“Ultrasound for fancoil” +0300059PT - rel. 1.6 - 06.10.2020
10.4 Read-only parameters
Parameter
UOM
range
def
note
d0
Th probe temperature reading
°C/°F
0-1000
0
d1
Th probe humidity reading
%rH
0-1000
0
d2
Configurable input reading (optional card)
% / %rH
0-100
0
d3
Tank operating hour counter (resettable, see "Reset
hour counter from display")
h
0-9999(*)
0
d4
Unit hour counter (read-only)
h
0-9999(*)
0
d5
Instant production
%
0...100
0
d6
Time remaining to end of piezoelectric transducer life
h
0...9999(*)
9999 equal to AF - piezoelectric transducer hour counter
d7
Manage secondary unit production
-
0...1
0
R/W parameter:
0 = the secondary exactly replicates the production of the main, as it depends
on the setting of parameter P0 on the main;
1 = the secondary produces according to the request sent by the main and its
own P0 setting; it is not affected by the setting of P0 on the main
d8
Dew point temperature
°C/°F
0…1000
0
calculated using d0 and d1
Tab. 10.e
(*) after 999 the display shows
to indicate the 1000s (the three digits are displayed with a dot at the top between the first and second digit).
11. HUMIDIFIER CONTROL VIA NETWORK
The variables shown in the list are a set of all the internal variables.
DO NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLE, OTHERWISE
HUMIDIFIER OPERATION MAY BE AFFECTED.
The serial connection (M11) is configured by default with the following parameters:
- Address 1
- Baud rate 19200 bps
- Frame 8,N,2
(not modifiable)
NOTICE:
it is recommended to set on the supervisor (main) the maximum waiting time for a response from humiSonic - after being queried by the supervisor - of
at least 500 ms.
11.1 Supervisor variable list
“A”
analogue variables* (Modbus®: REGISTERS)
R/W
CAREL - Modbus®
1
0
param. d0: Th probe temperature reading
R
2
1
param. d1: Th probe humidity reading
R
3
2
param. d2: Probe reading
R
4
3
param. d5: Instant production
R
9
8
param. d8: Dew point temperature
R
“I”
integer variables (Modbus®: REGISTERS)
R/W
CAREL
Modbus®
1
128
Level access password
R/W
7
134
Humidifier status
0=disabled/standby
1=autotest
2=initialisation
3=fill
4=production
5=drain
6=reset alarms
7=washing
8=cleaning procedure
R
2
129
Firmware release
R
15
142
Alarms, refer to Chap.ALARMS:
• bit0: Alarm E0
• bit1: Alarm Et
• bit2: Alarm EF
• bit3: Alarm Ed
• bit4: Alarm EP
• bit5: Alarm PU
• bit6: Alarm H ¯
• bit7: Alarm H_
• bit8: Alarm EE
• bit9: Alarm CL
• bit10: Alarm ES1
• bit11: Alarm ES2
• bit12: Alarm ES3
• bit13: Alarm OFL
• bit14: Alarm EL
• bit15: Alarm EtL
R/W
20
147
Parameter A0: Operating mode
R/W
21
148
Parameter A2: Type of external probe
R/W
22
149
Parameter A3: Probe minimum
R/W
23
150
Parameter A4: Probe maximum
R/W
24
151
Parameter A5: Probe offset
R/W
25
152
Parameter A6: Fan off delay time
R/W
26
153
Parameter A7: Fan speed
R/W
27
154
Parameter A8: Maximum evaporation time for no production alarm
R/W
28
155
Parameter A9: Minimum evaporation time for no production alarm
R/W
29
156
Parameter b0: Operating options
R/W
30
157
Parameter b1: Time between two washing cycles
R/W
31
158
Parameter b2: Inactivity time for washing on next start
R/W
32
159
Parameter b3: Washing time (fill + drain)
R/W
33
160
Parameter b4: Start delay time
R/W
34
161
Parameter b5: Operating hours for CL alarm
R/W
35
162
Parameter b6: Time to display new CL alarm in minutes
R/W
36
163
Parameter b7: Transducer On/Off control interval
R/W
37
164
Parameter b8: Probe delay disconnected
R/W