9. Technical data
All the distances involved are referred to a sample MC36CM device, with MC36CH/MC36CM pairs mounted far away
from other magnetic parts or devices, and with MC36CH frontally operated (see Fig. 2).
9.1 Electrical data
Rated operational voltage Ue
12-24 V AC/DC
Rated insulation voltage Ui
Cable version / M12: 120 Vac
M8 connector version: 60 Vac / 75 Vdc
Rated impulse withstand voltage Uimp
6 kV / 1.5 kV (with M8 connector)
Protection class
III
Reverse polarity protection
Yes
9.2 Outputs
Output function
2 x NO, 1 x NO + 1 x NC, 2 x NO + 1 x NC
Voltage drop
3.5 V for sensors with LED
0.5 V for sensors without LED
Rated operational current Ie
0.25 A (resistive load)
Short circuit proof
No
Switching frequency
100 Hz
Max switching load
6W (resistive load)
Thermal current Ith
0.25 A
9.3 Actuating characteristics
Operating principle
Magnetic
Actuator
MC36CM coded
Coding level according to EN ISO 14119
Low
9.4 Switching distances (with MC36CM)
Assured switching distance Sao
5 mm*
Assured switch-off distance Sar
15 mm*
Repeat accuracy
≤ 10%
Distance between two sensors
Min. 50 mm
9.5 Environmental conditions
Application (according to EN 60654-1)
Class C
Operating temperature
-25…80 °C (-13...176 °F)
Max. perm. Relative humidity
Short time: 5...95%
Permanent: 5...70%
Protection class (IEC 60529)
IP67; IP69K for M8 versions without LED
Pollution degree
3
9.6 Approvals / tests
EMC
IEC 60947-5-2
Shock resistance (EN 60068-2-27)
30 g (11 ms)
Vibration resistance (EN 60068-2-6)
10 g (10…150 Hz)