SEAL THE COVER

•  Install the rubber filler into the 4" opening in the bottom 

of the cover as shown

  8

  

INSTALL THE AIR INLET

•  Using the screws provided, install the CAP System air 

inlet onto the back plate

  9

   Slide the connecting flange onto the air inlet until 

secure. 

10

   

Route the wire leads from the air inlet kit to the low 
voltage blocked vent (BV) contacts on the Pro-X 70200 
primary control 

11 

SETTING BLOCKED VENT + AIR INTAKE FEATURE 

The Pro-X 70200 Primary Control (manufactured  
Sept. 2018 or later) is equipped with a Blocked Vent – 
Air Intake feature. To activate this setting:
 •  Press     and     simultaneously for 2 seconds. This 

brings you to the settings menu. 

 •  Scroll through the different settings using      until you 

reach 

Vent Input

•  Scroll down to 

Intake using the     .

•   Press     

 / ENTER button. The display will briefly indi-

cate 

Vent Input has been “Entered” and has replaced 

any previous setting.

NOTE: If the Pro-X 70200 is also connected to a 

blocked exhaust switch, call Carlin Technical Support 
for assistance.

12

  

 Install 3" PVC vent pipe to provide outside air to the 
CAP System. 

IMPORTANT: For proper operation of the CAP System, 

air inlet piping should only use schedule 40 or 80 PVC 
pipe (maximum of 80' total with each elbow equal to 10').  
Combustion air outdoor termination, use PVC elbow 
(downward facing) and bird screen provided. Maintain 
12" clearance above highest anticipated snow level. 
Avoid locations where snow may drift and block com-
bustion air. Ice or snow may cause boiler to shut down 
if combustion air becomes obstructed. Combustion air 
termination must be min. 12" from or below doors, win-
dows or gravity inlet. USE SWEEP ELBOWS FOR ALL 
COMBUSTION AIR PIPING. DO NOT USE short radius 
elbows for combustion air piping – boiler performance 
could be affected.

13

   

Mount the cover by aligning the two holes on the top 
flange of the cover with the mounting tabs on the back 
plate. Tighten the mounting screw, located in the center 
of the cover, securely to prevent basement air from 
entering the cover.

14

 

  

CHECK BURNER SETUP 

Use the table below to set the combustion settings 
based on outside temperatures at the time of setup.

CAP System utilizes outside air for combustion.  
Incoming air temperature will fluctuate by season  
which can significantly impact combustion.  
Use below chart to ensure proper setup.

Incoming combustion  

air temperature

during setup

CO

2

 min CO

2

 max

O

2

 max

O

2

 min

–20°F to 0°F

10.2%

11.0%

7.0%

5.8%

5°F to 30°F

11.0%

11.5%

5.8%

5.5%

35°F to 60°F

11.5%

12.2%

5.5%

4.2%

65°F or higher

12.0%

12.5%

4.6%

3.9%

HORIZONTAL or VERTICAL

3