CAP System Operation

The CAP System is designed to shut down the burner in the 
event the outside combustion air supply becomes blocked. At 
each burner startup, the system will check the air intake during 
pre-purge (Valve Delay On*). If the air is blocked, the control 
will abort ignition and shutdown the burner. If the air intake is 
not blocked during this startup test, but becomes blocked dur-
ing normal burner operation, the burner will shut down if the air 
remains blocked for 20 seconds. Following any shutdown, the 
burner will be permitted to recycle 3 times following a 1 minute 
delay. The system will lock out the burner if the blockage con-
tinues throughout 3 recycles during any single call for heat.
** If the Burner has no valve, the air intake cannot be checked 

during pre-purge. In this case, the burner will shut down 

following the 20 second blockage described above. For all 

burners with valves, Valve Delay settings of less than 15 Sec-

onds will be automatically changed to 15 Seconds to allow 

for the prepurge test.

Getting Started

1

  

Ensure you have the right CAP System Kit for your applica-
tion by confirming the firing rate (in GPH) with the table on 
page 1.

IMPORTANT: If you change the firing rate, pressure switch-

es are available separately to convert the CAP System after 
installation. (See instructions for Installing Pressure Switch 
on page 4).

2

   

Ensure that the burner is  
equipped with a Carlin Pro-X  
70200 primary control with  
low voltage blocked  
vent (BV) terminals as shown.  

NOTE: 70200 controls 

manufactured prior to  
Sept. 2018 are not compatible  
with the CAP System.

3

  

INSTALLING BACK PLATE

 

(for uncovered burners) 

• Install the two mounting screws as shown 
•  Reroute the burner wire harness through the air inlet 

knockout in the back plate 

4

 

 ROUTE THE OIL 

•  The oil line must enter the burner cover through one of 

the knockouts in the back plate. 

5

  

REMOVE AIR INLET KNOCKOUT

 

•  Remove the 2" x 4" air inlet knockout that corresponds 

to the desired air inlet position (vertical or horizontal) as 
shown in step 8.

6

  

SEAL THE BACK PLATE 

To prevent basement air from entering the cover, all holes 

on the back plate must be sealed. 

•  Install the filler plate below the burner air tube using the 

two 5/16" bolts provided. Use the plastic rivets at the 

bottom corners of the filler plate to properly align the filler 

plate with the burner back plate. 

•  Install the split grommet around the burner wire harness
• Install the split grommet around the oil line
•  Fill the 1/4" and 7/8" holes in the back plate with plugs 

provided 

2

Pressure Switch Conversion

Firing Rate GPH

Pressure Switch

0.50-1.00

50806A

1.05-1.45

50806B

1.50-1.90

50806C