10
only for signalling functions and
not for safety functions .
OPERATING MODE
With manual START configura-
tion, the safety outputs close, if
S1 & S2 are operated, when the
NO START pushbutton is pushed .
With automatic START configu-
ration, the safety outputs close
(NES13DB opens the auxiliary
output) as soon as both S1 & S2
switches are operated . The CH1 &
CHl 2 LED turn on .
Releasing even one input contact
(S1 and/or S2) forces immediately
the safety outputs to an open sta-
tus (NES13DB closes the auxiliary
output) . The LED relative to the
channel whose input has been
released turns off .
A new operating cycle is possi-
ble only after releasing both input
contacts and then operating them
again (and pushing the START
button, if the safety module has
been set up with manual START
configuration) .
For the “SC” and “DC” models it
is necessary a minimum delay of
500 ms from the operated status
of the input contacts to the pushing
of the START button . The same
delay is necessary between the
START button releasing and re-
operating, if the input terminals
have been previously operated
with the START button already
pushed .
In the models with monitored
manual START configuration, if
the NO START button gets wel-
ded, the safety outputs cannot
close their contacts any more .
TEST & ACTIVATION
The following operations must
be repeated when the module is
installed and every time the wiring
is changed and at regular intervals
by carrying out in sequence all the
steps described below without any
type of dangerous condition for the
operators .
STEP 1
Check the integrity, the
correct installation, the correct
positioning on the machine and
the correct functioning of all the
devices connected to the inputs
and to the outputs of the module .
Check also the correct wiring of all
the devices .
STEP 2
Power on the safety
module: the
POWER
LED turns on
(this LED has to be considered ON
in all the steps of this sequence) .
The
CH1
and
CH2
LEDs are off,
the safety outputs open and the
auxiliary output is closed .
Operate the input contacts: the
safety outputs are open and the
CH1
&
CH2
LEDs are off (if the
module is configured for automatic
START,
CH1
&
CH2
LEDs turns
on, the safety outputs close) .
Close the START contact: the