23
+05C003290 - 1.5 - 09.09.2008
english
• use the
↓↑
buttons to select the desired value, and confirm by pressing the
џ
button. If the value selected is
different than the value saved previously, the screen shown below will be displayed, and the new value will be
saved to permanent memory.
Display address
changed
If the field nn is set to the value 0, the terminal will communicate with the pCO
3
controller using the “point-to-
point” protocol (not pLAN) and the “I/O Board address: xx” field will not be displayed, as it no longer has meaning.
pCO
3
: assigning the list of private and shared terminals
At this stage, to modify the list of terminals associated with each individual pCO
3
board, proceed as follows:
• enter configuration mode by pressing the
↓↑
џ
buttons, as described in the previous paragraph;
• press the
џ
button until the cursor reaches the field xx (I/O board address) ;
• use the
↓↑
buttons to select the desired address of the pCO
3
board. The values that can be selected refer to
the pCO
3
boards that are effectively on line. If the pLAN network is not operating correctly, or alternatively no
pCO
3
board is connected, the field will not be able to be modified and will only show “—”;
• pressing the
џ
button again displays the following screens in sequence:
Terminal Config
Press ENTER
to continue
P12:Adr Priv/Shared
Trm1 02 Sh
Trm2 03 Pr
Trm3 None --OK?NO
• here too the
џ
button moves the cursor from one field to another, and the
↓↑
buttons change the value
of the current field. The field P:xx shows the address of the board selected; in the example shown in figure, the
address 12 has been selected;
• to exit the configuration procedure and save the data, select the field “OK ?” and set to Yes, then confirm by
pressing the
џ
button.
The fields in the “Adr” column represent the addresses of the terminals associated with the pCO3 board address
12, while the Priv/Shared column indicates the type of terminal.
Important: the pGD terminals cannot be configured as “Sp” (shared printer), as they do not have the printer
output.
If the terminal remains inactive (no button pressed) for more than 30 seconds, the configuration procedure is
automatically ended without saving any changes.
NOTES ON USING WINLOAD, BOOT AND BIOS
The most recent version of WinLoad should always be used. Management of the pCO
3
is supported by WinLoad
version 3.35.
From version 3.36, the download speed for the Bios and the application to the pCO
3
has been increased to 115200
bit/s from the standard speed of 28800 bit/s, however this change does not require any new settings by the user.
The pCO
3
BIOS and the BOOT are specific files, and different from the pCO
1
and pCO
2
BIOS and BOOT files.
Consequently, these cannot be loaded onto the pCO
3
, and, obviously, the pCO
1
and pCO
2
BOOT and BIOS cannot
be loaded onto the pCO
3
.
IMPORTANT WARNINGS
The REHAU product is a state-of-the-art product, whose operation is specified in the technical documentation
supplied with the product or can be downloaded, even prior to purchase, from the website www.rehau.com.
The client (builder, developer or installer of the final equipment) assumes every responsibility and risk relating to the
phase of configuration the product in order to reach the expected results in relation to the specific final installation
and/or equipment. The lack of such phase of study, which is requested/indicated in the user manual, can cause the
final product to malfunction of which REHAU can not be held responsible.
The final client must use the product only in the manner described in the documentation related to the product
itself.