MN99102  042015

– 14 –

Model 99FRD, 102CRD & EZ-66 Oil Burners — Instruction Manual

4.  Adjustment and Verification

Adjust burner using test instruments

1.  Operate burner for 15 minutes before making final adjustments using 

test equipment.

2.  Check for leaks in fuel  piping.

  Inspect fuel piping system for leaks. Repair any leaks to avoid 

fire hazard from oil leakage or combustion problems due to 
air infiltration into oil.

3.  Inspect flame
•  Look  at  flame  through  appliance  combustion  chamber  observation 

port. The flame should be well-defined and should not impinge on any 
appliance surface. (If you make air changes later, inspect the flame 
again.)

  Do not attempt to confirm combustion simply by inspecting 

the flame visually. You must use combustion test instruments. 
Failure to properly verify/adjust combustion could allow unsafe 
operation of the burner, resulting in severe personal injury, 
death or substantial property damage.

1.  Insert test probe into vent sample opening to sample flue products.
2.  With the 99FRD, EZ-66 or 102CRD burner equipped with the correct oil 

nozzle, head setting and air band setting, the flue products will usually 
contain between 11½% and 12½% CO

2

  (5.9% and 3.8% O

2

) and zero 

(Bacharach) smoke.

3.  Use combustion test equipment to verify that burner is properly set up 

for your installation, within the range listed in Table 3. Appliances with 
positive pressure in the chamber may require a wider air opening. See 
appliance instructions for details. Verify/adjust settings by testing with 
instruments.

a.  Check smoke. It should be zero on the Bacharach scale.
b.  Set the appliance flue damper or barometric draft regulator so the draft or 

pressure in the vent complies with the appliance manufacturer’s instruc-
tions.

  Heating units designed for natural draft operation are normally 

set for a slightly negative pressure, usually –0.01 to –0.02 
inches w.c. draft at the combustion chamber test port. Ap-
pliances designed for forced draft (positive pressure in the 
chamber) must be air-tight to prevent exfiltration of harmful 
combustion products. Failure to properly set draft for the 
appliance could result in severe personal injury or death.

c.  Check percent of CO

2

 (or O

2

). Fine tune the burner, if necessary, by slightly 

adjusting the head position for more or less air.

d.  Recheck smoke (should be zero) and flue or chamber pressure/draft (adjust 

if necessary and retest).

  All installations should be checked after one to two weeks of 

operation to ensure the appliance/burner units are operating 
correctly.

Figure 16  Maximum firing rate decreases as overfire 

pressure increases

Firing against positive overfire pressure

1.  Burner rating maximum inputs are based on operation with zero to 

slightly negative pressure overfire, typically 0.01 to 0.03 inches w.c.

2.  When a burner is applied to an appliance that operates with a higher 

pressure overfire, the maximum firing rate decreases because the 
maximum available air flow from the burner blower decreases.

3.  Read the graph below in Figure 16 to find the maximum burner firing 

rate at positive overfire pressures.

  Do not apply a 99FRD, EZ-66 or 102CRD burner at a pres-

sure higher than listed in Figure 16 unless the application 
has been factory pretested.

Содержание 102CRD

Страница 1: ...formation regarding operation of this burner The burner Instruction Manual is intended only for your service technician The burner and heat exchanger must be inspected and started at least annually by...

Страница 2: ...pliance per this manual and the appliance instructions see User s information To keep this manual at or near the burner appliance for ready ac cess by the user and service technician To contact the se...

Страница 3: ...ng GPH 0 50 to 3 00 2 00 to 3 50 3 00 to 4 50 Delavan Hollow 60 A Delavan Solid 60 B Hollow 70 A Solid 70 B Hago Hollow 60 H Solid 80 B Hollow 70 H Hago Semi solid 45 SS Monarch Hollow 60 NS Semi soli...

Страница 4: ...ning sizes are always given in free area This means after deduction for louver obstruction If you can t find the louver reduction for the grilles used assume free area is 20 of total for wood louvers...

Страница 5: ...sary clearances to combustible construction including the correct design of thimbles and insulation where penetrating combustible walls Illustrations A to F in Figure 1 show different chamber configur...

Страница 6: ...a diameter at least as larger as the minimum width listed For steel cylinder chambers increase this dimension by from 1 to 4 inches 4 Wing walls are not recommended Corbels can be beneficial to heat...

Страница 7: ...t flange if needed 7 The end of the air tube should be flush or almost flush with the inside of the combustion chamber wall 8 Verify the air tube is level and inserted the correct depth Adjust if nece...

Страница 8: ...s are intended only for negative overfire pressure For pressur ized firing you must obtain a burner with a welded flange designed for use with the specific appliance Failure to comply could result in...

Страница 9: ...ng from the housing Replace the gasket if not in good condition 9 Inspect the ignitor contact clips Clean or replace if necessary to ensure reliable contact with the electrodes Install nozzle check el...

Страница 10: ...retention ring clamp is firmly against the nozzle adapter shoulder Set initial burner air settings Combustion head 1 The combustion head adjusting slide controls the spacing between the retention ring...

Страница 11: ...15 20 0 20 0 20 0 1 25 1 70 2 2 15 2 60 4 0 4 75 2 3 20 2 3 65 5 5 4 5 80 3 25 3 70 5 10 5 100 4 5 70 4 100 6 45 6 100 6 100 5 100 8 65 7 100 6 7 100 9 100 8 100 11 100 10 102CRD 2 air cone B style a...

Страница 12: ...d installed and that the fuel flow is unob structed the oil tank is clean and only 1 or 2 heating oil are supplied Failure to supply a reliable oil flow could result in loss of heat and potential seve...

Страница 13: ...lation air openings and vent system o Fuel supply line in good condition and sized designed correctly o Oil tank has oil and oil line valves are open o Wiring installed per burner appliance instructio...

Страница 14: ...ents a Check smoke It should be zero on the Bacharach scale b Set the appliance flue damper or barometric draft regulator so the draft or pressure in the vent complies with the appliance manufacturer...

Страница 15: ...manual with the user Verify the user is aware of all procedures specified in the manuals Verify user will not store or use combustible liquids or materials or contaminants in the vicinity of the burn...

Страница 16: ...21998S 102CRD 7 C Air Tube Combustion Head Assy 22004S 102CRD 9 C Air Tube Combustion Head Assy 21915S 102CRD 11 C Air Tube Combustion Head Assy 4 41000S 110V Ignitor 41000S0CAS 110V Ignitor on Basepl...

Страница 17: ...arts continued ITEM PART NO DESCRIPTION 99FRD 100CRD 102CRD 17 70200S Universal Primary w Display 70200 48245S Model 48245 Primary w Smart Ignition 4020002S Model 40200 Primary 30 15 30 5020002S Model...

Страница 18: ...time you replace a component or disassemble any part of the burner for service maintenance perform a complete operational test after reassembly to verify the burner operates correctly Failure to veri...

Страница 19: ...MN99102 042015 19 Model 99FRD 102CRD EZ 66 Oil Burners Instruction Manual...

Страница 20: ...ttempt to use gasoline as a fuel for this burner as it is more combustible and could result in a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating oil ASTM D396...

Отзывы: