2.0 POSITIONING
Before proceeding with the positioning of the boiler, make sure that the installation room is suitable. It is forbidden to place
the generator inside fi re risk rooms. The installation of the boiler is allowed only in
a specifi c room that complies and
is compatible with the nature of the equipment itself (technical room).
ATTENTION!
It is mandatory that the boiler installation room has a support surface (fl oor slab) with load-bearing capacity suitable to bear
the overall weight of the equipment. Should the construction not meet this requirement, take appropriate measures.
Also check that the walls of the room are fi reproof.
The boiler installation room must be equipped with an adequate air vent as specifi ed in the standard
UNI EN 303-5
.
Ensure a pressure difference of 4 Pa or less between the external and internal environment.
The air vent must be:
• protected by an anti-insect grid;
• made in such a way as to gurantee maintenance;
The ventilation of the installation room can also be obtained through an adjacent room (indirect ventilation) as long as it en-
sures free fl ow through the permanent openings communicating with the outside. In these cases, the adjacent room cannot be
used as a garage or warehouse for combustible material and, more generally, for any fi re risk activity.
min 60
0 mm
min 1000 mm
min 1000 mm
min 800 mm