59
M
ask index
Displa
y Description
Description
Default
UOM
V
alues
Daf01
Number of pr
esent fans
Number of fans (line 1)
3
---
0…16
Daf02
Fan1, F
an2, …
Enable fans 1 t
o
12 (line 1)
AB
---
DIS / AB
Daf03
Fan13, F
an14, …
Enable fans 13 t
o
16 (line 1)
AB
---
DIS / AB
Daf04
Refr
igerant t
ype
Type of r
efr
igerant (condenser line 1)
R404A
---
R22 - R134a - R404A - R407C
- R410A - R507A - R290 - R600
- R600a - R717 - R744 - R728 -
R1270 - R417A - R422D
Daf05
D
e
vices r
otation t
ype
Type of r
otation devices (condenser line 1)
FIFO
---
------
FIFO
LIFO
TEMPO
CUST
OM
Daf07, Daf08
C
ust
om r
otation
Swit
ch ON or
der
Swit
ch ON or
der f
or fans with cust
om r
otation (condenser line 1)
1
---
1…16
Daf09, Daf10
C
ust
om r
otation
Swit
ch OFF or
der
Swit
ch OFF or
der f
or fans with cust
om r
otation (condenser line 1)
1
---
1…16
Dag01
M
odulat
e speed device
Fan dr
iv
er t
ype (line 1)
NONE
---
NONE
INVE
TER
PHASE C
ONTR
OL
Dag02
Neutral z
one r
e
g
.
Fan contr
ol also inside Neutral z
one (line 1)
NO
---
NO /
YES
M
in.out value
M
inimum v
oltage f
or compr
essor in
ve
rt
er (line 1)
0.0
V
0.0…9,9
M
ax.out value
M
aximum v
oltage f
or compr
essor in
ve
rt
er (line 1)
10.0
V
0.0…99,9
M
in. pow
er r
e
fe
r.
M
inimum capacit
y of fan modulating device (line 1)
60
%
0…100
M
ax. pow
er r
e
fe
r.
M
aximum capacit
y of fan modulating device (line 1)
100
%
0…999
Dag03
R
ising time
Time t
o
pass fr
om min capacit
y t
o
max capacit
y f
or fan modulating
device (line 1)
1200
s
0…32000
Falling time
Time t
o
pass fr
om max capacit
y t
o
min capacit
y f
or fan modulating
device (line 1)
1200
s
0…32000
Num.contr
ol
.fans
Number of fans under in
ve
rt
er (only f
or alar
m enabling)
1
---
0…16
Dag04
Split C
ondenser
Enable split condenser (line 1)
NO
---
NO /
YES
C
ontr
olled by
:
-Dig
ital input
Split C
ondenser contr
olled by dig
ital input (line 1)
---
---
NO /
YES
-Ex
te
rnal t
emp
.
Split C
ondenser contr
olled by outside t
emperatur
e (line 1)
---
---
NO /
YES
-Scheduler
Split C
ondenser contr
olled by scheduler (line 1)
---
---
NO /
YES
Dag05
Est.
Temp
.Thr
.
Split condenser by outside t
emperatur
e management setpoint
(line 1)
10.0 °C
…
-99,9…99,9
Est. T
emp
.Diff
.
Split condenser by outside t
emperatur
e management diff
er
ential (line 1)
2,5 °C
…
-99,9…99,9
Dag06
Type
Fans enabled with split condenser (line 1)
CUST
OM
---
CUST
OM
ODD
E
VEN
GREA
TER THAN
LESS THAN
---
Only when enabling t
ype is GREA
TER
THAN or LESS
THAN, number of
fans t
o
consider f
or splitting (line 1)
0
---
0…16