EM530/EM540 - User manual |23/11/2022 | CARLO GAVAZZI Controls SpA
15
Page title
Sub-menu
Description
Values
Default values Note
M bus
Pri Add
Primary address
1 to 250
0
M1 models
only
bAudrAtE
Baudrate
0.3 kbps
2.4 kbps
9.6 kbps
2.4 kbps
Output
Function
Function
Off
PuLSE (kWh+): pulse
output
linked to kWh+
PuLSE (kWh-): pulse
output
linked to kWh-
ALArM: linked to alarm
status
PuLSE (kWh+) O1 models
only
durAtion
Pulse duration
30 ms
100 m
30 ms
PuLSES
Pulse weight (pulses/kWh)
0.1/1/10/100/500/1000 1000
StAtuS
Output status
No (normally open)
Nc (normally closed)
ALARM
EnAbLE
Enable
YES/no
no
VAriAbLE
Monitored variable
kW
A
V L-N
V L-L
PF
Kvar
kVA
kW
SEt 1
Activation threshold
-15000 to 15000
0.00
Set 2
Deactivation threshold
-15000 to 15000
0.00
dELAY
Activation delay
0 to 3600 s
0
dISPLAY
LiGHt
Timer for backlight switch-off
On: always on
1 min
2 min
5 min
10 min
15 min
30 min
60 min
oFF: always off
On
SC SAVEr
Screensaver enabling, see
"Screensaver" on page 21
oFF
SLidE: slideshow
home: homepage
home
Non-MID
models only
HOME
homepage
1 to 27
1
Non-MID
models only
PAGES
Measurement page filter
enabling, see "Page filter" on
page 21
ALL
FiLtEr
OFF
WirinG
Wiring check enabling
on/OFF
on
PASS
Password enabling for the
SETTINGS and RESET menu
0 (not protected) to
9999
0 (NOT
PROTECTED)
End
-
Exit
-
-
INFO menu
This menu allows to display the set parameters.
Page
Page title
Description
Notes
1
YEAr
Production year
2
SEriAL n
Serial number
3
FW REV
FW revision