CARLO GAVAZZI G 3800 X015 Скачать руководство пользователя страница 23

© 2002 Carlo Gavazzi Industri A/S. All rights reserved

23

G 3800 X015 Configuration Software

October 2002

Tip: Entire address groups can be changed by clicking on the right mouse button.

Time characteristics (without toggle function selected)

t

t

t

PMan_TMaster_1a

t

2

t

1

t

4

t

3

IN

OUT

Switched
outputs

Toggle switch

function

Push button

function

The master function remains active until the input is switched off. In the above example, the outputs switch on,
and - in the case of a push button function - remain on, until the master function switches off again.

Parameter

Description

Address matrix

Mark the addresses to be switched on by the master function with “1” and the
addresses to be switched off with “0”.*
Addresses marked with “x” are not affected. Addresses which are automatically
marked with a red line cannot be controlled by a master function, eg master func-
tions, roller blind controls, etc.

Toggle switch

If this function is selected, the master function will toggle between the selected
output status and the inverted output status, whenever the input is activated.

Include Real-time

A real-time clock is included to time-control the master function. The field “Enter
Switch times” appears.

Enter Switch times

Click here to open or close a matrix in which to enter switch times

Real-time clock

Normally, the real-time clock for time-control of the master function behaves in
the same way as the object “Real-time clock”. See chapter 2.2.5. Real-time clock
for further details.

Unlike a separate real-time clock, the built-in real-time clock only generates one
switching impulse. This is particularly important to bear in mind when the master
function is to control push button functions, since the switch signal may be of
very short duration.

As a Flip-Flop Master

The real-time function operates both ON-switching and OFF-switching. This
enables simultaneous ON- and OFF-switching of multiple channels. The channels
marked with “1” switch on when the master is activated and switch off upon
deactivation. The channels marked with “0” behave in the opposite way.  

Содержание G 3800 X015

Страница 1: ...Configuration Software G3800 X015 User Manual Preliminary Data December 2002 Du line Fieldbus Installationbus...

Страница 2: ...2 General features 33 2 4 3 ISA Alarm 34 2 4 4 The Smoke Alarm 39 2 4 5 The Intruder Alarm 44 2 4 6 The Water Alarm 50 2 4 7 Common Siren 55 2 5 Roller blind control 56 2 5 1 Decentralized roller bli...

Страница 3: ...2002 Carlo Gavazzi Industri A S All rights reserved 3 G 3800 X015 Configuration Software October 2002...

Страница 4: ...nder Windows 95 98 2000 xp and NT and requires at least 486 processor with 8 Mbytes Ram or higher A free serial port Com1 or Com2 5 Mbytes hard disk for installation Screen resolution of 800 x 600 pix...

Страница 5: ...ation New Start from the beginning with default data Open Open existing file Save Save file Save As Save file under new name Write Generator Download the present configuration file to the Generator Re...

Страница 6: ...is active when the current date falls within any of the set time intervals SMS only valid for G38001015 Basic setup of the SMS messaging functions facilitated by the built in GSM modem Counter and Mu...

Страница 7: ...rt Selection of Com 1 Com 2 Com 3 or Com 4 port for connection of the G3800X015 Generator 1 2 4 Tools menu Generator firmware In this menu it is possible to download a new firmware file to the Generat...

Страница 8: ...tri A S All rights reserved G 3800 X015 Configuration Software October 2002 Menu Item Explanation General information You can call the Help menu at any time by pressing F1 About program Shows the open...

Страница 9: ...channel function Click on the symbol with the left mouse button and the parameters which can be set for that particular channel function can be viewed in the properties window The arrow keys can also...

Страница 10: ...onfig download and System power up If this box is checked the Generator will automatically set the correct status for realtime channels according to the switch time settings provided that the actual D...

Страница 11: ...erved 11 G 3800 X015 Configuration Software October 2002 2 1 General The objects are the specific functions of the G 3800 X015 The functions are assigned to channels and the associated parameters dete...

Страница 12: ...n and output an input on the address con figured as blank function will be ineffective At the same time it is possible to control the channel and consequently the functions coded for the address eithe...

Страница 13: ...nverted in Normally Closed function Parameters Configuration window of push button function Time characteristics t t PManTTast_1a t3 t2 t1 t t PManTTast_2a t3 t2 t1 The output follows the input upon a...

Страница 14: ...ter Generator Push button function Light control A1 Application Example Task A lamp is to be switched on and off by means of a switch Solution Use for example the universal input module to provide the...

Страница 15: ...function Time characteristics t t PMan_TToggle_1a t3 t2 t1 The first triggering of the input switches the output on the second triggering switches the output off again Parameter Description Intruder a...

Страница 16: ...nerator Toggle switch function Light control A1 Application Example Task A lamp is to be switched on and off by means of a conventional switch Solution Use for example the universal input module to pr...

Страница 17: ...s a square wave signal The output is activated after the set on delay period and de activated after the set off delay period This process is repeated as long as the input or the additional trigger is...

Страница 18: ...hich will also enable the timer function To prevent locking the channel assigned to the timer itself must not be used If the additional signal is an impulse select the option Activation by pulse Recyc...

Страница 19: ...r module for example a univer sal input module and configured for address A1 as a toggle switch function An output of a relay module is assigned the same address and activates the lighting A second ch...

Страница 20: ...1 t4 t3 t5 Function Real time clock with week and holiday planner Application Time controlled switching on and off of loads Also applicable as switching function Holiday setting can be performed centr...

Страница 21: ...module to provide the input signal and configure one of the inputs for address A1 Assign the same address to one of the outputs of a relay module Finally configure channel A1 in the Master Generator...

Страница 22: ...ter function the decentral functions are accepted again It is to be noted in particular in connection with real time clocks that only one master command can apply at a time When several master functio...

Страница 23: ...selected the master function will toggle between the selected output status and the inverted output status whenever the input is activated Include Real time A real time clock is included to time cont...

Страница 24: ...er function Calling lighting A3 scene Push button function Dimmer channels B1 B4 1 4 B5 B8 Toggle switch function Lamps C1 C4 Application Example Task The master function is to control four lamps and...

Страница 25: ...m that this object operates like the measuring sensor Temperature sensor This object also operates in the same way as the measuring sensor but has its own icon for easy recognition General information...

Страница 26: ...his means that the channel switches off when the analog value drops below the first entered value and the channel switches on when the analog value exceeds the second entered value But this is rarely...

Страница 27: ...ernative input must be acti vated The value can be overwritten at any time and deleted again by the Delete key Off Limit These are the switching limits of the sensor object If the option Invert limits...

Страница 28: ...sor as switching channel t t t PMan_TTemp_1a t2 t1 t5 t3 t4 t6 t1 The room temperature drops to the value entered for On Limit eg 21 C Since no Disable Address is entered the object Temperature sensor...

Страница 29: ...ation Example Task A heating element is to keep the room temperature between 19 C and 21 C during daytime At night the temperature must be lowered by 4 C A temperature sensor located in the room is co...

Страница 30: ...false alarms in the intruder alarm Select with mouse Motion detector Parameter Description Off time The time for which the channel remains activated 00 00 00 to 99 59 59 after a motion impulse has occ...

Страница 31: ...integrated in the intruder alarm system whose alarm siren can also be seen in the below diagram The number of impulses has been set to 3 t t t PMan_TMotion_1a tP2 tP1 tP4 tP3 tP1 tP2 tP3 and tP4 are t...

Страница 32: ...der alarm Manual armouring Alarm siren Also in this case the motion detector activates the output module for the lighting directly on address A1 If the alarm system is activated via the manual armouri...

Страница 33: ...signals for the intruder alarm The inputs can be either floating or non floating contacts connected to the system through digital Dupline inputs 4 Water alarm chapter 2 4 6 The Water alarm was develop...

Страница 34: ...Subsequent acuation of the Reset button switches the alarm contact off and releases the alarm system If the Reset button is actuated before the Acknowledgement button the system will also switch off t...

Страница 35: ...stem prevents configuration of the Reset object Passive detector Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the mo...

Страница 36: ...owledge No configuration possibilities Reset No configuration possibilities Lamp test No configuration possibilities Alarm siren Siren time This setting determines for how long the alarm output is to...

Страница 37: ...reset of an alarm in the operation mode Auto reset t1 When all contacts are in off position the Master Generator alerts the alarm system automatically upon loading of the application If a contact is...

Страница 38: ...Lamp test Activation of all B3 LEDs on the panel ISA alarm Alarm siren Alarm sounding B4 Application Example Task In a chemical factory eight laboratories are to be provided with alarm switches Upon a...

Страница 39: ...nsure correct function The status of the alarm contacts can be shown in a simple way on a panel All that is needed for this purpose is that the output channels are coded to the addresses of the alarm...

Страница 40: ...r off any further alarms Active detector Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Active detector function of the monitoring system whereby i...

Страница 41: ...is setting you determine the duration of the activation of the alarm output upon the occurence of an alarm The value can lie between 0 and 60 min The entered value is automatically adopted by the Comm...

Страница 42: ...he Passive detector channel whereby the alarm source is indicated t3 The channel generator activates the alarm signal channel after elapse of the set alarm signal delay TM t4 By activation of the rese...

Страница 43: ...ipped with smoke detectors When an alarm occurs a siren switches on and the fire authorities are notified Solution The alarm channels of the smoke detector are assigned to channels C1 to C8 The alarm...

Страница 44: ...d before elapse of the alarm signal delay the system automatically becomes alert again Note Configuration of the objects Manual armouring Door lock armouring or Code lock armouring is absolutely neces...

Страница 45: ...tal enabling Upon activation of the switch the armouring delay begins to run During this time the channel generator ignores activated alarm contacts If subsequently an alarm contact is activated this...

Страница 46: ...1 Z8 whose activation 1 signal will leave out the Active detector function of the monitoring system whereby it cannot trig ger off any further alarms Manual armouring Door lock armouring Code lock arm...

Страница 47: ...siren channel is thereby constantly switched on Note The options Flash Interval and Flashing Channels only appear when the option Flash when Alarm has been selected Flash Interval Here you can enter...

Страница 48: ...ing happens at first t3 After elapse of the armouring delay TFV the alarm is started ie both the channel of the alarm contact and that of the Manual Armouring start to flash t4 After elapse of the de...

Страница 49: ...ystem When an alarm occurs a siren switches on and the police is informed via a telephone modem A panel shows the source of the alarm The system should moreover make it possible to disable the alarm c...

Страница 50: ...the object Reset is absolutely necessary to ensure correct function The status of the alarm contacts can be shown in a simple way on a panel All that is needed for this purpose is that the output cha...

Страница 51: ...will leave out the Passive detector function of the monitoring system whereby it cannot trig ger off any further alarms Active detector Disable address Enter an address A1 P8 or a flag W1 Z8 whose ac...

Страница 52: ...siren Siren time With this setting you determine the duration of the activation of the alarm output upon the occurence of an alarm The value can lie between 0 and 60 min The entered value is automatic...

Страница 53: ...y TEV which can run for 3 11 s depending on the number of channels t3 Upon elapse of the switch on delay TEV the Master Generator causes the output of the activated contact as well as the alarm siren...

Страница 54: ...on and the house owner is informed by means of an SMS message The room in question should be recognizable on a panel Solution The alarm channels of the water stop sensors are assigned to channels G1...

Страница 55: ...iren is independent of whether a siren was configured in the individual alarm system Note The signal time entered in the Common siren is automatically adopted by the individual sirens This also applie...

Страница 56: ...figuration the motor runs in the opposite direction the corre sponding connecting cables of the motor are reversed In this case correct connection must be ensured the channels must under no circumstan...

Страница 57: ...on of several motors Simultaneous activation of several motors can be achieved by 1 connecting all motors to separate outputs and 2 assigning the same address to all up channels as well as all down ch...

Страница 58: ...e start The entered roll time is overwritten by the roll time of the master Reverse delay Enter the delay time milliseconds before the roller blind changes direction The value should lie between 500 a...

Страница 59: ...s activated again Since the impulse this time is longer than the Reverse Up time TV the roller master control attempts to switch the channel on for the total roll time t3 An additional actuation in th...

Страница 60: ...system should include groupwise control for two different floors as well as master control of all roller blinds together To protect the roller blinds a wind sensor and a rain sensor are installed The...

Страница 61: ...set roll time starts again Thus it cannot be stopped By pressing the other direction key the motors stop shortly decentrally set Reverse Up time and run in the opposite direction until the end positi...

Страница 62: ...rvals This time interval is also observed in connection with change of direction or tilting blind Reverse Up time This time interval does not affect the set roll time Roll time The roll time determine...

Страница 63: ...ctuated whereby the roller blind is forced in the opposite direction The motors stop one by one and the Reverse delay TU set for the decentral roller blind object begins t4 After elapse of the Reverse...

Страница 64: ...ter module G 4420 7401 Apart from the setting the counter range it is also necessary to assign an address to each module through rotary switch Data format A description of the used data format can be...

Страница 65: ...er Relay output Switching power G1 N8 outlets Configuration of Master Generator Counter range Channels for B1 F8 counter values Toggle switch function Switches for power G1 N8 Application Example Task...

Страница 66: ...plied modules and can thus not be reserved by the Master Generator Also when the number is limited to 16 because only four channels have been reserved 112 values can actual ly be processed This is pos...

Страница 67: ...ad the preceding chapter 2 6 1 Multiplexer Transmission of counter values Working with test unit GTU8 GTU8 makes it easy to read out and simulate analog values of this format operation mode Analog BCD...

Страница 68: ...er or conditions The Master Generator offers a splendid tool for solving these tasks the logic functions with which any rela tion can be established between the individual channels The logic functions...

Страница 69: ...backwards Adding All fields in a logic setup must be filled in ie all 4 components must be available Any number of setups can be selected and gaps are allowed To add a function place the cursor in an...

Страница 70: ...ering on leading edge Adding a backslash in front of the address leads to triggering on trailing edge This change in ouput does not affect the input channels or flags 3 3 2 1 Inversion Inversion can b...

Страница 71: ...t stored upon voltage failure at the Master Generator Flags basically operate in the same way as the Push button function ie the value of the flags changes immediately with the result of the logic set...

Страница 72: ...can be controlled by sending commands via SMS messages In order to make use of the GSM modem the following is required A SIM card with the pin code 9090 needs to be inserted into the slot in the front...

Страница 73: ...rmed by sending either a request or just an empty SMS mes sage to the Generator Max User Response time Only valid when one by one to acknowledge is selected Here the maximum time the Generator shall w...

Страница 74: ...swer by sending back an SMS with the requested data The format of the SMS commands and requests are shown in the example below NB When using controlling commands on a channel which is also configured...

Страница 75: ...by the SMS command are the Toggle and Realtime channels For Push button Timer Master Roller Blind Alarm Reset and Acknow ledge channels an SMS ON command will initiate a pulse on the channel and ther...

Страница 76: ...l 3AS types from the Finnish manufacturer SATEL www satel fi These are not supplied by Carlo Gavazzi but are available with local support worldwide Find below an application diagram for the Radio Mode...

Страница 77: ...to the next substation The default time is 1 s which is fine for most applications but longer time may be needed if repeater stations are used on the radio modems No of substations Defines the number...

Страница 78: ...radio communication Per default the substations maintain the last received Dupline output data no matter how long time has passed since the last telegram was received from the central master generato...

Отзывы: