
41.5
1.13
60.0
1.1
40
30.1
49.1
1.43
49.5
1.1
40
25
050
5000
28.3
51.4
1.37
40.0
1.5
40
35.2
61.8
1.68
78.0
2.2
40
25
060
6000
34.5
61.7
1.64
47.0
1.5
40
43.7
73.9
2.08
44.0
2.2
40
25
070
7000
40.3
71.3
1.92
66.0
1.5
40
49.4
85.3
2.35
59.0
2.2
50
25
080
8000
46.2
83.1
2.20
58.0
2.2
40
57.6
98.3
2.74
56.0
3.0
50
25
090
9000
52.1
93.1
2.48
79.0
2.2
40
64.8
110.3
3.09
25.4
3.0
50
25
105 10500
59.9
108.1
2.85
51.0
3.0
50
75.1
135.3
3.58
39.0
3.0
50
25
120 12000
69.3
131.7
3.3
57.0
4.0
50
85.8
161.1
4.09
44.0
4.0
50
25
Model
Air
Flow
4Rows
6Rows
Condensate
Water Pipe
Power
Supply
Drive
Type
Rated
Cooling
Capacity
Rated
Heating
Capacity
Water
Flow
Water
Pressure
Drop
Motor
Power
Chilled
Water
Pipe
Rated
Cooling
Capacity
Rated
Heating
Capacity
Water
Flow
Water
Pressure
Drop
Motor
Power
Chilled
Water
Pipe
39TF
m
3
/h
kW
kW
I/s
kPa
kW
DN
kW
kW
I/s
kPa
kW
DN
DN
010
1000
13.9
13.2
0.66
16.0
0.18
32
15.8
15.6
0.75
31.0
0.18
32
25
380V
3N~
50Hz
Direct
Drive
020
2000
27.0
27.5
1.29
49.0
0.32
32
31.2
31.3
1.49
35.0
0.32
32
25
030
3000
39.9
40.9
1.90
48.0
1.1
40
45.8
45.1
2.18
80.0
1.1
40
25
Belt
Drive
040
4000
49.7
51.1
2.37
38.0
1.1
40
63.8
61.8
3.04
76.0
1.1
50
25
050
5000
64.5
64.0
3.07
63.0
1.5
50
75.4
70.3
3.59
51.0
2.2
50
25
060
6000
72.7
75.5
3.46
74.0
1.5
50
92.6
91.9
4.41
57.0
2.2
50
25
070
7000
84.1
87.1
4.00
17.0
1.5
50
105.6
104.8
5.03
80.0
2.2
65
25
080
8000
99.0
101.7
4.71
14.4
2.2
50
120.7
119.7
5.75
30.0
3.0
65
25
090
9000
111.0
113.8
5.29
19.0
2.2
65
137.3
135.3
6.54
41.0
3.0
65
25
105 10500
133.1
133.4
6.34
31.0
3.0
65
160.2
157.9
7.63
57.9
3.0
80
25
120 12000
149.4
155.1
7.12
35.0
4.0
65
185.2
180.4
8.20
68.8
4.0
80
25
NOTE:
1. Cooling capacity is based on the following:
a) Inlet and outlet water temperature: 7°C/12°C b) Air entering condition: 35°C DB/28°C WB
2. Heating capacity is based on the following(with the same water flow rate as cooling mode):
a) Inlet and outlet water temperature: 60°C/50°C b) Air entering condition: 7°C DB
3. The manufacturer reserves the rights to make changes to the above specifications without prior notice.
4. The water flow in the above table indicates the cold water supply flow. Because the hot water supply flow is smaller than cold water supply flow, cold water
supply flow is provided in the table for your reference to select the water pump.
5. The external static pressure is 0 Pa. If an air duct is required, please specify when you make the order.
NOTE:
1. Cooling capacity is based on the following:
a) Inlet and outlet water temperature: 7°C/12°C b) Air entering condition: 27°C DB/19.5°C WB
2. Heating capacity is based on the following(with the same water flow rate as cooling mode):
a) Inlet and outlet water temperature: 60°C/50°C b) Air entering condition: 15°C DB
3. The manufacturer reserves the rights to make changes to the above specifications without prior notice.
4. The water flow in the above table indicates the cold water supply flow. Because the hot water supply flow is smaller than cold water supply flow, cold water
supply flow is provided in the table for your reference to select the water pump.
5. The external static pressure is 0 Pa. If an air duct is required, please specify when you make the order.
Return air condition
AIR HANDLING UNIT
11
CARRIER
Содержание 010
Страница 1: ...AC Fan Mini Air Handling Unit Ceiling Concealed Type ...
Страница 17: ...39TF D B S Wiring Diagrams AIR HANDLING UNIT 17 CARRIER ...
Страница 22: ...Note 22 CARRIER ...
Страница 23: ...Note AIR HANDLING UNIT 23 CARRIER ...
Страница 24: ...The Manufacturer reserves the right to change any produt specifications without prior notices ...