Accumulate or Reset
Factory default is set so the timer continues where it left off after a power cycle
(accumulate). This prevents the timer from re-starting in the event of an electrical
brown-out or power outage. To change the setting so the timer re-starts to zero when
power is cycled, follow the steps below. A power outage will not change the cycle time
(SET1 & SET2) values.
6. Hold the MODE button down for 3 seconds
7. The red display will show ōFtr.
8. Press the MODE button three times until tōtm is displayed 9red letters)
9. Use the up and down arrow buttons to change the green display from tōF1 to
tōFF
10.
Hold the MODE button down for 3 seconds to return to the normal mode
Setting the 2
nd
Set-point (also called idle set point)
To set the “day” and “night” temperature and humidity (optional) settings on the
controller, use the following procedure.
To adjust the “day” set-point:
1. press the ADVANCE button several times from the home page until “id.S1” is
displayed.
2. set the set-point using the UP & DOWN arrow buttons
3. exit to the home page by pressing the INFINITY button
To adjust the “night” set-point, from the home page, set the set-point using the UP &
DOWN arrow buttons
Accumulate
Reset