RGC
Installation Instructions
X =
product
width
Y2 =
100mm
Y1 = 5mm
Connection Specifications
POWER CONNECTIONS: 1/L1, 2 /T2
Torque specifications
2 Nm (17.7 in-lb)
M4, Pozidriv 2
Use 75°C copper (Cu)
conductors
Stripping Length (X) = 11mm
Rigid (Solid & Stranded)
UL/ CSA rated data
2 x 2.5..6 mm
2
2 x 2.5..6 mm
2
2 x 14..10 AWG
1 x 14..10 AWG
Flexible with end sleeve
2 x 2.5..4mm
2
2 x 2.5..4mm
2
2 x 14..12AWG
1 x 14..12AWG
Flexible without end sleeve
2 x 2.5..6 mm
2
1 x 2.5..6 mm
2
2 x 14..10 AWG
1 x 14..10 AWG
Aperture for termination lug
12.3mm
CONTROL CONNECTIONS: A1(+), A2(-)
Torque specifications
0.5 Nm (4.4 in-lb)
M3, Pozidriv 1
Use 60/75°C copper (Cu)
conductors
Stripping Length (X) = 6mm
Rigid (Solid & Stranded)
2 x 0.5..2.5mm
2
1 x 0.5..2.5mm
2
2 x 18..12 AWG
1 x 18..12 AWG
Flexible with end sleeve
2 x 0.5..2.5mm
2
1 x 0.5..2.5mm
2
2 x 18..12AWG
1 x 18..12AWG
Protective Earth Connection
RGC..20: M4; RGC..30: M5
1.5Nm (13.3 in-lb)
Note: Protective Earth connection must be connected whenever the product
is intended to be used in Class 1 applications according to EN/IEC 61140.
X
X