background image

6

pushed).

The

CH1

&

CH2

LEDs  turn  on  as

soon as the safety outputs close.

Pushing  the  E-STOP button  leads

to  a  safety  condition,  forcing  the

safety  outputs  to  an  open  status

when  the  delay  has  expired.  The

POW ER

,

CH1

&

CH2

LEDs turn off.

A new  operating  cycle  is  possible

only  after  releasing  the  E-STOP

button  (and  pushing  the  START

button,  if  the  safety  module  has

been  set  up  with  manual  START

configuration).

6.

TEST & ACTIVATION

The  following  operations  must  be

repeated  when  the  module  is

installed and every time the wiring

is changed and at regular intervals

by carrying out in sequence all the

steps described below without any

type of dangerous condition for the

operators.

STEP

1

Check  the  integrity,  the

correct  installation,  the  correct

positioning on the machine and the

correct  functioning  of  all  the

devices  connected  to  the  inputs

and  to  the  outputs  of  the 

NA13CT

safety module. Check also the cor-

rect  wiring  of  all  the  devices  (See

4.2)  and  the  integrity  of  the  labels

and documentation.

STEP 2

Power  on  the  safety  mod-

ule with E-STOP button not pushed:

with  manual  START configuration

the 

POW ER

LED  turns  on,  while

the 

CH1

and 

CH2

LEDs are off, the

safety  outputs  are  open  and  the

auxiary  output  is  closed  (in  auto-

matic  START configuration  all  the

LEDs  are  on,  the  safety  outputs

are closed and the auxiliary output

is open).

Close the N.O.START contact: the

safety  outputs  close,  the  auxiliary

output  opens  and  the 

CH1

,

CH2

LEDs turn on.

STEP 3

Push  the  E-STOP button:

the  safety  outputs  open  (after  the

delay  has  expired),  the  auxiliary

output  closes  and  the 

POW ER

,

CH1

,

CH2

LEDs  turn  off (always

when the delay has expired).

Repeat  STEP 2 checking  that  the

safety  outputs  do  not  close  -  with

manual START configuration - sim-

ply  releasing  the  E-STOP device,

without pushing the START button.

Check also that the safety outputs

do not close, that the auxiliary out-

put  does  not  open,  and  that  the

POW ER

,

CH1

,

CH2

LEDs  are  off

simply  pushing  the  START button

with E-STOP button pushed.

If more than one E-STOP is used,

the  STEPS  2  and  3  must  be

repeated for each device.

7.

USAGE PRECAUTIONS

The  safety  module  can  check  the

integrity  of  external  contactors  or

expansion  modules  simply  con-

Содержание NA13CT

Страница 1: ...User Manual User Manual SAFETY SAFETY MO DULE MO DULE NA1 3 CT NA1 3 CT...

Страница 2: ...e r s u p p ly 5 4 4 E S T O P c o nne c tio n 5 4 5 S T A R T C irc u it 5 4 6 S afe ty O u tp u ts 5 4 7 A u x iliary o u tp u t 5 5 OP E RA TING MODE 5 6 TEST ACTIV A TION 6 7 USAGE PRECAUTIONS 6 8...

Страница 3: ...imp ro p erly used by no t f o llo wingo nlyand all the indic atio ns o fthis manual o r whenev er these indic atio ns are p artially inc o rrec tly o r inc o mp letely ap p lied by p erso n nel unsp...

Страница 4: ...he safety of the operator any more and the warranty is void T o avoid interference due to cou pling run the limit switches con necting conductors separately from the power conductors Avoid the risk of...

Страница 5: ...it The safety module can be config ured for manual START not mon itored for welding fault or auto matic START T o set up the manual START con figuration it is necessary to con nect a N O pushbutton t...

Страница 6: ...ation STEP 2 Power on the safety mod ule with E STOP button not pushed with manual START configuration the POW ER LED turns on while the CH1 and CH2 LEDs are off the safety outputs are open and the au...

Страница 7: ...range in designing his own machine in order to avoid the pos sibility for the operator to reach hazardous areas when dangerous situations are still active The NA13CT safety relay can be employed also...

Страница 8: ...lose with automatic START or are enabled to close with manual START When the E STOP button is pushed the safety module is switched off the safety outputs open and the auxiliary output clos es as soon...

Страница 9: ...9 Fig 4 NA13CT application with two double channel E STOP devices Fig 5 NA13CT application with two single channel E STOP devices...

Страница 10: ...ntacts Max Switching Voltage AC 250 V Max Switching Current 6 A Max Switching Power Resistive Load 1500 VA Output contacts protection External fuse 4 A Mechanical Life 10 7 switching cycles Electrical...

Страница 11: ...rotection degree of the module IP30 Minimum Protection degree of the installation location IP54 EMC compatibility EN 61000 6 2 EN 61000 6 3 Operating T emperature 20 55 C Storage T emperature 25 75 C...

Страница 12: ...12 CARLO GAVAZZI reserves the right to make improvements or changes without prior notice 8020731 MOD NA13CT...

Отзывы: