36
Technical features
Housing
31
Dual phase system
32
38
38
Contact reading voltage:
12V < +Aux < 24VDC
Logic status:
OFF < 2V; ON > 10V.
Contact reading voltage:
15mA max.
Input impedance:
1k
Ω
Contact resistance:
≤
1k
Ω
close contact,
≥
100k
Ω
open
contact
Insulation:
by means of optocouplers, 2000 V
RMS
between
digital inputs and measuring inputs, 2000 V
RMS
between
digital inputs and power supply input.
■
Software functions
Password:
numerical code of max. 3 digits; 2 protection
levels of the programming data:
1st level Password “0”, no protection;
2nd level Password from 1 to 1000, all data are protected.
Transformer ratio
CT:
from 1 to 5000
VT:
from 1.0 to 199.9 and from 200 to 1999
Note: the CT * VT ratio must never exceed 5000. The current
measuring inputs are able to manage the CTs with secondary
of 1A and 5A (the accuracy is anyway always referred to 5A).
Display:
up to 2 variables/page.
Page 1: kWh, kvarh
Page 2a: kWh (t
1
-t
2
-t
3
-t
4
), kvarh (t
1
-t
2
-t
3
-t
4
)
Page 2b: GAS m
3
day-time tariff, GAS m
3
night-time tariff
Page 2c: H
2
O m
3
, GAS m
3
Page 3: W
L1
Page 4: W
L2
Page 5: W
L3
Page 6: W
dmd
(power demand)
Errors:
Phase sequence, serial communication status,
wrong connection of current measuring inputs.